INSTALLATION
Wiring Connectors
Select a connector according to the wire size, material and your application
requirements.
A compression connector is recommended for models EMX4e-0184B to
EMX4e-0580B. The recommended crimping tool is TBM8-750.
Model
Example connector –
aluminium cable
Example connector –
copper cable
EMX4e-0184B
61162
60150
EMX4e-0200B
61165
60156
EMX4e-0229B
61171
60165
EMX4e-0250B
EMX4e-0352B
61162
60150
EMX4e-0397B
61165
60156
EMX4e-0410B
60162
EMX4e-0550B
61178
60171
EMX4e-0580B
Motor Connection
The EMX4e must be connected to the motor in-line (also called three-wire
connection).
34
33
K1
K1
F1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
M
3
K1
Main contactor (strongly recommended)
F1
Fuses or circuit breaker
33, 34 Main contactor output
EMX4e User Manual (710-18433-00C) |
29