Assembly Instructions 

 Spindle Drive SP -24 V / 230 V  

9000002601.doc 

Page

 33 

of

 34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Avoiding risk situations 

  

 

Make sure that the  
power-operated 
window can move freely and 
does not clash with any  
fixed parts (e.g. wall…..). 
 
 

Window casement 
stability / safety 
 

 

Casements must be hung or secured such way that, in case one 
of the mounting elements fails, it will not break away from the 
frame and fall to the ground or have unintended movements by 
providing double suspensions, safety scissors, casement stays. 

Inward and outward opening bottom-hung casements must be 
provided with safety scissors / casement stays.  
They prevent damage if the drive breaks down.

 

The safety stays should be selected to suit the opening width and 
the mechanical features of the window as intended. 
They must not restrict the drive stroke.

 

 

Also refer to the „Guidelines 
for power-operated windows, 
doors and gates” (BGR 232) 
and to the ZVEI Brochure „SHEV News,  
No. 3, Power-operated windows“ 
 

 

Cable routing and 
electrical connection

               

      

 

Before working on the system the mains 

voltage supply and the batteries shall be disconnected in all 
poles. Never operate the drives, controllers, manual switches and 
sensors on operating voltages and connections contrary to the 
specifications in the operating instructions. 
There is danger to life and it may result in the destruction of the 
components!  
Cable routing and electrical connections may only be carried out 
by qualified electricians. Secure power supply lines 230 / 400V 
AC separately on site. The installation requires compliance with 
the relevant laws, regulations, guidelines and standards such as 
the Model Wiring Guideline (MLAR/ LAR/ RbALei), the VDE0100 
“Erection of power installations with rated voltages below 1000V”, 
VDE 0815 “Installation cables and wires”, VDE 0833 “Hazard  
alarm systems for Fire, Intruder and Hold-up”. Specify suitable 
types of cable on consultation with the competent local certifica-
tion authorities, energy supply companies or fire protection

 

au-

thorities, if necessary.

  

Extra low-voltage lines (e.g. 24 V DC) must be laid separately 
from low-voltage lines (e.g. 230 V AC). Flexible lines must not be 
flush-mounted. Freely suspended lines must be provided with 
strain

 

relief.

 

All lines must be laid such way that they can be nei-

ther sheared off, nor twisted or kinked during operation. 

 

All power supply connections, control units and junction boxes 
must be accessible for maintenance work. 
Select the types, lengths and cross-sections of the lines accord-
ing to the technical specifications. 
Check connection points for tight fit of the screwed connections 
and cable ends. 

A

Wall

Risk of entrapment

Mechanical and Electrical Safety 

Mounting and fastening material 
 

Required or supplied fastening material shall be se-
lected and, if necessary, supplemented to suit the 
building’s structure and the corresponding strain. 
 

 Crush and shear points 

Power-operated windows, doors and gates: the dan-
ger zones of crush and shear points, for example 
between casement and frame or light dome and metal 
curb must be secured by appropriate devices that will 
prevent any injury. 
 
Also refer to the „Guidelines for power-operated win-
dows, doors and gates” (BGR 232) and to the ZVEI 
Brochure „SHEV News, No. 3, Power-operated win-
dows“ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
Accident prevention regulations and guide-
lines issued by the employers’ liability 
insurance association 

 

  

When working at, in or on a building or part of a  
building the specifications and notes of the respective 
accident prevention regulations (UVV) and the regula-
tions and rules of the employers’ liability insurance 
association (BGR) must be observed and adhered to. 
 
 

Ambient conditions 

The product must not be hit, dropped or exposed to 
vibrations, humidity, aggressive gases or other dam-
aging environments unless it is approved for one or 
several of these ambient conditions by the manufac-
turer. 
 

23

 

Danger zones: Crush / shear points

Side-hung / 
vertically pivoting window

Bottom-hung / horizontally
pivoting window

Roof windows / light domes

Louvre windows

Safety scissors

Содержание SP 8 Series

Страница 1: ...ler gmbh de www aumueller gmbh de Aum ller Aumatic GmbH Gemeindewald 11 86672 Thierhaupten Germany 49 0 82 71 8185 0 49 0 82 71 8185 250 info aumueller gmbh de www aumueller gmbh de Assembly Instructi...

Страница 2: ...ormation are as correct and up to date as possible we still cannot guarantee that they are free from mistakes and errors All information and data contained in this document are subject to alterations...

Страница 3: ...e and for specific profile systems 16 Mounting brackets with thick clamping blocks 17 Mounting brackets with thin clamping blocks 18 Mounting brackets with clamping bolt connection 19 Recommended Fixi...

Страница 4: ...rning notes in these instructions Failure to comply with the safety instructions warning notes results in irreversible injury or death Failure to comply with the safety instructions warning notes can...

Страница 5: ...from the homepage of Aum ller Aumatic GmbH www aumueller gmbh de It is essential to ensure compliance with the latest version of the guidelines standards and national legislation applicable to the as...

Страница 6: ...power consumption Required fastening material shall be selected and if necessary completed to suit the drive and the exerted loads Make sure that all products installed are permanently protected from...

Страница 7: ...Assembly Instructions Spindle Drive SP 24 V 230 V 9000002601 doc Page 7 of 34 Certificate 2...

Страница 8: ...Page 8 of 34 9000002601 doc Assembly Instructions Spindle Drive SP 24 V 230 V Declaration of Incorporation 2...

Страница 9: ...after activation from a control unit SHEV control unit or after triggering of a fire alarm button or smoke detector or trigger ing of the fire alarm unit Range of application Casement dimensions Case...

