Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 8

6

  HEAt with SP1 and CooL with “SP2” [status] 

(see “Note about digital inputs”);

7

  Timer Run/Hold/Reset [transition]. 

A short closure allows to start timer execution 
and to suspend it while a long closure (longer 
than 10 seconds) allows to reset the timer;

8

  Timer Run [transition]. A short closure allows to 

start timer execution;

9

  Timer reset [transition].  A short closure allows 

to reset timer count;

10

  Timer run/hold [Status]:  

- Contact close = timer RUN; 
- Contact open = timer Hold.

11

  Timer run/reset [status];

12

  Timer run/reset with a special “lock” at the end of 

the time count (in order to restart the time count 
the instrument must detect a run command com-
ing from serial link keyboard or digital input 2);

13

  Program Run [transition]. 

The first closure allows to start program execu-
tion but a second closure restart the program 
execution from the beginning;

14

  Program Reset [transition]. 

A contact closure allows to reset program execution;

15

  Program Hold [transition]. 

The first closure allows to hold program execution 
and a second closure continue program execution;

16

  Program Run/Hold [status]. 

When the contact is closed the program is running;

17

  Program Run/Reset [status]. 

- Contact closed - Program run; 
- Contact open - Program reset;

18

  Sequential Set Point selection [transition] 

(see “Note about digital inputs”);

19

  SP1/SP2 selection [status];

20

  Binary selection of the Set Point made by digital 

input 1 (less significant bit) and digital input 2 
(most significant bit) [status];

21

  Digital input 1 will work in parallel with the 

 

button while digital input 2 will work in parallel 
with the 

 button.

Notes:   1. 

When [10] diF1 or [11] diF2 (e.g. diF1) are equal 
to 6 the instrument operates as follows: 

• 

When the contact is open, the control action is 
an heating action and the active Set Point is SP.

• 

When the contact is closed, the control action is 
a cooling action and the active Set Point is SP2.

2. 

When [10] diF1 = 20, [11] diF2 is forced to 20 and 
cannot perform another function.

3. 

When [10] diF1 = 20 and [11] diF2 = 20, the SP se-
lection will be in accordance with the following table:

Digital Input 1 Digital Input 2 Operative Set Point

Off

Off

Set Point 1

On

Off

Set Point 2

Off

On

Set Point 3

On

On

Set Point 4

4. 

When [10] diF1 is equal to 21, [11] diF2 is forced 
to 21 (up.du) and cannot perform another function.

5. 

When a “Sequential Set Point selection” is used 
(diF1 or diF2 = 18), every closure of the logic 
input increases the value of SPAT (active Set 
Point) of one step.  The selection is cyclic: 

SP

 -> 

SP2

 -> 

SP3

 -> 

SP4

.

6. 

Setting [10] diF1 or [11] diF2 equal to 6 the 
instrument makes the [66] tcH, [67] rcG and 
[68] tcc parameters available.

[12] di.A - Digital Inputs Action

Available: 

Always.

Range: 0

  DI1 Direct action, DI2 (if configured) Direct action;

1

  DI1 Reverse action,  

DI2 (if configured) Direct action;

2

  DI1 Direct action,  

DI2 (if configured) Reverse action;

3

  DI1 Reverse action,  

DI2 (if configured) Reverse action.

]

out Group - Output parameters

[13] o1.t - Out 1 type

Available: 

When the out 1 is a linear output.

Range: 0-20

 

0... 20 mA;

4-20

 

4... 20 mA;

0-10

 

0... 10 V;

2-10

 

2... 10 V.

[14] o1.F - Out 1 function

Available: 

Always.

Range:  • 

When the out 1 is a linear output:

nonE

 

Output not used.  With this setting the sta-
tus of this output  can be driven directly from 
serial link;

H.rEG

  Heating output;

c.rEG

  Cooling output;

r.inP

 

Measured value Analogue retransmission.

r.Err

 

Analogue retransmission of the measured 
error (PV-SP);

r.SP

 

Analogue retransmission of the operative 
Set Point;

r.SEr

 

Analogue retransmission of a value coming 
from serial link;

r.Po

 

Power output retransmission.

• 

When the out 1 is a digital output (relay or SSR):

nonE

 

Output not used.  With this setting the 
status of this output can be driven directly 
from serial link;

H.rEG

  Heating output;

c.rEG

  Cooling output;

AL

 

Alarm output;

t.out

 

Timer output;

t.HoF

  Timer out - OFF in Hold;

P.End

  Program end indicator;

P.HLd

  Program hold indicator;

P.uit

 

Program wait indicator;

P.run

 

Program run indicator;

P.Et1

 

Program Event 1;

P.Et2

 

Program Event 2;

or.bo

 

Out-of-range or burn out indicator;

P.FAL

  Power failure indicator;

bo.PF

  Out-of-range, Burnout and Power failure 

indicator;

St.By

  Stand By status indicator;

diF1

 

Repeats the digital input 1 status;

diF2

 

Repeats the digital input 2 status;

on

 

Out 1 always ON;

riSP

 

Inspection request.

Notes:   1. 

When two or more outputs are programmed in the 
same way, these outputs are driven in parallel.

Содержание KM2

Страница 1: ...protection IP65 is desired the optional gasket must be mounted 1 2 Dimensions 1 2 1 Controller with non removable terminals 63 3 14 11 44 5 PV AT 48 48 1 2 2 Removable terminals 40 15 5 18 85 26 15 8...

Страница 2: ...ration According to EN 60751 A2 2 3 5 V and mV Input mV V _ _ 1 2 Input impedance 1 M for mV Input 500 k for Volt Input 2 3 6 mA Input 0 4 20 mA input wiring for passive transmitter using the auxiliar...

Страница 3: ...Logic level 1 12 V 20 15 mA max Current Analogue Output mA 7 8 mA output 0 4 20 mA galvanically isolated RL max 600 Voltage Analogue Output V 7 8 V output 0 2 10 V galvanically isolated RL min 500 2...

Страница 4: ...m 1 78 0 023 x 1 78 0 023 in Weight 180 g max Power supply 24 240 VAC DC 10 Power consumption 5 VA max Insulation voltage 3000 V rms according to EN 61010 1 Display updating time 500 ms Sampling time...

Страница 5: ...he instrument has a complete parameter set that allows the user to adapt the controller to the destination application Note The instrument normally shows only the parameters consistent with the specif...

Страница 6: ...20 0 20 mA linear 4 20 4 20 mA linear 0 5 0 5 V linear 1 5 1 5 V linear 0 10 0 10 V linear 2 10 2 10 V linear When the code of the input type is equal to e see How to order paragraph J TC J 50 1000 C...

Страница 7: ...g 9 io3F from on to Out3 makes the 22 O3F parameter visible and equal to nonE 10 diF1 Digital input 1 function Available Always Range oFF No function 1 Alarm Reset status 2 Alarm acknowledge ACK statu...

Страница 8: ...ollowing table Digital Input 1 Digital Input 2 Operative Set Point Off Off Set Point 1 On Off Set Point 2 Off On Set Point 3 On On Set Point 4 4 When 10 diF1 is equal to 21 11 diF2 is forced to 21 up...

Страница 9: ...Output not used With this setting the status of this output can be driven directly from serial link H rEG Heating output c rEG Cooling output AL Alarm output t out Timer output t HoF Timer out OFF in...

Страница 10: ...ion Available When 25 AL1t is different from nonE Range 0 15 with the following rule 1 Not active at Power ON 2 Latched alarm manual reset 4 Acknowledgeable alarm 8 Relative alarm not active at Set Po...

Страница 11: ...ysteresis equal to 25 C 31 AL1d Alarm 1 delay Available When 25 AL1t is different from nonE Range 0 oFF 1 9999 seconds Note The alarm goes ON only when the alarm condition persists for a time longer t...

Страница 12: ...larm with alarm indication out of the band LHAi Absolute band alarm with alarm indication inside the band SE br Sensor break Note The relative alarm are relative to the current Set Point this may be d...

Страница 13: ...ilable When 49 Ct So is different from oFF Range 0 Automatic reset 1 Manual reset 2 Acknowledgeable 54 Ct Ld Load current threshold Available When 49 Ct So is different from oFF Range 0 Disabled 1 999...

Страница 14: ...and 1 00 it is possible to slow down the instrument action during Set Point approach Setting Fuoc 1 this function is disabled PV SP time 2 1 3 Available When 57 cont PID Range 0 2 00 Note Fast auto tu...

Страница 15: ...tH parameter 2 When the power limiter has a negative value the limit is applied to the cooling action the soft start function will be aborted when the measured value is lower or equal to SS tH paramet...

