PROGRAMMING MENU
Description:
Selects the function of Input A.
6B – Input A Name
Options:
Input Trip (default)
No Flow
Low Pressure
Starter Disable
High Pressure
Controller
Pump Fault
PLC
Low Level
Vibration
High Level
Description:
Selects a message for the keypad to display when Input A is active.
6C – Input A Trip
Options:
Always Active (default)
A trip can occur at any time when the soft starter is receiving power.
Operating Only
A trip can occur while the soft starter is running, stopping or starting.
Run Only
A trip can only occur while the soft starter is running.
Description:
Selects when an input trip can occur.
6D – Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter tripping.
6E – Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is counted from the time a start signal is received.
The state of the input is ignored until the initial delay has elapsed.
6F, 6G, 6H, 6I, 6J – Input B Trip
Parameters 6F~6J configure the operation of Input B, in the same way as parameters 6A~6E configure Input A. Refer to Input A for
details.
•
6F
Input B Function
(Default: Input Trip (N/O))
•
6G
Input B Name
(Default: Input Trip)
•
6H
Input B Trip
(Default: Always Active)
•
6I
Input B Trip Delay
(Default: 0:00)
•
6J
Input B Initial Delay
(Default: 0:00)
6K, 6L – Inputs C and D
Parameters 6K and 6L select the function of Inputs C and D. Refer to parameter 6A for details.
Inputs C and D are only available if the input/output expansion card has been installed.
Options:
Motor Set Select
Local/Remote Select
Emergency Run
Starter Disable (N/C)
Off (default)
6M – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the EMX3's remote reset input (terminals C41, C42) is normally open or normally closed.