Figure 30:
Indication lights/LEDs on local controls
[1]
Marking with symbols (standard)
[2]
Marking with figures (option)
Table 7:
Meaning of signals
Meaning of signal
Behaviour (default)
Indication light
Actuator is in end position CLOSED
illuminated
LED 1 (
)
Running indication: Actuator runs in direction
CLOSE
blinking
Torque fault CLOSE
illuminated
LED 2 (T)
Motor protection tripped
illuminated
LED 3 (Th)
Torque fault OPEN
illuminated
LED 4 (T)
Actuator is in end position OPEN
illuminated
LED 5 (
)
Running indication: Actuator runs in direction
OPEN
blinking
Bluetooth connection available
illuminated
LED 6 (BT) (option)
Information
The behaviour (blinking/illuminated) can be changed via the
BLINKER (M1311)
parameter.
7.3
Mechanical position indicator/running indication
Mechanical position indicator:
●
Continuously indicates the valve position
(For a swing angle of 90°, the indicator disc [2] rotates by approximately 180°.)
●
Indicates whether the actuator is running (running indication)
●
Indicates that the end positions are reached (via indicator mark [3])
Figure 31:
Mechanical position indicator
[1]
Cover
[2]
Indicator disc
[3]
Mark
[4]
Symbol for position OPEN
[5]
Symbol for position CLOSED
32
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
Indications
ACExC 01.1 Non-Intrusive