PROGRAMMING MENU
10J – Adaptive Stop Profile-2
Options:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Description:
Selects which profile the EMX3 will use for an Adaptive Control soft stop.
10K – Adaptive Control Gain-2
Range:
1% - 200%
Default:
75%
Description:
Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control.
10L – Brake Torque-2
Range:
20% - 100%
Default:
20%
Description:
Sets the amount of brake torque the EMX3 will use to slow the motor.
10M – Brake Time-2
Range:
1 - 30 (seconds)
Default:
1 second
Description:
Sets the duration for DC injection during a braking stop.
11 RTD Temperatures
The EMX3 has one RTD/PT100 input and can be fitted with another six PT100 inputs by using the RTD/PT100 and ground fault
protection card. The inputs can trip the soft starter when the temperature exceeds a specified point, and different trip temperatures
can be set for each input.
PT100 inputs B ~ G are only available if the RTD/PT100 and ground fault protection card has been installed.
Range:
0 - 250 ° C
Default:
50 ° C
Description:
Sets the trip points for the RTD/PT100 inputs.
•
11A
RTD A Trip Temp
•
11B
RTD B Trip Temp
•
11C
RTD C Trip Temp
•
11D
RTD D Trip Temp
•
11E
RTD E Trip Temp
•
11F
RTD F Trip Temp
•
11G
RTD G Trip Temp
12 Slip-Ring Motors
These parameters allow the soft starter to be configured for use with a slip-ring motor.
12A, 12B – Motor Data-1 and Motor Data-2 Ramp
Options:
Single Ramp (default)
Dual Ramp
Description:
Selects whether to use a single or dual current ramp profile for soft starting. Set to single ramp for non-slip
ring induction motors, or dual ramp for slip-ring induction motors.
Parameter 12A selects the ramp configuration for the primary motor and parameter 12B selects the ramp
configuration for the secondary motor.
12C – Changeover Time
Range:
100 - 500 (milliseconds)
Default:
150 milliseconds
Description:
Sets the delay between the rotor resistance relay closing and the low resistance current ramp starting. Set so that
the contactor has enough time to close, but the motor does not slow down.
Parameter 12C only applies if parameter 12A or 12B is set to 'Dual Ramp', and an output relay is set to
'Changeover Contactor'.