CAUTION: Never connect
propane/LP fireplace directly to
the propane/LP supply. This log
set requires an external regula-
tor (not supplied). Install the
external regulator between the
log set and propane/LP supply.
WARNING: Never connect
natural gas fireplace to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
Installation Items Needed
Before installing the log set, make sure you have
the items listed below.
• external regulator (for propane/LP units only,
supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved flexible gas line with gas connector
(if allowed by local codes) (provided)
* A CSA design-certified equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certified equipment shutoff valve from your
dealer. See
Accessories
, page 19.
For propane/LP units, the installer must supply
an external regulator. The external regulator will
reduce incoming gas pressure. You must reduce
incoming gas pressure to between 11" and 14" of
water column. If you do not reduce incoming gas
pressure, log set regulator damage could occur.
Install external regulator with the vent pointing
down as shown in Figure 6. Pointing the vent down
protects it from freezing rain or sleet.
Figure 6 - External Regulator With Vent
Pointing Down
Propane/LP
Supply Tank
External
Regulator
Vent
Pointing
Down
INSTALLATION
Continued
CAUTION: Use only new, black
iron or steel pipe. Internally-tinned
copper tubing may be used in
certain areas. Check your local
codes. Use pipe of 1/2" diameter or
greater to allow proper gas volume
to the log set. If pipe is too small,
undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate NPT
tap within reach for test gauge hook up. NPT tap
must be upstream from the log set (see Figure 7).
IMPORTANT:
Install equipment shutoff valve
in an accessible location. The equipment shutoff
valve is for turning on or shutting off the gas to
the appliance.
* Purchase the optional CSA design-certified
equipment shutoff valve from your dealer. See
Accessories
, page 25.
** Minimum inlet pressure for purpose of input
adjustment.
Figure 7 - Gas Connection
3" Minimum
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
Cap Pipe Tee
Nipple Joint
Sediment Trap
Natural Gas
From Gas Meter
(5" W.C.** to 10.5"
W.C. Pressure)
Propane/LP Gas
From External
Regulator
(11" W.C.** to
14" W.C.
Pressure)
To Gas