Pre-assembly Checks

 

Checking Installation Requirements  

Depending on the place of installation / type of window and 
on the real structural conditions there are different installa-
tion requirements for the drives. 
They are obtained from the special installation sketches 
and/or planning drawings and have to be checked accord-
ingly.  
 
Generally the following should be checked first of all: 
 
- Are the supporting surface and the structural conditions  
  adequate for the load transfer? 
- Does the installation level require an additional supporting  
  structure? 
- Is there enough space for the pivotal motion of the drive? 
- Have sufficient measures been taken to avoid thermal  

  bridges (thermal separation) at the application points? 
  

 

If not, the operator must be notified of these require-
ments! 
 

Information on the Load Transfer 

of the drives to the window profiling:

 

The supporting surface of the brackets and casement 
brackets must fully rest on the window or frame profile, 
respectively.

 

Tilting movements of the mounting elements 

when

 

the spindel moves out are not allowed. Safe and firm 

mounting on the window profile must be ensured.

  

Insert underlay plates / brackets, if necessary. 
 

 

It is absolutely essential to take the drive tilting 
range into consideration. If this cannot be ensured, 
find mounting alternative or another type of drive. 

 

 

 

 

5

 

Important instructions for safe assembly! Fully observe all  
instructions! Incorrect assembly may lead to serious injuries! 

 230 V  

 

  

24 V

Tandem operation
(no synchronized)

Influence of forces other
than push or compression

F

outside

inside

Tilting range

    Supporting
surface of bracket

Supporting
surface of bracket

Structural factors
(obstacles)
e.g. jamb

!

 

WARNING

Storage of the drives on site prior to the assembly

Protective measures against damage, dust, humidity or 
contamination (for example caused by covers, film or card-
board packaging) must be taken.  
Only store the drives in dry and well ventilated places be-
fore installation.

 

 

Testing the drives prior to installation 

We recommend checking the drives prior to installation for 
their good mechanical condition and completeness.

 

Drives must run easily in both directions. We recommend 
the use of our test kit for drives in 24 V DC / 230 V AC 
(part no.: 533981). 
Never install and operate damaged 
products. Any damage must be  
reported immediately to the  
supplier / manufacturer. 
Drives must always be tested on  
a non-slip and stable surface or in 
a test fixture. 
During trial operation there should be no physical contact 
with the extending spindle. 

 

Instructions on Intended Use 

Ensure that the use of the drives is in accordance with the 
specified range of application / area of application. Any 
other use of the products causes loss of warranty. 
The end-user must be informed about the intended use of 
the drives.

 

In particular, it must be pointed out to the end-user that - 
apart from pressure and tensile forces in opening / closing 
direction - no additional forces

 

may impact on the drive 

spindle.  
Additional warning signs might be required.

 

 
Determining required safety measures in  
accordance with MD 2006/42/EC 

A risk assessment must be carried out in order to determine 
any required safety measures. Furthermore the  
operator must be notified of the remaining risks.  
(Separate documents are available from  
Aumüller Aumatic GmbH). 
 

Predictable Misuse  

It is absolutely essential to avoid any foreseeable misuse of 
the drives!    

 
Some examples:

 

 

Содержание SP 8 Series

Страница 1: ...ler gmbh de www aumueller gmbh de Aum ller Aumatic GmbH Gemeindewald 11 86672 Thierhaupten Germany 49 0 82 71 8185 0 49 0 82 71 8185 250 info aumueller gmbh de www aumueller gmbh de Assembly Instructi...

Страница 2: ...ormation are as correct and up to date as possible we still cannot guarantee that they are free from mistakes and errors All information and data contained in this document are subject to alterations...

Страница 3: ...e and for specific profile systems 16 Mounting brackets with thick clamping blocks 17 Mounting brackets with thin clamping blocks 18 Mounting brackets with clamping bolt connection 19 Recommended Fixi...

Страница 4: ...rning notes in these instructions Failure to comply with the safety instructions warning notes results in irreversible injury or death Failure to comply with the safety instructions warning notes can...

Страница 5: ...from the homepage of Aum ller Aumatic GmbH www aumueller gmbh de It is essential to ensure compliance with the latest version of the guidelines standards and national legislation applicable to the as...

Страница 6: ...power consumption Required fastening material shall be selected and if necessary completed to suit the drive and the exerted loads Make sure that all products installed are permanently protected from...

Страница 7: ...Assembly Instructions Spindle Drive SP 24 V 230 V 9000002601 doc Page 7 of 34 Certificate 2...

Страница 8: ...Page 8 of 34 9000002601 doc Assembly Instructions Spindle Drive SP 24 V 230 V Declaration of Incorporation 2...

Страница 9: ...after activation from a control unit SHEV control unit or after triggering of a fire alarm button or smoke detector or trigger ing of the fire alarm unit Range of application Casement dimensions Case...

Страница 10: ...very many different kinds of window profile systems on the market Different mounting brackets and fastening devices to be used depend on the particular profile On the pages below you may find special...

Страница 11: ...Tilting range Supporting surface of bracket Supporting surface of bracket Structural factors obstacles e g jamb WARNING Storage of the drives on site prior to the assembly Protective measures against...

