CHAPTER 4: PROFILES TAB
4-4
MDU Solutions
®
– UCrypt
®
Monitoring Server - Operation Manual
monitoring Server. When the Monitoring Server detects this condition, it triggers an email message to defi ned
recipients and as well, an SNMP trap Northbound (traps sent to an SNMP Manager), if set to do so.
•
Sender
This is the Alert Message displayed in the Events list which is usually the same as the Alert message from the
monitored Device itself though it may be modifi ed by the Monitoring Server if necessary.
•
Email Alert
The email message that is sent to recipients that have been defi ned for each trigger. An email address of
on_duty
will specify that an email message is to be sent to whatever technician is defi ned as being on call or ‘On Duty’.
Procedure
This procedure outlines enabling trigger scripts, adding email recipients to the script and forwarding SNMP Northbound traps.
1. Click the
Profi les
tab if it is not already selected, Figure 4-7.
2. The upper section lists the profi les and their included scripts. These elements are also hyperlinks but do not use
these links for confi guration.
3. Confi guration is done in the second lower section titled
Trigger Scripts
. They relate directly to the familiar Device
Alerts as there is one for each Alert that you are familiar with and a few new ones that relate to the interaction with
the Monitor Server and the remitting of specifi c Alerts.
4. Click the
Trigger
to be confi gured. There is only one set of triggers per Monitoring Server. All monitored Devices
whose profi le includes a trigger will use the same set of Trigger Scripts.
5. Tick the box to enable this trigger, Figure 4-8.
6. Select the Error Level from the dropdown menu choices of High, Medium, Low or Info.
Info
does not generate an
email but all levels above do result in an email being sent.
7. Enter the email addresses of each recipient that should receive an email alert when this alert is triggered. Multiple
addresses may be entered with comma separation. Entering
on_duty
will link to the designated on call technician
defi ned with the
Modify On Duty
button on the Status Page, (see
“2.3.2 Assign the ‘On Duty’
Technician” on page 2-3
for this procedure)
.
8. If Northbound SNMP traps (traps sent to an SNMP Manager) are required, tick the box to enable. Be sure to confi gure
the SNMP trap target, see
“5.4 Confi gure SNMP” on page 5-12.
9. Click
Save
when fi nished.
1
2
4
3
Figure 4-7: Confi gure Trigger Script
5
6
7
8
9
Figure 4-8: Complete Trigger Form