PROGRAMMING MENU
10.3
Access Code
Critical parameters (parameter group 15 and higher) are protected by a four-digit security access code, preventing unauthorised
users from viewing or modifying parameter settings.
When a user attempts to enter a restricted parameter group, the keypad prompts for an access code. The access code is requested
once for the programming session, and authorisation continues until the user closes the menu.
To enter the access code, use the and buttons to select a digit, and the
and
buttons to change the value. When all
four digits match your access code, press STORE. The keypad will display an acknowledgement message before continuing.
Enter Access Code
0###
STORE
Access Allowed
SUPERVISOR
To change the access code, use parameter 15A.
The simulation tools and counter resets are also protected by the security access code.
The default access code is 0000.
10.4
Quick Setup
The Quick Setup Menu makes it easy to configure the EMX3 for common applications. The EMX3 selects the parameters relevant to
the application and suggests a typical setting, and you can adjust each parameter to suit your exact requirements.
Always set parameter 1A
Motor Full Load Current
to match the motor's nameplate full load current. The suggested value is the
starter's minimum full load current.
On the display, the highlighted values are suggested values and the values indicated by a
are the loaded values.
Application
Parameter
Suggested value
Pump Centrifugal
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
Model dependent
Adaptive Control
Early Acceleration
10 seconds
Adaptive Control
Late Deceleration
15 seconds
Pump Submersible
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
Model dependent
Adaptive Control
Early Acceleration
5 seconds
Adaptive Control
Late Deceleration
5 seconds
Fan Damped
Motor Full Load Current
Start Mode
Current Limit
Model dependent
Constant Current
350%
Fan Undamped
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Excess Start Time
Locked Rotor Time
Model dependent
Adaptive Control
Constant Acceleration
20 seconds
30 seconds
20 seconds
Compressor Screw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Model dependent
Constant Current
5 seconds
400%
User Manual (710-04840-00M) |
39