COMMISSIONING
Page 42
MVS User Manual
710-13019-00A
4.
Press . The MVS simulates starting. The Run LED flashes.
Run
Simulation
Starting
X:XXs
STORE to Continue
5.
Press . The MVS simulates running. The Run LED stays on without
flashing and the bypass contactor closes (if installed)
Run
Simulation
Running
Apply Stop Signal
6.
Press STOP or activate the stop input. The MVS simulates stopping. The
Run LED flashes and the bypass contactor opens (if installed)
Run
Simulation
Stopping
X:XXs
STORE to Continue
7.
Press . The Ready LED flashes and the main contactor opens (if installed)
Run
Simulation
Stopped
STORE to Continue
8.
Press to return to the commissioning menu.
NOTE
Run simulation can be exited at any stage by pressing the .
.
Protection Simulation
The protection simulation simulates activation of each protection mechanism to confirm that the soft starter and
associated control circuits are responding correctly.
To use the protection simulation:
1.
Open the Commissioning Menu.
2.
Scroll to Protection Simulation and press .
3.
Use the
and
buttons to select the protection you want to
simulate.
4.
Press and hold to simulate the selected protection.
5.
The screen is displayed momentarily. The soft starter's response
depends on the Protection Action setting (parameter group 16).
0.0A
Tripped
Selected Protection
6.
Use or to select another simulation, or press to return to
the commissioning menu.
NOTE
If the protection trips the soft starter, reset before simulating another protection. If the protection action is set
to 'Warning & Log', no reset is required.
If the protection is set to 'Warning & Log', the warning message can be viewed only while the STORE button
is pressed.
If the protection is set to 'Log only', nothing appears on the screen but an entry will appear in the log.
Output Signal Simulation
The output signal simulation simulates output signalling to confirm that outputs and associated control circuits are
operating correctly.
NOTE
To test operation of the flags (motor temperature and low/high current), set an output relay to the
appropriate function and monitor the relay's behaviour.
To use the output signal simulation:
Содержание MVS
Страница 1: ......
Страница 67: ...APPENDIX Page 66 MVS User Manual 710 13019 00A ...
Страница 68: ...APPENDIX 710 13019 00A MVS User Manual Page 67 ...
Страница 69: ...APPENDIX Page 68 MVS User Manual 710 13019 00A ...
Страница 70: ...È710 13019 00A ËÍ 7 1 0 1 3 0 1 9 0 0 A ...