PROGRAMMABLE PARAMETERS
Warning
The relay closes when the starter issues a
warning (refer to
6 Protection Action
on
page 62).
Trip
The relay closes when the starter trips
(refer to
6 Protection Action
on page 62).
Low Current Flag The relay closes when the low current flag
activates while the motor is running (refer
to parameter 8G
Low Current Flag
).
High Current Flag The relay closes when the high current flag
activates while the motor is running (refer
to parameter 8H
High Current Flag
).
Motor Temperature
Flag
The relay closes when the motor
temperature flag activates (refer to
parameter 8I
Motor Temperature Flag
).
Trip Failsafe
The relay closes when control power is
applied. The relay opens if the soft starter
trips or if control power is lost.
Description:
Selects the function of Relay A. Relay A is a changeover relay.
8B –
Relay A On Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for changing the state of Relay A.
8C –
Relay A Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for changing the state of Relay A.
8D –
Relay B Function
Options:
Off
Low Current Flag
Ready
High Current Flag
Run (default)
Motor Temperature Flag
Warning
Trip Failsafe
Trip
Description:
Selects the function of Relay B (normally open). Refer to
parameter 8A
Relay A Function
.
8E –
Relay B On Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for closing Relay B.
8F –
Relay B Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
Default:
0 second
Description:
Sets the delay for re-opening Relay B.
68 |
EMX4e User Manual (710-18433-00C)