SYSTEM DESIGN
3.13
Fuse Selection for Type 2 Coordination
Type 2 coordination is achieved by using semiconductor fuses. These fuses must be
able to carry motor start current and have a total clearing I
2
t less than the I
2
t of the
soft starter SCRs.
When selecting semiconductor fuses for EMX4e, use the I
2
t values in the table.
For further information on selecting semiconductor fuses, contact your local
distributor.
I
2
t values for Type 2 coordination
Model
SCR I
2
t (A
2
s)
EMX4e-0024B
1150
EMX4e-0042B
7200
EMX4e-0052B
EMX4e-0064B
15000
EMX4e-0069B
EMX4e-0105B
80000
EMX4e-0115B
EMX4e-0135B
125000
EMX4e-0184B
320000
EMX4e-0200B
EMX4e-0229B
EMX4e-0250B
EMX4e-0352B
202000
EMX4e-0397B
EMX4e-0410B
320000
EMX4e-0550B
781000
EMX4e-0580B
EMX4e User Manual (710-18433-00C) |
19