Страница 10: ...very many different kinds of window profile systems on the market Different mounting brackets and fastening devices to be used depend on the particular profile On the pages below you may find special...

Страница 11: ...Tilting range Supporting surface of bracket Supporting surface of bracket Structural factors obstacles e g jamb WARNING Storage of the drives on site prior to the assembly Protective measures against...

Страница 12: ...product features Silver anodized aluminium body E6 C 0 Robust aluminum spindle Maintenance free drive RAL colour finish possible Versions has disconnection via end switches and disconnection at overlo...

Страница 13: ...al description product features Silver anodized aluminium body E6 C 0 Robust aluminum spindle Maintenance free drive RAL colour finish possible Versions and Standard has internal disconnection via end...

Страница 14: ...extended spindle if unit suspended at rear Front suspension Rear suspension L L ength KLB Clamping area 2 3 KLB 1 3 KLB optional eye bolt for fixing Fixing with clamping bolt connection Observe speci...

Страница 15: ...ive to be used must be selected to suit the specified range of application appropriate stroke stroke force and installation length 3 Proper fastening accessories brackets casement brackets must be sel...

Страница 16: ...F 1 casement bracket with locking bolt 6 mm Max load 1000 N ord no 150102 F 2 casement bracket extruded aluminium for Eternit roof lights Max load 800 N ord no 150303 FXXX 8 F 11 casement bracket wit...

Страница 17: ...r clamping fitting with 2x 12 mm collar screws ord no 157500 6 5 x4 K 5 mounting bracket stainless steel V2A with 12 5 mm hole for clamping fitting with 2x 12 mm collar screws ord no 155800 12 14 G 1...

Страница 18: ...155610 6 5 x6 K 82 mounting bracket stainless steel V2A with 12 5 mm hole for clamping fitting with 2x 12 mm collar screws ord no 151320 7 20 36 G1 8 KS clamping block SP thin aluminum for mounting br...

Страница 19: ...ting bracket with 20 mm hole steel br zinc plated ord no 160930 steel RAL 9010 ord no 160933 6 5 x4 100 30 70 20 6 5 x4 5 K 9 mounting bracket aluminium E6 C 0 for mounting with various brackets ord n...

Страница 20: ...crews Metric screws with blind rivet nuts Thread self tapping or sheet metal screws such as Cylinder head with hex socket internal serration Torx Phillips or external hex head Blind rivet nut size M6...

Страница 21: ...e correct torque Fixation of brackets in guide of sliding link with clamping screws K5 2x KS thick 2 x BS K7 2x KS thin K82 2 x BS KVS K57 K57 2 K57 3 K59 K92 1 2 3 4 2 x KVS Fixation of brackets in g...

Страница 22: ...openings Adjustment possibility for disconnection loosen lock nut manually turn AS inward and or outward dependent on assembly tighten lock nut again ensure that drive shuts off via end switch and no...

Страница 23: ...0 1400 1600 1800 2000 2200 2400 2600 Abstand Antrieb Band mm ffnungswinkel DEG 1 Hubl nge 100mm 2 Hubl nge 200mm 3 Hubl nge 300mm 4 Hubl nge 400mm 5 Hubl nge 500mm 6 Hubl nge 600mm 7 Hubl nge 700mm 8...

Страница 24: ...w e g top hung projecting casement RA K82 M6 base plate set on site F10 6 FL M6 F1 RA FL Roof casement system SCH CO AWS 57RO outward opening on HSK K82 F10 6 Roof casement system FAKRO outward openin...

Страница 25: ...C T IT E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FG 16 Fit the casement bracket make sure it is parallel to the edge of...

Страница 26: ...f the window e g borehole intervals determined on site Dimensions for brackets see page 17 19 Hang drive in mounting brackets e K59 g for installation of bracket positioning fixing see page 21 22 Do n...

Страница 27: ...ut off via end switch see page 22 Route cable according to on site situation the cable must adapt to pivoting angle of the drive lay with strap Cable must be protected against damage such as shearing...

Страница 28: ...Check safety of assembled system Connect control voltage Check fasteners brackets mounting brackets and tighten as necessary Perform operational test Visual inspection of casement movements Immediatel...

Страница 29: ...DC BN BU Version with Z contact close 2 1 BK WH CLOSE 3 4 3 4 BK WH Switch position with spindle inside Contact load max 48V min 12V DC 10mA PVC cable 6 x 0 75mm with electronic end switches and overl...

Страница 30: ...drive cable A mm L A mm Example calculation Available figures 10m Drive current for each drive 2 x 0 8 A from data sheet Length of cable run from last window to control unit e g The number of wires r...

Страница 31: ...switch with OFF default setting min 1 5m Mount all manual controllers out of reach for unauthorized persons Instructions OPEN CLOSE Sign such as spindle chain rack and pinion Drive Target group This o...

Страница 32: ...motor controller relay Cables Copper Zinc Electrical devices and batteries cannot be disposed of as domestic waste Locking fittings Drive such as spindle chain rack and pinion Problem Possible Causes...

Страница 33: ...ertifica tion authorities energy supply companies or fire protection au thorities if necessary Extra low voltage lines e g 24 V DC must be laid separately from low voltage lines e g 230 V AC Flexible...

Страница 34: ...causes Improper use of the drive Improper assembly commissioning operation maintenance and repair of the drive Operating the drive with defective improperly installed or malfunctioning safety and pro...

Страница 35: ...Assembly Instructions Spindle Drive SP 24 V 230 V 9000002601 doc Page 35 of 34 Notes...

Страница 36: ...Engineering Service Systemtechnik Rauch und W rmeabzug Parkraum Management Kontrollierte nat rliche L ftung...

Отзывы: