MODULEX CONTROLLER OPERATION
21
Table 3-3. EXPERT Menu Listing -
Continued
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
SOLAR M/F Sub-Menu
MF (1-4)
FUNCTION
Not Applicable
MF (1-4)
SET TEMP
Not Applicable
MF (1-4)
HYST (1-4)
Not Applicable
F15 FUNCTION
F15 Function
00 = Room Sensor for Heating Circuit 2
01 = 0
– 10V Input
02 = Light sensor
00 -02
00
RETURN
Press Program Key to exit SOLAR M/F Sub-
Menu.
3.5.1 Available V-Curve Preset Voltage Curves for 0
– 10 Volt Input
The following listing shows the available preset V-Curve settings for operation in the 0 to 10 Volt Mode:
CURVE NO.
U1
U2
T1
T2
UA
0
2.0 V
10.0 V
32°C
194°C
2.0 V
1
2.5 V
0.3 V
100°C
176°C
5.0 V
2
2.5 V
0.3 V
100°C
167°C
5.0 V
3
2.5 V
0.3 V
100°C
113°C
5.0 V
4
4.0 V
0.1 V
68°C
185°C
5.0 V
5
4.0 V
0.1 V
68°C
167°C
5.0 V
6
4.0 V
0.1 V
68°C
131°C
5.0 V
7
4.0 V
0.1 V
68°C
189°C
5.0 V
8
4.0 V
0.1 V
68°C
189°C
5.0 V
9
4.0 V
0.1 V
68°C
163°C
5.0 V
10
4.0 V
0.1 V
68°C
127°C
5.0 V
11
4.0 V
0.1 V
68°C
194°C
5.0 V