MODULEX CONTROLLER OPERATION
18
Table 3-3. EXPERT Menu Listing -
Continued
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
- Continued
HYSTERESIS
Not Applicable
FOUND MODULS
Displays the number of heat modules
available for service.
display
CAP/MODULE
Displays the maximum kW output of each
heat module. SuperModulex
00 - 1000 kW
40 kW
NEW CONFIG
Not Applicable
MIN MOD CASC
Not Applicable
01 - 08
01
HW-BOILER
Not Applicable
00 - 08
00
CONTR DEVIAT
Control Deviation indicates the temperature
difference between the Boiler set point and
the actual water temperature.
display
°C
DES OUPUT
Required system output [in %]
0 - 100%
00
SWITCH TIME
Not Applicable
(N/A)
(N/A)
BLOCK TIME
Not Applicable
(N/A)
(N/A)
MAX T-MODUL
Maximum temperature of Heat Module
50.0°C to
110.0°C
90.0°C
DYN UPWARD
Not Applicable
(N/A)
(N/A)
DYN
DOWNWARD
Not Applicable
(N/A)
(N/A)
RESET TIME
Not Applicable
5 - 500
50
MODULAT MAX
Start Level. If this modulation percentage is
exceeded, the next heat module is connected
after the delay time elapses.
50% - 100%
30%
MODULAT MIN
Stop Level. If value drops below this
modulation percentage, the last heat
generator (module) of the current sequence is
switched off
10% - 60%
35%
MIN MOD HS
Not Applicable
0% - 60%
35%
MOD LEVEL HW
Not Applicable
SEQUENCE 1
Boiler sequence 1
12345678
SEQUENCE 2
Boiler sequence 2
87654321
Содержание Modulex E8
Страница 1: ...Operation User Guide Modulex E8 Controller ...
Страница 30: ...MODULEX CONTROLLER OPERATION 28 Figure 3 7 INSTALLATION Menu Flow Chart ...
Страница 50: ......
Страница 51: ...MODULEX CONTROLLER OPERATION A 1 APPENDIX A CONTROLLER MENU LISTINGS ...
Страница 69: ...A 19 MODULEX CONTROLLER OPERATION NOTES ...