background image

Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 25

7.3  How to see but not modify the 

“limited access parameters”

Sometime it is necessary to give to the operator the possibility 
to see the value assigned to the parameter promoted in the 
Limited Access level but it is important that all changes are 
made by authorized personnel only.
In this cases, proceed as follows:

1. 

Press the 

 button for more than 5 seconds; the upper 

display shows 

PASS

 while the lower display shows 

0

;

2. 

By 

 and 

 button set the value 

-181

;

3. 

Push 

 button; the upper display shows the acronym 

of the first parameter promoted to the level 2 and lower 
display shows its value;

4. 

Using 

 button it is possible to see the value assigned 

to all parameters present in level 2 but will not possible to 
modify them;

5. 

It is possible to return to the “standard display” pushing 
the 

 button for more than 3 seconds or by pushing no 

buttons for more than 10 seconds. 

7.4  Automatic Mode

7.4.1  Keyboard function when the instrument 

 

is in Auto mode

  Performs the action programmed by [121] uSrb  

(

 button function during RUN TIME) parameter.

  Enters the parameter modification procedures.
  a short pressure (less than 2 seconds) Displays the 

“additional information” (see below)

 

a pressure longer than 2 second starts the “Direct Set 
Point modification” function (see below).

  Starts the “Direct Set Point modification” function (see 

below).

 + 

 Allows to enter in MANual mode and return to 

AUTO mode.

Note: 

 To enter in MANual mode, press the 

 button 

and (maintaining the pressure) within 1 s push the 

 button also; the MAN LED lights ON and the 

lower display starts showing the power output. 
To exit MANual mode, press the 

 button and 

(maintaining the pressure) within 1 s push also the 

 button and maintain both pressed until the MAN 

LED goes OFF.

7.4.2  Direct Set Point modification

This function allows to quickly modify the Set Point value select-
ed by [81] A.SP (selection of the active Set Point) or to the Set 
Point of the segment (of the programmer) currently in progress.
While the instrument is showing the “Standard display”:

1. 

Push the 

 or the 

 button for more than 2 s.  The 

upper display start showing the acronym of the selected 
Set Point (e.g. SP2) while the lower one shows its value.

Note: 

When the programmer is running, the instrument 
shows the Set Point of the group currently in use 
(e.g. if the instrument is performing the soak 3 the 
instrument will show [107] Pr.S3).

2. 

Using the 

 and 

 buttons, assign to this parameter 

the desired value;

3. 

Push no buttons for more than 5 second or  
push the 

 button.

In both cases the instrument stores the new value and 

returns to the “Standard display”.

Note: 

If the selected Set Point has not been promoted to the 
Operator level, the instrument allows you to see the 
value but not to modify it.

7.4.3  Additional information

The instrument is able to display some additional information 
which can help in managing the system.
The additional information are related on how the instrument 
is programmed, hence in many cases, only part of these 
information are available.

1. 

While the instrument is showing the “standard display” 
push the 

 button for less than 2 seconds.  The lower 

display will show 

H

 or 

c

 followed by a 2 digit number.  

This value is the output power (as a %) applied in that 
moment to the process.  

H

 indicates that the instrument 

is performing a Heating action while 

c

 means that is 

performing a Cooling action.

2. 

Push 

 again.  If the programmer is running the lower 

display shows the segment currently performed and the 
Event status (see below): where the first character can be 

r

 for a ramp or 

S

 for a soak, the next digit indicates the 

number of the segment (e.g. 

S3

 means Soak number 3) 

and the two less significant digits (LSD) the status of the 
two events (the LSD is the Event 2);

3. 

Push 

 again.  If the programmer is running the lower 

display shows the theoretical remaining time to the end of 
the program preceded by a 

P

 letter;

4. 

Push 

 again.  If the timer is running the lower display 

s

 

and the remaining time to the end of the time count;

5. 

Push 

 again.  If the wattmeter function is running the 

lower display shows 

U

 followed by the measured energy.  

The energy calculation will be in accordance with the 
[132] Co.tY parameter setting;

6. 

Push 

 again.  If the “Worked time count” is running the 

lower display shows 

d

 for days or 

h

 for hours followed by 

the measured elapsed time;

7. 

Push 

 again.  If 

HBD

 alarm has been programmed, 

the lower display shows the 

CT

 measure during the ON 

period preceded by the 

C

 letter;

8. 

Push 

 again.  If the 

HBD

 alarm has been programmed 

the lower display shows the 

CT

 measure during the OFF 

period preceded by the 

o

 letter;

9. 

Push 

 again.  If the 

HBD

 alarm has been programmed 

the lower display shows the instantaneous current 
measured by 

CT

 measure preceded by a 

A

 letter;

10. 

Push 

 again.  The instrument returns to the “standard 

display”.

Note: 

The additional information visualization is subject to 
a time out.  If no button is pressed for more than 10 
seconds the instrument automatically returns to the 
Standard display.

Содержание KM2

Страница 1: ...protection IP65 is desired the optional gasket must be mounted 1 2 Dimensions 1 2 1 Controller with non removable terminals 63 3 14 11 44 5 PV AT 48 48 1 2 2 Removable terminals 40 15 5 18 85 26 15 8...

Страница 2: ...ration According to EN 60751 A2 2 3 5 V and mV Input mV V _ _ 1 2 Input impedance 1 M for mV Input 500 k for Volt Input 2 3 6 mA Input 0 4 20 mA input wiring for passive transmitter using the auxiliar...

Страница 3: ...Logic level 1 12 V 20 15 mA max Current Analogue Output mA 7 8 mA output 0 4 20 mA galvanically isolated RL max 600 Voltage Analogue Output V 7 8 V output 0 2 10 V galvanically isolated RL min 500 2...

Страница 4: ...m 1 78 0 023 x 1 78 0 023 in Weight 180 g max Power supply 24 240 VAC DC 10 Power consumption 5 VA max Insulation voltage 3000 V rms according to EN 61010 1 Display updating time 500 ms Sampling time...

Страница 5: ...he instrument has a complete parameter set that allows the user to adapt the controller to the destination application Note The instrument normally shows only the parameters consistent with the specif...

Страница 6: ...20 0 20 mA linear 4 20 4 20 mA linear 0 5 0 5 V linear 1 5 1 5 V linear 0 10 0 10 V linear 2 10 2 10 V linear When the code of the input type is equal to e see How to order paragraph J TC J 50 1000 C...

Страница 7: ...g 9 io3F from on to Out3 makes the 22 O3F parameter visible and equal to nonE 10 diF1 Digital input 1 function Available Always Range oFF No function 1 Alarm Reset status 2 Alarm acknowledge ACK statu...

Страница 8: ...ollowing table Digital Input 1 Digital Input 2 Operative Set Point Off Off Set Point 1 On Off Set Point 2 Off On Set Point 3 On On Set Point 4 4 When 10 diF1 is equal to 21 11 diF2 is forced to 21 up...

Страница 9: ...Output not used With this setting the status of this output can be driven directly from serial link H rEG Heating output c rEG Cooling output AL Alarm output t out Timer output t HoF Timer out OFF in...

Страница 10: ...ion Available When 25 AL1t is different from nonE Range 0 15 with the following rule 1 Not active at Power ON 2 Latched alarm manual reset 4 Acknowledgeable alarm 8 Relative alarm not active at Set Po...

Страница 11: ...ysteresis equal to 25 C 31 AL1d Alarm 1 delay Available When 25 AL1t is different from nonE Range 0 oFF 1 9999 seconds Note The alarm goes ON only when the alarm condition persists for a time longer t...

Страница 12: ...larm with alarm indication out of the band LHAi Absolute band alarm with alarm indication inside the band SE br Sensor break Note The relative alarm are relative to the current Set Point this may be d...

Страница 13: ...ilable When 49 Ct So is different from oFF Range 0 Automatic reset 1 Manual reset 2 Acknowledgeable 54 Ct Ld Load current threshold Available When 49 Ct So is different from oFF Range 0 Disabled 1 999...

Страница 14: ...and 1 00 it is possible to slow down the instrument action during Set Point approach Setting Fuoc 1 this function is disabled PV SP time 2 1 3 Available When 57 cont PID Range 0 2 00 Note Fast auto tu...

Страница 15: ...tH parameter 2 When the power limiter has a negative value the limit is applied to the cooling action the soft start function will be aborted when the measured value is lower or equal to SS tH paramet...

