13. Enter password:
→
Press 4 x = 0000 (default factory password).
➥
EDIT
M1210
OPENING
CLOSING
BY-PASS DURATION
EDIT
M2111
OPENING
CLOSING
BY-PASS DURATION
Use and to select between
OPENING
and
CLOSING
.
14. Press .
➥
Display shows the set value:
EDIT
M1210
OPENING
100%
:EDIT
C:ESC
EDIT
M1211
CLOSING
100%
:EDIT
C:ESC
Use and to select between
OPENING
and
CLOSING
.
Information: The value can be displayed in percent, Newtonmeter (Nm), or in
Lbs/ft. To display in percent: 100 % equals the max. torque indicated on the
name plate of the actuator. Example: SA 07.5 with 20 – 60 Nm: 100 % = 60
Nm (33 % = 20 Nm).
15. Press again to enter the edit mode.
➥
Display indicates:
EDIT
M1210
OPENING
100%
:EDIT
:OK
C:ESC
EDIT
M1211
CLOSING
100%
:EDIT
:OK
C:ESC
16. Set new value:
→
Press
.
44
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
Commissioning (basic settings)
ACExC 01.1 Non-Intrusive