PROGRAMMABLE PARAMETERS
9.11
9 Analog Output
9A –
Analog Output A
Options:
Current (% FLC)
(default)
Current as a percentage of motor full load
current.
Motor Temperature
(%)
The motor's temperature, calculated by the
thermal model.
Motor pf
Motor power factor, measured by the soft
starter.
Heatsink
Temperature %
The soft starter's temperature, as a
percentage of the heatsink’s maximum
allowed operating temperature.
Description:
Selects which information will be reported via the analog output.
9B –
Analog A Scale
Range:
0-20 mA
4-20 mA (default)
Description:
Selects the range of the analog output.
9C –
Analog A Maximum Adjustment
Range:
0% - 600%
Default:
100%
Description:
Calibrates the upper limit of the analog output to match the
signal measured on an external current measuring device.
9D –
Analog A Minimum Adjustment
Range:
0% - 600%
Default:
0%
Description:
Calibrates the lower limit of the analog output to match the
signal measured on an external current measuring device.
9.12
10 Display
10A –
Language
Options:
English (default)
Português
Chinese
Français
Español
Italiano
Deutsch
Russian
Description:
Selects which language the keypad will use to display messages
and feedback.
10B –
Temperature Scale
Options:
Celsius (default)
Fahrenheit
Description:
Selects whether the EMX4e will display temperatures in
degrees Celsius or Fahrenheit.
70 |
EMX4e User Manual (710-18433-00C)