Parameter 9E
Reserved
This parameter is reserved for future use.
10 Start/Stop-2
10A ~ 8N – Start/Stop-2
Refer to Start/Stop-1 (parameters 2A~2I) for details.
Parameter 10A
Start Mode-2
Options:
Constant Current (Default)
Description:
Selects the soft start mode.
Parameter 10B
Start Ramp Time-2
Range:
0:01 - 3.00 (minutes:seconds)
Default: 1 second
Description:
Sets the ramp time for current ramp starting (from the initial current to the current limit).
Parameter 10C
Initial Current-2
Range:
100% - 600%
Default: 400%
Description:
Sets the initial start current level for current ramp starting, as a percentage of motor full load
current. Set so that the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
Parameter 10D
Current Limit-2
Range:
100% - 600% FLC
Default: 400%
Description:
Sets the current limit for constant current and current ramp soft starting, as a percentage of
motor full load current.
Parameter 10E
Reserved
Description:
This parameter is reserved for future use.
Parameter 10G
Kickstart Time-2
Range:
0 - 2000 (milliseconds)
Default: 0000 milliseconds
Description:
Sets the kickstart duration. A setting of 0 disables kickstart.
Parameter 10F
Kickstart Level-2
Range:
100% - 700% FLC
Default: 500%
Description:
Sets the level of the kickstart current.
Parameter 10H
Stop Mode-2
Options:
Coast To Stop (Default)
TVR Soft Stop
Description:
Selects the stop mode.
Parameter 8N
Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default: 0 seconds
Description:
Sets the stop time.
11 RTD/PT100 (Reserved)
This parameter group is reserved for future use.
12 Slip-Ring Motors
These parameters allow the soft starter to be configured for use with a slip-ring motor.
12A, 12B – Motor Data-1 and Motor Data-2 Ramp
Options:
Single Ramp (Default)
Dual Ramp
Description:
Selects whether to use a single or dual current ramp profile for soft starting. Set to single
ramp for non-slip ring induction motors, or dual ramp for slip-ring induction motors.
Parameter 12A selects the ramp configuration for the primary motor and parameter 12B
selects the ramp configuration for the secondary motor.
12C – Changeover Time
Range:
100 - 500 (milliseconds)
Default: 150 milliseconds