Страница 12: ...product features Silver anodized aluminium body E6 C 0 Robust aluminum spindle Maintenance free drive RAL colour finish possible Versions has disconnection via end switches and disconnection at overlo...

Страница 13: ...al description product features Silver anodized aluminium body E6 C 0 Robust aluminum spindle Maintenance free drive RAL colour finish possible Versions and Standard has internal disconnection via end...

Страница 14: ...extended spindle if unit suspended at rear Front suspension Rear suspension L L ength KLB Clamping area 2 3 KLB 1 3 KLB optional eye bolt for fixing Fixing with clamping bolt connection Observe speci...

Страница 15: ...ive to be used must be selected to suit the specified range of application appropriate stroke stroke force and installation length 3 Proper fastening accessories brackets casement brackets must be sel...

Страница 16: ...F 1 casement bracket with locking bolt 6 mm Max load 1000 N ord no 150102 F 2 casement bracket extruded aluminium for Eternit roof lights Max load 800 N ord no 150303 FXXX 8 F 11 casement bracket wit...

Страница 17: ...r clamping fitting with 2x 12 mm collar screws ord no 157500 6 5 x4 K 5 mounting bracket stainless steel V2A with 12 5 mm hole for clamping fitting with 2x 12 mm collar screws ord no 155800 12 14 G 1...

Страница 18: ...155610 6 5 x6 K 82 mounting bracket stainless steel V2A with 12 5 mm hole for clamping fitting with 2x 12 mm collar screws ord no 151320 7 20 36 G1 8 KS clamping block SP thin aluminum for mounting br...

Страница 19: ...ting bracket with 20 mm hole steel br zinc plated ord no 160930 steel RAL 9010 ord no 160933 6 5 x4 100 30 70 20 6 5 x4 5 K 9 mounting bracket aluminium E6 C 0 for mounting with various brackets ord n...

Страница 20: ...crews Metric screws with blind rivet nuts Thread self tapping or sheet metal screws such as Cylinder head with hex socket internal serration Torx Phillips or external hex head Blind rivet nut size M6...

Страница 21: ...e correct torque Fixation of brackets in guide of sliding link with clamping screws K5 2x KS thick 2 x BS K7 2x KS thin K82 2 x BS KVS K57 K57 2 K57 3 K59 K92 1 2 3 4 2 x KVS Fixation of brackets in g...

Страница 22: ...openings Adjustment possibility for disconnection loosen lock nut manually turn AS inward and or outward dependent on assembly tighten lock nut again ensure that drive shuts off via end switch and no...

Страница 23: ...0 1400 1600 1800 2000 2200 2400 2600 Abstand Antrieb Band mm ffnungswinkel DEG 1 Hubl nge 100mm 2 Hubl nge 200mm 3 Hubl nge 300mm 4 Hubl nge 400mm 5 Hubl nge 500mm 6 Hubl nge 600mm 7 Hubl nge 700mm 8...

Страница 24: ...w e g top hung projecting casement RA K82 M6 base plate set on site F10 6 FL M6 F1 RA FL Roof casement system SCH CO AWS 57RO outward opening on HSK K82 F10 6 Roof casement system FAKRO outward openin...

Страница 25: ...C T IT E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FG 16 Fit the casement bracket make sure it is parallel to the edge of...

Страница 26: ...f the window e g borehole intervals determined on site Dimensions for brackets see page 17 19 Hang drive in mounting brackets e K59 g for installation of bracket positioning fixing see page 21 22 Do n...

Страница 27: ...ut off via end switch see page 22 Route cable according to on site situation the cable must adapt to pivoting angle of the drive lay with strap Cable must be protected against damage such as shearing...

Страница 28: ...Check safety of assembled system Connect control voltage Check fasteners brackets mounting brackets and tighten as necessary Perform operational test Visual inspection of casement movements Immediatel...

Страница 29: ...DC BN BU Version with Z contact close 2 1 BK WH CLOSE 3 4 3 4 BK WH Switch position with spindle inside Contact load max 48V min 12V DC 10mA PVC cable 6 x 0 75mm with electronic end switches and overl...

Страница 30: ...drive cable A mm L A mm Example calculation Available figures 10m Drive current for each drive 2 x 0 8 A from data sheet Length of cable run from last window to control unit e g The number of wires r...

Страница 31: ...switch with OFF default setting min 1 5m Mount all manual controllers out of reach for unauthorized persons Instructions OPEN CLOSE Sign such as spindle chain rack and pinion Drive Target group This o...

Страница 32: ...motor controller relay Cables Copper Zinc Electrical devices and batteries cannot be disposed of as domestic waste Locking fittings Drive such as spindle chain rack and pinion Problem Possible Causes...

Страница 33: ...ertifica tion authorities energy supply companies or fire protection au thorities if necessary Extra low voltage lines e g 24 V DC must be laid separately from low voltage lines e g 230 V AC Flexible...

Страница 34: ...causes Improper use of the drive Improper assembly commissioning operation maintenance and repair of the drive Operating the drive with defective improperly installed or malfunctioning safety and pro...

Страница 35: ...Assembly Instructions Spindle Drive SP 24 V 230 V 9000002601 doc Page 35 of 34 Notes...

Страница 36: ...Engineering Service Systemtechnik Rauch und W rmeabzug Parkraum Management Kontrollierte nat rliche L ftung...

Отзывы: