Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 4
2.6 Power Supply
Power
Supply
AC/DC
9
10
Supply Voltage:
24... 240 VAC/DC (±10%).
Notes: 1.
Before connecting the instrument to the power
line, make sure that line voltage is equal to the
voltage shown on the identification label;
2.
The polarity of the power supply has no importance;
3.
The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
4.
When the instrument is powered by the A01 key,
the outputs are NOT supplied and the instrument
can show the Out 3 Overload indication (
ouLd
).
3. TECHNICAL CHARACTERISTICS
3.1 Technical specification
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection:
IP65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection:
IP20 according to EN 60070-1;
Installation:
Panel mounting;
Terminal block:
16 M3 screw terminals for cables of
0.25... 2.5 mm
2
(AWG22... AWG14) with connection diagram;
Dimensions:
48 x 48, depth 88.3... 99 mm, (1.77 x 1.77 x
3.49... 3.9 in.) depending on the type of terminals used;
Panel cutout:
45
(+0.6)
x 45
(+0.6)
mm [1.78
(+0.023)
x 1.78
(+0.023)
in.];
Weight:
180 g max.;
Power supply:
24... 240 VAC/DC (±10%);
Power consumption:
5 VA max.;
Insulation voltage:
3000 V rms according to EN 61010-1;
Display updating time:
500 ms;
Sampling time:
130 ms;
Resolution:
30000 counts;
Total Accuracy:
±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Temperature drift:
It is part of the global accuracy;
Operating temperature:
0... 50°C (32... 122°F);
Storage temperature:
-30... +70°C (-22... +158°F);
Humidity:
20... 85% RH, not condensing.
Electromagnetic compatibility and safety requirements
Compliance:
•
EMC Directive (EN 61326-1),
•
Safety Directive (EN 61010-1);
Installation category:
II;
Pollution category:
2.
4. HOW TO ORDER
Power supply
U
= 24... 240 VAC/DC
Analoue input
C
= J, K, R, S, T, PT100, PT 1000 (2 wires), mA, mV, V
E
= J, K, R, S, T, NTC, PTC, mA, mV, V
Output 1
I
= 0/4... 20 mA, 0/2... 10 V
R
= Relay SPST 4 A (resistive load)
O
= VDC for SSR
Input/Output 3
D
= Digital Input DI1 +
Output 3 (VDC for SSR)/Pow. Supply/Digital Input DI2
C.T. Input
H
= Heater Break Down Alarm
Serial Communications
-
= TTL Modbus
S
= RS485 TTL Modbus
Connection type
-
= Standard (screw terminals not removable)
E
= Removable screw terminals
M
= Removable spring terminals
N
= Removable terminals (the fixed part only)
Output 2
-
= Not available
R
= Relay SPST 2 A (resistive load)
O
= VDC for SSR
Model
KM2
- = Controller
KM2T
= Con timer
KM2P
= Cont timer + programmer