MODULEX CONTROLLER OPERATION
20
Table 3-3. EXPERT Menu Listing -
Continued
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
HEAT CIRCUIT 1 & 2 Sub-Menus
The Sub-Menu Functions for HEAT CIRCUIT
1 & HEAT CIRCUIT 2 are identical, except for
the MIXER OPEN & MIXER CLOSE
Functions which apply only to HEAT CIRCUIT
1. The Function values in this Sub-Menu level
will change, depending on the Heat Circuit
Function (HC FUNCTION) selected.
HC FUNCTION
Heat Circuit Function defines type of circuit:
00 = Standard Heat Circuit
01 = Control to fixed flow temperature
02 = Swimming pool control (HC 2 ONLY)
03 = Hot Water Circuit
04 = Return flow temp. increase via mixing
valve.
00
– 04
00
(Standard
Heat Circuit)
PUMP MODE
Circulation pump mode control for ON/OFF
switching of pumps.
00 = Standard pump control
01 = Pump switching per heating limits
02 = Pump switching per heating program
03 = Continuous pump operation
00 - 03
00
MIXER OPEN
Not Applicable
MIXER CLOSE
Not Applicable
MAX T-FLOW
Maximum allowable water temperature setting
for the heating circuit.
20.0
°
C
–
110.0
°
C
80.0
°
C
MIN T-FLOW
Minimum allowable water temperature setting
for the heat circuit.
10.0
°
C
–
110.0
°
C
10.0
°
C
T-FROST PROT
Specifies the minimum allowable outside air
temperature setting for the Frost Protection
Mode. If temperature drops below this value,
the system switches to the Frost Protect Mode
and the pumps are switched ON.
(This Function should be set to 0°C in the
INSTALLATION Mode)
-20.0
°
C
–
5.0
°
C
0.0
°
C
OUT-TEMP-DEL
Not Applicable
N/A
N/A
SLOPE OFFSET
Not Applicable
N/A
N/A
B-HEAT SINK
Not Applicable
N/A
N/A
RETURN
Press Program Key to exit HEAT CIRCUIT 1
(or 2) Sub-Menu
.
Содержание Modulex E8
Страница 1: ...Operation User Guide Modulex E8 Controller ...
Страница 30: ...MODULEX CONTROLLER OPERATION 28 Figure 3 7 INSTALLATION Menu Flow Chart ...
Страница 50: ......
Страница 51: ...MODULEX CONTROLLER OPERATION A 1 APPENDIX A CONTROLLER MENU LISTINGS ...
Страница 69: ...A 19 MODULEX CONTROLLER OPERATION NOTES ...