MODULEX CONTROLLER OPERATION
A-14
EXPERT PROGRAM MENU TABLE -
Continued
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
HEAT CIRCUIT 1 & 2 Sub-Menus
- Continued
B-HEAT SINK
Circuit Enable
00 = OFF
01 = ON
01 (ON)
RETURN
Press Program Key to exit HEAT CIRCUIT 1
(or 2) Sub-Menu
.
SOLAR M/F Sub-Menu
MF (1-4)
FUNCTION
Multi-Function (MF) Relay Functions.
00 = No Function
01 = Header Pump
02 = Circulation (Time)
03 = Booster Pump
05 = Pump HS1
06 = Pump HS2
20 = Temp-Controlled Circulation Pump
21 = Pulsed Circulation Pump
22 = Solid Fuel Boiler Integration
23 = Solar Integration
24 = Return Flow Temperature Increase HS1
25 = Return Flow Temperature Increase HS2
26 = Return Flow Temperature Increase HS
Via Buffer Storage
00, 01, 02, 03,
05, 06 & 20-26
00
(No
Function)
MF (1-4)
SET TEMP
Multi-Function Relay Set Point Temperature
indicates switching temperature for relay
30°C
– 90°C
30°C
MF (1-4)
HYST (1-4)
Multi-Function Relay Hysteresis
2°C
– 10°C
5°C
F15 FUNCTION
F15 Function
00 = Room Sensor for Heating Circuit 2
01 = 0
– 10V Input
02 = Light sensor
00 -02
00
RETURN
Press Program Key to exit SOLAR M/F Sub-
Menu.