9.4
Type of seating: check/edit for end positions
Valve damage due to incorrect setting!
→
The torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Limit seating
The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
Torque seating
The torque switching is set to the desired tripping torque. After reaching the tripping
torque the actuator is turned off.
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, one of the following fault
signals is displayed:
TSO FAULTS
or
TSC FAULTS
(menu S1).
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SEATING MODE (M11)
VIEW (M110)
EDIT (M111)
OPEN POSITION (M11_0)
CLOSED POSITION (M11_1)
Default value:
LIMIT
Step by step:
1.
Set selector switch to position 0 (OFF).
2.
Press
C
and hold it down for approx. 3 seconds.
➥
Display indicates:
MAIN MENU
M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3.
Press .
➥
Display indicates:
MAIN MENU
M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4.
Press .
➥
Display indicates:
SETTINGS
M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
38
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
Commissioning (basic settings)
ACExC 01.1 Non-Intrusive