background image

Ascon Tecnologic - KM2 Line - ENGINEERING MANUAL - PAG. 5

5.  CONFIGURATION PROCEDURE

5.1  Introduction

When the instrument is powered, it starts immediately to work 
according to the parameters values loaded in its memory.
The instrument behaviour and its performance are governed 
by the value of the stored parameters.
At the first start up the instrument uses a “default” parameter 
set (factory parameter set); this set is a generic one (e.g. a 
TC J input is programmed).

Before connecting the output actuators

,  

we recommend to configure the parameters to suit 
your application (e.g.: input type, Control strategy, 
alarms, etc.).

Do not change the parameter 

[5] Unit

 (Engineering 

Unit) during process control; the instrument scales the 
measurement (and the variables) but does not modify 
the value of the parameters related to the display.

To change these parameters you need to enter the 
“Configuration mode”.

5.2  Instrument behaviour at Power ON

At power ON the instrument can start in one of the following 
mode depending on its configuration:

Auto mode

 without program functions.

 

The upper display will show the measured value;

 

The lower display will show the Set Point value;

 

The decimal figure of the less significant digit of the lower 
display is OFF;

 

The instrument is performing the standard closed loop control.

Manual mode

 (oPLo).

 

The upper display shows the measured value;

 

The lower display shows the power output [preceded by 

H

 

(for heating) or 

C

 (for cooling)].  The MAN LED is lit;

 

The instrument does not perform Automatic control;

 

The control output can be: equal to 0 or equal to the value 
assigned to it before the power down.   In any case, it can 
be manually modified by 

 and 

 buttons.

Stand by mode

 (St.bY).

 

The upper display will show the measured value;

 

The lower display will show alternately the Set Point value 
and the message 

St.bY

 or 

od

;

 

The instrument does not perform any control (the control 
outputs are OFF);

 

The instrument is working as an indicator.

Auto mode 

with automatic program start up.

 

The upper display will show the measured value

 

The lower display will show one of the following information;

• 

The operative Set Point (when it is performing a ramp)

• 

The time of the segment in progress (when it is perform-
ing a soak);

• 

The Set Point value alternate with the message 

St.bY

;

 

In all cases, the decimal figure of the less significant digit 
of the lower display is lit.

We define all the above described conditions as “

Standard 

Display

”.

5.3 

Entering the “Configuration modes”

The instrument has a complete parameter set that allows the 
user to “adapt” the controller to the destination application.

Note: 

The instrument normally shows only the parameters 
consistent with the specific hardware and in accordance 
with the value assigned to the previous parameters  
(e.g.: if you set an output as “not used” the instrument 
will mask all other parameters related to that output).

5.3.1  Complete configuration procedure

The configuration parameters are collected in various 
groups.  Every group defines all parameters related with a 
specific function (e.g.: control, alarms, output functions).

1. 

Push the 

 button for more than 5 seconds.  The upper 

display will show 

PASS

 while the lower display will show 

0

.

2. 

Using 

 and 

 buttons set the programmed password.

Notes:   1. 

The factory default password for configuration 
parameters is equal to 30.

2. 

During parameter modification the instrument con-
tinue to perform the control.  In certain conditions, 
when a configuration change can produce a heavy 
bump to the process, it is advisable to temporarily 
stop the controller from controlling during the pro-
gramming procedure (control output will be OFF). 
A password equal to 2000 + the programmed 
value (e.g. 2000 + 30 = 2030). 
The control will restart automatically when the 
configuration procedure will be manually closed.

3. 

Push the 

 button. 

If the password is correct the display will show the acronym 
of the first parameter group preceded by the symbol: 

]

In other words the upper display shows: 

]inp

  

(group of the 

Input parameters

).

The instrument is in configuration mode.

5.3.2  How to exit the “Configuration mode”

Push 

 button for more than 5 seconds, the instrument will 

come back to the “standard display”.

5.4  Keyboard functions during 

parameter changing

  A short press allows to exit from the current parameter 

group and select a new parameter group.

 

A long press allows you to close the configuration 
parameter procedure (the instrument will come back 
to the “standard display”).

  When the upper display is showing a group and the 

lower display is blank, this key allows to enter in the 
selected group.

 

When the upper display is showing a parameter and 
the lower display is showing its value, this key allows 
to store the selected value for the current parameter 
and access the next parameter within the same group.

  Allows to increase the value of the selected parameter.
  Allows to decrease the value of the selected parameter.
 + 

  These two keys allow to return to the previous 

group.  Proceed as follows: 

 

Push the 

 button and maintaining the pressure, 

then push the 

 button; release both the buttons.

Note: 

The group selection is cyclic as well as the selection 
of the parameters in a group.

Содержание KM2

Страница 1: ...protection IP65 is desired the optional gasket must be mounted 1 2 Dimensions 1 2 1 Controller with non removable terminals 63 3 14 11 44 5 PV AT 48 48 1 2 2 Removable terminals 40 15 5 18 85 26 15 8...

Страница 2: ...ration According to EN 60751 A2 2 3 5 V and mV Input mV V _ _ 1 2 Input impedance 1 M for mV Input 500 k for Volt Input 2 3 6 mA Input 0 4 20 mA input wiring for passive transmitter using the auxiliar...

Страница 3: ...Logic level 1 12 V 20 15 mA max Current Analogue Output mA 7 8 mA output 0 4 20 mA galvanically isolated RL max 600 Voltage Analogue Output V 7 8 V output 0 2 10 V galvanically isolated RL min 500 2...

Страница 4: ...m 1 78 0 023 x 1 78 0 023 in Weight 180 g max Power supply 24 240 VAC DC 10 Power consumption 5 VA max Insulation voltage 3000 V rms according to EN 61010 1 Display updating time 500 ms Sampling time...

Страница 5: ...he instrument has a complete parameter set that allows the user to adapt the controller to the destination application Note The instrument normally shows only the parameters consistent with the specif...

Страница 6: ...20 0 20 mA linear 4 20 4 20 mA linear 0 5 0 5 V linear 1 5 1 5 V linear 0 10 0 10 V linear 2 10 2 10 V linear When the code of the input type is equal to e see How to order paragraph J TC J 50 1000 C...

Страница 7: ...g 9 io3F from on to Out3 makes the 22 O3F parameter visible and equal to nonE 10 diF1 Digital input 1 function Available Always Range oFF No function 1 Alarm Reset status 2 Alarm acknowledge ACK statu...

Страница 8: ...ollowing table Digital Input 1 Digital Input 2 Operative Set Point Off Off Set Point 1 On Off Set Point 2 Off On Set Point 3 On On Set Point 4 4 When 10 diF1 is equal to 21 11 diF2 is forced to 21 up...

Страница 9: ...Output not used With this setting the status of this output can be driven directly from serial link H rEG Heating output c rEG Cooling output AL Alarm output t out Timer output t HoF Timer out OFF in...

Страница 10: ...ion Available When 25 AL1t is different from nonE Range 0 15 with the following rule 1 Not active at Power ON 2 Latched alarm manual reset 4 Acknowledgeable alarm 8 Relative alarm not active at Set Po...

Страница 11: ...ysteresis equal to 25 C 31 AL1d Alarm 1 delay Available When 25 AL1t is different from nonE Range 0 oFF 1 9999 seconds Note The alarm goes ON only when the alarm condition persists for a time longer t...

Страница 12: ...larm with alarm indication out of the band LHAi Absolute band alarm with alarm indication inside the band SE br Sensor break Note The relative alarm are relative to the current Set Point this may be d...

Страница 13: ...ilable When 49 Ct So is different from oFF Range 0 Automatic reset 1 Manual reset 2 Acknowledgeable 54 Ct Ld Load current threshold Available When 49 Ct So is different from oFF Range 0 Disabled 1 999...

Страница 14: ...and 1 00 it is possible to slow down the instrument action during Set Point approach Setting Fuoc 1 this function is disabled PV SP time 2 1 3 Available When 57 cont PID Range 0 2 00 Note Fast auto tu...

Страница 15: ...tH parameter 2 When the power limiter has a negative value the limit is applied to the cooling action the soft start function will be aborted when the measured value is lower or equal to SS tH paramet...

Страница 16: ...controllers The Slave zones use it as a Set Point trim The first zone is the master zone and it uses a Set Point equal to 210 C The second zone has a local Set Point equal to 45 C The third zone has...

Страница 17: ...m steps Some additional parameters allow to define the time scale the automatic RUN conditions and the instrument behaviour at the end of the program Notes 1 All steps can be modified during program e...

