background image

Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 15

[70] od - Delay at power ON

Available: 

When at least one output is programmed as 
control output.

Range: oFF

 

Function not used;

0.01... 99.59

 hh.mm.

Notes:   1. 

This parameter defines the time during which 
(after a power ON) the instrument remains in 
stand by mode before to start all other function 
(control, alarms, program, etc.).

2. 

When a program with automatic start at power ON and 

od

 function are programmed, the instrument performs 

od

 function before to start the program execution.

3. 

When an auto-tune with automatic start at power 
ON and od function are programmed, the auto-
tune will start at the end of od delay.

General notes about soft start function.

The soft start function allows to limit the power output for 
a programmable time ([72] SSt) or up to a programmed 
threshold value ([73] SS.tH) (the first of the two).
When soft start function is running the lower display will 
show the message “SSt” alternately to the value selected by 
[120] “LdSP” parameter.

[71] St.P  - Maximum power output used during 

soft start

Available: 

When at list one output is programmed as control 
output.

Range: -100... +100%

.

Notes:   1. 

When St.P parameter have a positive value, the 
limit will be applied to the heating output(s) only.

2. 

When St.P parameter have a negative value, the 
limit will be applied to the cooling output(s) only.

3. 

When a program with automatic start at Power 
ON and soft start function are programmed, 
the instrument performs the soft start and the 
program function at the same time.

4. 

The auto-tune function will be performed after soft 
start function.

5. 

The Soft start function is available also when 
ON/OFF control is used. In ON condition the 
instrument will partialize the output using the 
programmed cycle time ([66] tc.H  or [68] tc.c).

[72] SSt - Soft start time 

Available: 

When at list one output is programmed as control 
output.

Range: oFF

 Function not used;

0.01... 7.59  hh.mm;

inF

  Soft start always active (

no “SSt” indication

).

[73] SS.tH - Threshold for soft start disabling

Available: 

When at list one output is programmed as control 
output.

Range: -1999... 9999

 engineering units.

Notes:   1. 

When the power limiter has a positive value (the 
limit is applied to the heating action) the soft start 
function will be aborted when the measured value 
is greater or equal to SS.tH parameter.

2. 

When the power limiter has a negative value (the 
limit is applied to the cooling action) the soft start 
function will be aborted when the measured value 
is lower or equal to SS.tH parameter.

]

SP Group - Set Point parameters

The SP group will be available only when at least one output 
is programmed as control output (H.rEG or C.rEG).

[74] nSP - Number of used Set Points

Available: 

When at least one output is programmed as 
control output.

Range: 1... 4

.

Note: 

When you change the value of this parameter, the 
instrument operates as follows:

• 

[81] A.SP parameter will be forced to SP.

• 

The instrument verifies that all used Set Point are 
within the limits programmed by [75] SPLL and 
[76] SPHL.  If an SP is out of this range, the instru-
ment forces it to the maximum acceptable value.

[75] SPLL - Minimum Set Point value

Available: 

When at least one output is programmed as 
control output.

Range: 

 From 

-1999

 to 

[76] SPHL

 engineering units

Notes:   1. 

When you change the [75] SPLL value, the inst.ru-
ment checks all local Set Points (SP, SP2, SP3 and 
SP4 parameters) and all Set Points of the program 
([95] Pr.S1, [100] Pr.S2, [105] Pr.S3, [110 Pr.S4 
parameters).  If an SP is out of this range, the instru-
ment forces it to the maximum acceptable value

2. 

A [77] SPLL change produces the following actions:

• 

When [82] SP.rt = SP the remote Set Point is 
forced to be equal to the active Set Point.

• 

When [82] SP.rt = trim the remote Set Point 
is forced to zero.

• 

When [82] SP.rt = PErc the remote Set Point 
is forced to zero.

[76] SPHL - Maximum Set Point value

Available: 

When at least one output is programmed as 
control output.

Range: 

From 

[75] SPLL

 to 

9999

 engineering units.

Note: 

For other details see [75] SPLL parameter.

[77] SP - Set Point 1

Available: 

When at least one output is programmed as 
control output.

Range: 

From 

[75] SPLL

 to 

[76] SPHL

 engineering units.

[78] SP 2 - Set Point 2

Available: 

When at least one output is programmed as con-
trol output and [74] nSP > 2.

Range: 

From 

[75] SPLL

 to 

[76] SPH

L engineering units.

[79] SP 3 - Set Point 3

Available: 

When at least one output is programmed as con-
trol output and [74] nSP > 3.

Range: 

From 

[75] SPLL

 to 

[76] SPH

L engineering units.

[80] SP 4 - Set Point 4

Available: 

When at least one output is programmed as con-
trol output and [74] nSP =4.

Range: 

From 

[75] SPLL

 to 

[76] SPH

L engineering units.

[81] A.SP - Selection of the active Set Point

Available: 

When at least one output is programmed as 
control output.

Range: 

From 

SP

 to 

[74] nSP

.

Notes:   1. 

A [81] A.SP change produces the following actions:

• 

When [82] SP.rt = SP - the remote Set Point 

Содержание KM2

Страница 1: ...protection IP65 is desired the optional gasket must be mounted 1 2 Dimensions 1 2 1 Controller with non removable terminals 63 3 14 11 44 5 PV AT 48 48 1 2 2 Removable terminals 40 15 5 18 85 26 15 8...

Страница 2: ...ration According to EN 60751 A2 2 3 5 V and mV Input mV V _ _ 1 2 Input impedance 1 M for mV Input 500 k for Volt Input 2 3 6 mA Input 0 4 20 mA input wiring for passive transmitter using the auxiliar...

Страница 3: ...Logic level 1 12 V 20 15 mA max Current Analogue Output mA 7 8 mA output 0 4 20 mA galvanically isolated RL max 600 Voltage Analogue Output V 7 8 V output 0 2 10 V galvanically isolated RL min 500 2...

Страница 4: ...m 1 78 0 023 x 1 78 0 023 in Weight 180 g max Power supply 24 240 VAC DC 10 Power consumption 5 VA max Insulation voltage 3000 V rms according to EN 61010 1 Display updating time 500 ms Sampling time...

Страница 5: ...he instrument has a complete parameter set that allows the user to adapt the controller to the destination application Note The instrument normally shows only the parameters consistent with the specif...

Страница 6: ...20 0 20 mA linear 4 20 4 20 mA linear 0 5 0 5 V linear 1 5 1 5 V linear 0 10 0 10 V linear 2 10 2 10 V linear When the code of the input type is equal to e see How to order paragraph J TC J 50 1000 C...

Страница 7: ...g 9 io3F from on to Out3 makes the 22 O3F parameter visible and equal to nonE 10 diF1 Digital input 1 function Available Always Range oFF No function 1 Alarm Reset status 2 Alarm acknowledge ACK statu...

Страница 8: ...ollowing table Digital Input 1 Digital Input 2 Operative Set Point Off Off Set Point 1 On Off Set Point 2 Off On Set Point 3 On On Set Point 4 4 When 10 diF1 is equal to 21 11 diF2 is forced to 21 up...

Страница 9: ...Output not used With this setting the status of this output can be driven directly from serial link H rEG Heating output c rEG Cooling output AL Alarm output t out Timer output t HoF Timer out OFF in...

Страница 10: ...ion Available When 25 AL1t is different from nonE Range 0 15 with the following rule 1 Not active at Power ON 2 Latched alarm manual reset 4 Acknowledgeable alarm 8 Relative alarm not active at Set Po...

Страница 11: ...ysteresis equal to 25 C 31 AL1d Alarm 1 delay Available When 25 AL1t is different from nonE Range 0 oFF 1 9999 seconds Note The alarm goes ON only when the alarm condition persists for a time longer t...

Страница 12: ...larm with alarm indication out of the band LHAi Absolute band alarm with alarm indication inside the band SE br Sensor break Note The relative alarm are relative to the current Set Point this may be d...

Страница 13: ...ilable When 49 Ct So is different from oFF Range 0 Automatic reset 1 Manual reset 2 Acknowledgeable 54 Ct Ld Load current threshold Available When 49 Ct So is different from oFF Range 0 Disabled 1 999...

Страница 14: ...and 1 00 it is possible to slow down the instrument action during Set Point approach Setting Fuoc 1 this function is disabled PV SP time 2 1 3 Available When 57 cont PID Range 0 2 00 Note Fast auto tu...

Страница 15: ...tH parameter 2 When the power limiter has a negative value the limit is applied to the cooling action the soft start function will be aborted when the measured value is lower or equal to SS tH paramet...

