If the AUMA cable set is not used:
-
Use suitable flexible and screened connecting cables.
-
Use separate CAN bus cable of 120 Ohm character impedance for MWG
(e.g. UNITRONIC BUS-FD P CAN UL/CSA - 2 x 2 x 0.5 mm², manufacturer:
Lapp).
-
Data cable connection: XM2-XA2 = CAN L, XM3-XA3 = CAN H.
-
MWG voltage supply if the AUMATIC has been ordered and delivered with
wall bracket: XM6-XA6 = GND, XM7-XA7 = + 24 V DC (refer to wiring
diagram).
-
MWG voltage supply if AUMATIC has been subsequently separated from
the actuator: XM6-XA6 = GND, XM11-XA117 = + 5 V DC (refer to wiring
diagram).
●
When using connecting cables, e.g. of the heater, requiring direct wiring from
the actuator to the XK customer plug (XA-XM-XK, refer to wiring diagram),
these connecting cables must be subject to an insulation test in compliance
with EN 50178. Connecting cables for MWG do not belong to this group. They
may not be subject to an insulation test.
5.4.2
Parking frame
Application
Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
Figure 19:
Parking frame and plug/socket connector with screw-type terminals
(KP/KPH)
Figure 20:
Parking frame and plug/socket connector with terminal blocks (KES)
5.4.3
Protection cover
Protection cover for plug compartment when plug is removed.
The open terminal compartment can be closed using a protective cover (not
illustrated).
23
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
ACExC 01.1 Non-Intrusive
Electrical connection