Страница 16: ...controllers The Slave zones use it as a Set Point trim The first zone is the master zone and it uses a Set Point equal to 210 C The second zone has a local Set Point equal to 45 C The third zone has...

Страница 17: ...m steps Some additional parameters allow to define the time scale the automatic RUN conditions and the instrument behaviour at the end of the program Notes 1 All steps can be modified during program e...

Страница 18: ...ent 1 Event 2 Event 1 Event 2 00 01 off off off on 10 01 on off off on 01 01 off on off on 11 01 on on off on 00 11 off off on on 10 11 on off on on 01 11 off on on on 11 11 on on on on 100 Pr S2 Set...

Страница 19: ...m Hold rES Program reset Note This parameter allows to manage program execution by a parameter PAn group Operator HMI 116 PAS2 Level 2 password Limited access level Available Always Range oFF Level 2...

Страница 20: ...o when ON OFF control is selected ct on CT measure during ON ct OF CT measure during OFF ct iS Instantaneous CT measurement 120 L dSP Secondary Display Management Available Always Range nonE Display O...

Страница 21: ...estart from the soak time minus the stored elapsed time In order to obtain this features the 126 dSPu Status of the instrument at Power ON parameter must be set to AS Pr If the 126 dSPu parameter is d...

Страница 22: ...ays when 132 Co tY 4 1 9999 hours when 132 Co tY 5 136 t Job Worked time not resettable Available Always Range 1 9999 days CAL group User calibration group This function allows to calibrate the comple...

Страница 23: ...9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set a password equal to 8...

Страница 24: ...If no button is pressed for more than 10 seconds the instrument goes back to the standard display and the new value of the last selected parameter will be lost 7 2 Enter the Limited access level The i...

Страница 25: ...sing the and buttons assign to this parameter the desired value 3 Push no buttons for more than 5 second or push the button In both cases the instrument stores the new value and returns to the Standar...

Страница 26: ...program is running the door is locked Application Example 2 edge bending machine with glue tank for wood At the working temperature the hot melt rapidly oxidizes and runs down from the dispenser For t...

Страница 27: ...and by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you set stand by mode during self tune execution the self tune function will be abort...

Страница 28: ...t there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 9 3 Disposal The appliance or the product must be disposed of...

Страница 29: ...52 F Ir J Exergen IRS J 46 785 C 50 1445 F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc PTC KTY81 121 55 150 C 67 302 F ntc NTC 103 AT2 50 110 C 58 230 F 0 60 0 60 mV 12 60 12 60 mV 0 20 0 20 mA 4 20 4...

Страница 30: ...output 0 NonE Output not used H rEG Heating output c rEG Cooling output r inP Measure retransmission r Err Error SP PV retransmission r SP Set Point retransmission r SEr Serial value retransmission r...

Страница 31: ...3 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Heater Break Down 16 Sensor Break 32 Overload on output 3 AL1 21 o2Ac Out 2 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse...

Страница 32: ...n stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default...

Страница 33: ...ditions 1 Alarm 1 enabled in stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 HBD group Heater Break Down Parameters no Param...

Страница 34: ...01 99 99 1 00 68 tcc Cooling output cycle time C rEG 1 0 2 130 0 s 20 0 69 rS Manual reset Integral pre load 1 100 0 100 0 0 0 70 od Delay at Power ON 2 0 00 oFF 00 01 99 59 hh mm oFF 71 St P Maximum...

Страница 35: ...s and seconds inF Forced to ON oFF 95 Pr S1 Set Point of the first soak dP From SPLL to SPHL 0 96 Pr G1 Gradient of the first ramp 1 0 1 999 9 Engineering Unit minute inF Step transfer inF 97 Pr t1 Ti...

Страница 36: ...r is running the display shows the timer counting up ti du When the timer is running the display shows the timer counting down PErc Percent of the power output used during soft start ct on Current mea...

Страница 37: ...measure starts from zero when a program runs end stops at the end of the program A new program execution will reset the value 4 Total worked days number of hours the instrument is turned ON divided by...

Страница 38: ...eters no Param Description Dec Point Values Default 137 AL P Adjust Low Point dp From 1999 to AH P 10 in engineering units 0 138 AL o Adjust Low Offset dp 300 300 E U 0 139 AH P Adjust High Point dp F...

Страница 39: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 39...

Страница 40: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 40...

Отзывы: