![AUMA SGExC 05.1 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/auma/sgexc-05-1/sgexc-05-1_operation-instructions-manual_3016501041.webp)
15. Press again to enter the edit mode.
➥
Display indicates:
EDIT
M1110
OPEN POSITION
LIMIT
:EDIT
:OK
C:ESC
EDIT
M1111
CLOSED POSITION
LIMIT
:EDIT
:OK
C:ESC
16. Set new value:
→
Press
.
17. Accept value or cancel?
→
Accept value: Press .
→
Cancel process without accepting the value: Press
C
.
➥
Display indicates:
EDIT
M1110
OPEN POSITION
LIMIT
:EDIT
C:ESC
AENDERN
M1111
CLOSED POSITION
LIMIT
:EDIT
C:ESC
Use and to select between
OPEN POSITION
and
CLOSED POSITION
.
18. Return to status display:
→
Press
C
several times until
S0
is displayed.
9.5
Torque switching: check/set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve). .
Information
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
TORQUE (M12)
VIEW (M120)
EDIT (M121)
OPENING (M12_0)
CLOSING (M12_1)
41
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
ACExC 01.1 Non-Intrusive
Commissioning (basic settings)