FAULT IND.
S1
NO FAULT
Table 11:
Description of the fault indications
Remedy
Description
Signal
No fault has occurred.
NO FAULT
For further information:
1.
Go to group
D0
: Press
C
and hold it
down until diagnostic indication
D0
is
displayed.
2.
Go to diagnostic indication
D2
: Press
twice.
Internal fault has occurred.
INTERNAL FAULT
Operation command in direction OPEN.
Torque fault in direction CLOSE.
TORQUE FAULT (CLOSE)
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button Reset.
Operation command in direction CLOSE.
Torque fault in direction OPEN.
TORQUE FAULT (OPEN)
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button Reset.
Test/connect phases.
One phase is missing.
LOSS OF PHASE
Cool down, wait.
Motor protection tripped.
THERMAL FAULT
If the fault indication display persists after
cooling down:
Set selector switch to position Local control
(LOCAL) or reset fault indication via push
button Reset.
Check fuse F4.
For further information:
1.
Go to group
D0
: Press
C
and hold it
down until diagnostic indication
D0
is
displayed.
2.
Go to diagnostic indication
D4
: Press
4 x.
The controls configuration is incorrect.
CONFIGURATION FAULT
10.2.3
Status indication S2 - warnings
Faults are indicated within the status indication
S2
:
WARNING IND.
S2
NO WARNINGS
Table 12:
Description of the warnings
Remedy
Description
Signal
No warnings have occurred.
NO WARNINGS
Set the operating time (
MONITOR TRIG-
GERS
parameter) in accordance with the
actual operating time.
Preset running time for a travel between end
position OPEN and end position CLOSED
has been exceeded.
WARNING OPER. TIME
Check tripping behaviour of end position
switches.
Verify actuator mechanics.
53
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
ACExC 01.1 Non-Intrusive
Corrective action