Страница 16: ...controllers The Slave zones use it as a Set Point trim The first zone is the master zone and it uses a Set Point equal to 210 C The second zone has a local Set Point equal to 45 C The third zone has...

Страница 17: ...m steps Some additional parameters allow to define the time scale the automatic RUN conditions and the instrument behaviour at the end of the program Notes 1 All steps can be modified during program e...

Страница 18: ...ent 1 Event 2 Event 1 Event 2 00 01 off off off on 10 01 on off off on 01 01 off on off on 11 01 on on off on 00 11 off off on on 10 11 on off on on 01 11 off on on on 11 11 on on on on 100 Pr S2 Set...

Страница 19: ...m Hold rES Program reset Note This parameter allows to manage program execution by a parameter PAn group Operator HMI 116 PAS2 Level 2 password Limited access level Available Always Range oFF Level 2...

Страница 20: ...o when ON OFF control is selected ct on CT measure during ON ct OF CT measure during OFF ct iS Instantaneous CT measurement 120 L dSP Secondary Display Management Available Always Range nonE Display O...

Страница 21: ...estart from the soak time minus the stored elapsed time In order to obtain this features the 126 dSPu Status of the instrument at Power ON parameter must be set to AS Pr If the 126 dSPu parameter is d...

Страница 22: ...ays when 132 Co tY 4 1 9999 hours when 132 Co tY 5 136 t Job Worked time not resettable Available Always Range 1 9999 days CAL group User calibration group This function allows to calibrate the comple...

Страница 23: ...9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set a password equal to 8...

Страница 24: ...If no button is pressed for more than 10 seconds the instrument goes back to the standard display and the new value of the last selected parameter will be lost 7 2 Enter the Limited access level The i...

Страница 25: ...sing the and buttons assign to this parameter the desired value 3 Push no buttons for more than 5 second or push the button In both cases the instrument stores the new value and returns to the Standar...

Страница 26: ...program is running the door is locked Application Example 2 edge bending machine with glue tank for wood At the working temperature the hot melt rapidly oxidizes and runs down from the dispenser For t...

Страница 27: ...and by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you set stand by mode during self tune execution the self tune function will be abort...

Страница 28: ...t there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 9 3 Disposal The appliance or the product must be disposed of...

Страница 29: ...52 F Ir J Exergen IRS J 46 785 C 50 1445 F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc PTC KTY81 121 55 150 C 67 302 F ntc NTC 103 AT2 50 110 C 58 230 F 0 60 0 60 mV 12 60 12 60 mV 0 20 0 20 mA 4 20 4...

Страница 30: ...output 0 NonE Output not used H rEG Heating output c rEG Cooling output r inP Measure retransmission r Err Error SP PV retransmission r SP Set Point retransmission r SEr Serial value retransmission r...

Страница 31: ...3 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Heater Break Down 16 Sensor Break 32 Overload on output 3 AL1 21 o2Ac Out 2 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse...

Страница 32: ...n stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default...

Страница 33: ...ditions 1 Alarm 1 enabled in stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 HBD group Heater Break Down Parameters no Param...

Страница 34: ...01 99 99 1 00 68 tcc Cooling output cycle time C rEG 1 0 2 130 0 s 20 0 69 rS Manual reset Integral pre load 1 100 0 100 0 0 0 70 od Delay at Power ON 2 0 00 oFF 00 01 99 59 hh mm oFF 71 St P Maximum...

Страница 35: ...s and seconds inF Forced to ON oFF 95 Pr S1 Set Point of the first soak dP From SPLL to SPHL 0 96 Pr G1 Gradient of the first ramp 1 0 1 999 9 Engineering Unit minute inF Step transfer inF 97 Pr t1 Ti...

Страница 36: ...r is running the display shows the timer counting up ti du When the timer is running the display shows the timer counting down PErc Percent of the power output used during soft start ct on Current mea...

Страница 37: ...measure starts from zero when a program runs end stops at the end of the program A new program execution will reset the value 4 Total worked days number of hours the instrument is turned ON divided by...

Страница 38: ...eters no Param Description Dec Point Values Default 137 AL P Adjust Low Point dp From 1999 to AH P 10 in engineering units 0 138 AL o Adjust Low Offset dp 300 300 E U 0 139 AH P Adjust High Point dp F...

Страница 39: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 39...

Страница 40: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 40...

Отзывы: