INSTALLATION
4.
Installation
WARNING
Do not apply mains voltage to the starter until all wiring is complete.
WARNING
Always apply control voltage before (or with) mains voltage.
4.1
Command Source
The EMX4e can be started and stopped via the digital inputs, remote keypad,
communication network or smart card. The command source can be set via the
Setup Tools, or using parameter 1A
Command Source
.
4.2
Setup Procedure Overview
1.
Mount the soft starter (refer to
Physical Installation
on page 12 for details).
2.
Connect control wiring (refer to on page 23 for details).
3.
Apply control voltage to the starter.
4.
Configure your application:
1.
Press MENU to open the Menu.
2.
Press to open the Quick Setup menu.
3.
Scroll through the list to find your application, then press to begin the
configuration process (refer to
Quick Setup
on page 32 for details).
5.
If your application is not listed in Quick Setup:
1.
Press to return to the Menu.
2.
Use to scroll to Main Menu and press .
3.
Scroll to Motor Details and press , then press then to edit
parameter 1B
Motor Full Load Current
.
4.
Set parameter 1B to match the motor's full load current (FLC).
5.
Press to save the setting.
6.
Close the Menu by pressing repeatedly.
7.
(Optional) Use the built-in simulation tools to check that the control wiring is
connected correctly (refer to
Run simulation
on page 33).
8.
Power off the soft starter.
9.
Connect the motor cables to starter output terminals 2/T1, 4/T2, 6/T3.
10.
Connect mains supply cables to starter input terminals 1/L1, 3/L2, 5/L3 (refer
to
Power Terminations
on page 28).
The soft starter is now ready to control the motor.
22 |
EMX4e User Manual (710-18433-00C)