PROGRAMMABLE PARAMETERS
6M –
Motor Overtemperature
Options:
Soft Trip and Log (default)
Warn and Log
Soft Trip and Reset
Log Only
Trip Starter
Trip + Shunt Relay
Trip and Reset
Description:
Selects the soft starter's response to the protection event.
6N –
Motor Thermistor Circuit
Options:
Soft Trip and Log (default)
Warn and Log
Soft Trip and Reset
Log Only
Trip Starter
Trip + Shunt Relay
Trip and Reset
Description:
Selects the soft starter's response to the protection event.
9.9
7 Inputs
7A –
Input A Function
Options:
Command
Override: Network
Overrides the setting of 1A and sets the
command source to the communications
network.
Command
Override: Digital
Overrides the setting of 1A and sets the
command source to the digital inputs.
Command
Override: Keypad
Overrides the setting of 1A and sets the
command source to the remote keypad.
Input Trip (N/O)
(default)
A closed circuit across 13, 14 trips the soft
starter.
Input Trip (N/C)
An open circuit across 13, 14 trips the soft
starter.
Emergency Mode A closed circuit across 13, 14 activates
emergency mode. When the EMX4e
receives a start command, it will continue
to run until a stop command is received,
ignoring all trips and warnings.
Description:
Selects the function of Input A.
7B –
Input A Trip
Options:
Always Active
A trip can occur at any time when the soft
starter is receiving power.
Operating Only
(default)
A trip can occur while the soft starter is
running, stopping or starting.
Run Only
A trip can only occur while the soft starter
is running.
Description:
Selects when an input trip can occur.