Страница 18: ...ent 1 Event 2 Event 1 Event 2 00 01 off off off on 10 01 on off off on 01 01 off on off on 11 01 on on off on 00 11 off off on on 10 11 on off on on 01 11 off on on on 11 11 on on on on 100 Pr S2 Set...

Страница 19: ...m Hold rES Program reset Note This parameter allows to manage program execution by a parameter PAn group Operator HMI 116 PAS2 Level 2 password Limited access level Available Always Range oFF Level 2...

Страница 20: ...o when ON OFF control is selected ct on CT measure during ON ct OF CT measure during OFF ct iS Instantaneous CT measurement 120 L dSP Secondary Display Management Available Always Range nonE Display O...

Страница 21: ...estart from the soak time minus the stored elapsed time In order to obtain this features the 126 dSPu Status of the instrument at Power ON parameter must be set to AS Pr If the 126 dSPu parameter is d...

Страница 22: ...ays when 132 Co tY 4 1 9999 hours when 132 Co tY 5 136 t Job Worked time not resettable Available Always Range 1 9999 days CAL group User calibration group This function allows to calibrate the comple...

Страница 23: ...9 td Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set a password equal to 8...

Страница 24: ...If no button is pressed for more than 10 seconds the instrument goes back to the standard display and the new value of the last selected parameter will be lost 7 2 Enter the Limited access level The i...

Страница 25: ...sing the and buttons assign to this parameter the desired value 3 Push no buttons for more than 5 second or push the button In both cases the instrument stores the new value and returns to the Standar...

Страница 26: ...program is running the door is locked Application Example 2 edge bending machine with glue tank for wood At the working temperature the hot melt rapidly oxidizes and runs down from the dispenser For t...

Страница 27: ...and by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you set stand by mode during self tune execution the self tune function will be abort...

Страница 28: ...t there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 9 3 Disposal The appliance or the product must be disposed of...

Страница 29: ...52 F Ir J Exergen IRS J 46 785 C 50 1445 F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc PTC KTY81 121 55 150 C 67 302 F ntc NTC 103 AT2 50 110 C 58 230 F 0 60 0 60 mV 12 60 12 60 mV 0 20 0 20 mA 4 20 4...

Страница 30: ...output 0 NonE Output not used H rEG Heating output c rEG Cooling output r inP Measure retransmission r Err Error SP PV retransmission r SP Set Point retransmission r SEr Serial value retransmission r...

Страница 31: ...3 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Heater Break Down 16 Sensor Break 32 Overload on output 3 AL1 21 o2Ac Out 2 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse...

Страница 32: ...n stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default...

Страница 33: ...ditions 1 Alarm 1 enabled in stand by mode 2 Alarm 1 enabled in out of range conditions 3 Alarm 1 enabled in stand by mode and out of range conditions 0 HBD group Heater Break Down Parameters no Param...

Страница 34: ...01 99 99 1 00 68 tcc Cooling output cycle time C rEG 1 0 2 130 0 s 20 0 69 rS Manual reset Integral pre load 1 100 0 100 0 0 0 70 od Delay at Power ON 2 0 00 oFF 00 01 99 59 hh mm oFF 71 St P Maximum...

Страница 35: ...s and seconds inF Forced to ON oFF 95 Pr S1 Set Point of the first soak dP From SPLL to SPHL 0 96 Pr G1 Gradient of the first ramp 1 0 1 999 9 Engineering Unit minute inF Step transfer inF 97 Pr t1 Ti...

Страница 36: ...r is running the display shows the timer counting up ti du When the timer is running the display shows the timer counting down PErc Percent of the power output used during soft start ct on Current mea...

Страница 37: ...measure starts from zero when a program runs end stops at the end of the program A new program execution will reset the value 4 Total worked days number of hours the instrument is turned ON divided by...

Страница 38: ...eters no Param Description Dec Point Values Default 137 AL P Adjust Low Point dp From 1999 to AH P 10 in engineering units 0 138 AL o Adjust Low Offset dp 300 300 E U 0 139 AH P Adjust High Point dp F...

Страница 39: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 39...

Страница 40: ...Ascon Tecnologic KM2 Line ENGINEERING MANUAL PAG 40...

Отзывы: