OPERATION
Application
Start Mode
St
ar
t R
am
p
Tim
e
(s
ec
on
ds
)
In
itia
l Cu
rr
ent
(%
FL
C)
Cu
rr
en
t L
im
it
(%
FL
C)
Stop Mode
St
op Ti
m
e
(s
ec
on
ds
)
Compressor - screw -
unloaded
Constant Current
1
200
350
Coast To Stop
n/a
Conveyor - horizontal
Constant Current
5
200
400
TVR Soft Stop
10
Conveyor - inclined
Constant Current
2
200
450
Coast To Stop
n/a
Conveyor - vertical
(bucket)
Constant Current
2
200
450
Coast To Stop
n/a
Crusher - cone
Constant Current
1
200
350
Coast To Stop
n/a
Crusher - jaw
Constant Current
1
200
450
Coast To Stop
n/a
Crusher - rotary
Constant Current
1
200
400
Coast To Stop
n/a
Debarker
Constant Current
1
200
350
Coast To Stop
n/a
Fan - axial (damped)
Constant Current
1
200
350
Coast To Stop
n/a
Fan - axial (undamped) Constant Current
1
200
450
Coast To Stop
n/a
Fan - centrifugal
(damped)
Constant Current
1
200
350
Coast To Stop
n/a
Fan - centrifugal
(undamped)
Constant Current
1
200
450
Coast To Stop
n/a
Fan - high pressure
Constant Current
1
200
450
Coast To Stop
n/a
Mill - ball
Constant Current
1
200
450
Coast To Stop
n/a
Mill - hammer
Constant Current
1
200
450
Coast To Stop
n/a
Pump - bore
Adaptive Control
(Const. accel.)
3
n/a
500
Adaptive Control
(Const. decel.)
3
Pump - centrifugal
Adaptive Control
(Const. accel.)
10
n/a
500
Adaptive Control
(Const. decel.)
15
Pump - hydraulic
Constant Current
2
200
350
Coast To Stop
n/a
Pump - positive
displacement
Adaptive Control
(Const. accel.)
10
n/a
400
Adaptive Control
(Const. decel.)
10
Pump - submersible
Adaptive Control
(Const. accel.)
5
n/a
500
Adaptive Control
(Const. decel.)
5
Saw - bandsaw
Constant Current
1
200
450
Coast To Stop
n/a
Saw - circular
Constant Current
1
200
350
Coast To Stop
n/a
Shredder
Constant Current
1
200
450
Coast To Stop
n/a
EMX4e User Manual (710-18433-00C) |