INSTALLATION
5.
Installation
5.1
Physical Installation
1 EMX3-0023B ~ EMX3-0220B: Allow 100 mm (3.94 inches) between soft starters.
EMX3-0255B ~ EMX3-1000B: Allow 200 mm (7.88 inches) between soft starters.
EMX3-0255C: Allow 100 mm (3.94 inches) between soft starters.
EMX3-0360C ~ EMX3-1600C: Allow 200 mm (7.88 inches) between soft starters.
2 EMX3-0023B ~ EMX3-0220B: Allow 50 mm (1.97 inches) between the soft starter and solid surfaces.
EMX3-0255B ~ EMX3-1000B: Allow 200 mm (7.88 inches) between the soft starter and solid surfaces.
EMX3-0255C: Allow 100 mm (3.94 inches) between the soft starter and solid surfaces.
EMX3-0360C ~ EMX3-1600C: Allow 200 mm (7.88 inches) between the soft starter and solid surfaces.
3 Soft starters may be mounted side by side with no clearance (that is, if mounted without communications modules).
4 The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%.
5.2
Control Terminals
Control terminations use 2.5mm
2
plug-in terminal blocks. Unplug each block, complete the wiring, then reinsert the block.
Remote Control Inputs
Relay Outputs
Analog
Output
5.3
Control Voltage
Different models require control voltage to different terminals:
•
C1 (110~210 VAC)
A1, A2
•
C1 (220~440 VAC)
A2, A3
•
C2 (24 VAC/VDC)
A1, A3
User Manual (710-04840-00M) |
9