Страница 16: ...controllers The Slave zones use it as a Set Point trim The first zone is the master zone and it uses a Set Point equal to 210 C The second zone has a local Set Point equal to 45 C The third zone has...

Страница 17: ...m steps Some additional parameters allow to define the time scale the automatic RUN conditions and the instrument behaviour at the end of the program Notes 1 All steps can be modified during program e...

Страница 18: ...ent 1 Event 2 Event 1 Event 2 00 01 off off off on 10 01 on off off on 01 01 off on off on 11 01 on on off on 00 11 off off on on 10 11 on off on on 01 11 off on on on 11 11 on on on on 100 Pr S2 Set...

Страница 19: ...m Hold rES Program reset Note This parameter allows to manage program execution by a parameter PAn group Operator HMI 116 PAS2 Level 2 password Limited access level Available Always Range oFF Level 2...

Страница 20: ...o when ON OFF control is selected ct on CT measure during ON ct OF CT measure during OFF ct iS Instantaneous CT measurement 120 L dSP Secondary Display Management Available Always Range nonE Display O...

Страница 21: ...estart from the soak time minus the stored elapsed time In order to obtain this features the 126 dSPu Status of the instrument at Power ON parameter must be set to AS Pr If the 126 dSPu parameter is d...

Страница 22: ...ays when 132 Co tY 4 1 9999 hours when 132 Co tY 5 136 t Job Worked time not resettable Available Always Range 1 9999 days CAL group User calibration group This function allows to calibrate the comple...

Страница 23: ...9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set a password equal to 8...

Страница 24: ...If no button is pressed for more than 10 seconds the instrument goes back to the standard display and the new value of the last selected parameter will be lost 7 2 Enter the Limited access level The i...

Страница 25: ...sing the and buttons assign to this parameter the desired value 3 Push no buttons for more than 5 second or push the button In both cases the instrument stores the new value and returns to the Standar...

Страница 26: ...program is running the door is locked Application Example 2 edge bending machine with glue tank for wood At the working temperature the hot melt rapidly oxidizes and runs down from the dispenser For t...

Страница 27: ...and by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you set stand by mode during self tune execution the self tune function will be abort...

Страница 28: ...t there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 9 3 Disposal The appliance or the product must be disposed of...

Страница 29: ...52 F Ir J Exergen IRS J 46 785 C 50 1445 F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc PTC KTY81 121 55 150 C 67 302 F ntc NTC 103 AT2 50 110 C 58 230 F 0 60 0 60 mV 12 60 12 60 mV 0 20 0 20 mA 4 20 4...

Страница 30: ...output 0 NonE Output not used H rEG Heating output c rEG Cooling output r inP Measure retransmission r Err Error SP PV retransmission r SP Set Point retransmission r SEr Serial value retransmission r...

Страница 31: ...3 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Heater Break Down 16 Sensor Break 32 Overload on output 3 AL1 21 o2Ac Out 2 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse...

Страница 32: ...n stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default...

Страница 33: ...ditions 1 Alarm 1 enabled in stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 HBD group Heater Break Down Parameters no Param...

Страница 34: ...01 99 99 1 00 68 tcc Cooling output cycle time C rEG 1 0 2 130 0 s 20 0 69 rS Manual reset Integral pre load 1 100 0 100 0 0 0 70 od Delay at Power ON 2 0 00 oFF 00 01 99 59 hh mm oFF 71 St P Maximum...

Страница 35: ...s and seconds inF Forced to ON oFF 95 Pr S1 Set Point of the first soak dP From SPLL to SPHL 0 96 Pr G1 Gradient of the first ramp 1 0 1 999 9 Engineering Unit minute inF Step transfer inF 97 Pr t1 Ti...

Страница 36: ...r is running the display shows the timer counting up ti du When the timer is running the display shows the timer counting down PErc Percent of the power output used during soft start ct on Current mea...

Страница 37: ...measure starts from zero when a program runs end stops at the end of the program A new program execution will reset the value 4 Total worked days number of hours the instrument is turned ON divided by...

Страница 38: ...eters no Param Description Dec Point Values Default 137 AL P Adjust Low Point dp From 1999 to AH P 10 in engineering units 0 138 AL o Adjust Low Offset dp 300 300 E U 0 139 AH P Adjust High Point dp F...

Страница 39: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 39...

Страница 40: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 40...

Отзывы: