PROGRAMMING MENU
Page 32
MVS User Manual
710-13019-00A
Input Trip (N/O)
Input A can be used to trip the soft starter. When parameter
6A is set to Input Trip (N/O), a closed circuit across C53, C54
trips the soft starter.
(Refer to parameters 6C, 6D, 6E)
Input Trip (N/C)
When parameter 6A is set to Input Trip (N/C), an open circuit
across C53, C54 trips the soft starter.
(Refer to parameters 6C, 6D, 6E)
Local/Remote Select
Input A can be used to select between local and remote
control, instead of using the LCL/RMT button on the
Controller. When the input is open, the starter is in local mode
and can be controlled via the Controller. When the input is
closed, the starter is in remote mode. The START and
LCL/RMT buttons are disabled, and the soft starter will ignore
any Local/Remote select command from the serial
communications network.
To use Input A to select between local and remote control,
parameter 6Q must be set to LCL/RMT Anytime or LCL/RMT
when Off.
Emergency Run
In emergency run the soft starter continues to run until
stopped, ignoring all trips and warnings (refer to parameter
15C for details).
Closing the circuit across C53, C54 activates emergency run.
Opening the circuit ends emergency run and the MVS stops
the motor.
Emergency Stop
The MVS can be commanded to emergency stop the motor,
ignoring the soft stop mode set in parameter 2H.
When the circuit across C53, C54 is opened, the soft starter
allows the motor to coast to stop.
Description:
Selects the function of Input A.
6B – Input A Name
Options:
Input Trip (Default)
No Flow
Low Pressure
Emergency Stop
High Pressure
Controller
Pump Fault
PLC
Low Level
Vibration Alarm
High Level
Description:
Selects a message for the Controller to display when Input A is active.
6C, 6D, 6E – Input A Trip
Parameter 6C
Input A Trip
Options:
Always Active (Default)
A trip can occur at any time when the soft starter is receiving
power.
Operating Only
A trip can occur while the soft starter is running, stopping or
starting.
Run Only
A trip can only occur while the soft starter is running.
Description:
Selects when an input trip can occur.
Parameter 6D
Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default: 0 seconds
Description:
Sets a delay between the input activating and the soft starter tripping.
Parameter 6E
Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default: 0 seconds
Description:
Sets a delay before an input trip can occur, after the soft starter has entered the state selected
in 6C.
6F, 6G, 6H, 6I, 6J – Input B Trip
Parameters 6F~6J configure the operation of Input B, in the same way as parameters 6A~6E configure Input A.
Refer to Input A for details.
6F
Input B Function
(Default: Input Trip N/O)
6G
Input B Name
(Default: Input Trip)