Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 1

e34B

DIGITAL ELECTRONIC 

TEMPERATURE CONTROLLER 

WITH DEFROSTING FUNCTION

OPERATING INSTRUCTIONS

20/06 - code: ISTR_M_e34B_E_02_--

ASCON TECNOLOGIC S.r.l.

Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY 
Tel.:  +39 0381 69871 - Fax: +39 0381 698730 

http:\\www.ascontecnologic.com

 

[email protected]

PREFACE

D

D

This manual contains the information necessary for 
the product to be installed correctly and also instruc-
tions for its maintenance and use; we therefore recom-
mend that the utmost attention is paid to the following 
instructions and to save it.

This document is the exclusive property of Ascon Tecnologic 
S.r.l. which forbids any reproduction and divulgation, even 
partially, of the document, unless expressly authorized.
Ascon Tecnologic S.r.l. reserves the right to make any formal 
or functional changes at any moment and without any notice.
Ascon Tecnologic S.r.l. and its legal representatives do not 
assume any responsibility for any damage to people, things 
or animals deriving from violation, wrong or improper use or 
in any case not in compliance with the instrument features.

D

D

Whenever a failure or a malfunction of the device 
may cause dangerous situations for persons, thing 
or animals, please remember that the plant has to be 
equipped with additional electromechanical devices 
which will guarantee safety.

1.  INSTRUMENT DESCRIPTION

1.1 

General description

The model 

e34B

 is a microprocessor based digital electronic 

temperature controller that is typically used in cooling applica-
tions with 

ON/OFF temperature control

 and 

defrost

 

control

 

at time intervals, by arrival at temperature or by length of time 
of continuous compressor operation through stopping the 
compressor, electric heating or hot gas/cycle inversion.
The controller is equipped with special 

defrost optimization 

functions

 and with other functions that can be used to obtain 

energy savings from the controlled system

.

The instrument has up to 

4 relay outputs

 and up to 

3 NTC 

temperature probes

 inputs 

one of which

 can be 

config-

ured as digital input

.

The instrument has an 

internal buzzer

 for the 

acoustic 

alarms

 signalling and a 

voltage alarm system

 that deacti-

vates the outputs if the 

mains voltage

 is 

too high/low

.

Index

1.  Instrument description ............................................... 1

1.1  General description ........................................................... 1
1.2  Front panel pescription ..................................................... 2

2. Programming ............................................................... 2

2.1  Fast Normal Set Point Programming................................. 2
2.2  Standard mode parameters programming ........................ 3
2.3  Parameter protection using a Password ........................... 3
2.4  Customized mode parameter programming  

(parameters programming level) ....................................... 3

2.5  Reset parameters to default value .................................... 4
2.6  Keyboard lock function ...................................................... 4
2.7  Variables display ............................................................... 4

3.  Usage warnings ........................................................... 4

3.1  Admitted use ..................................................................... 4

4.  Installation warnings ................................................... 5

4.1  Mechanical mounting ........................................................ 5
4.2  Dimensions [mm] .............................................................. 5
4.3  Electrical connections ....................................................... 5

5. Functions ..................................................................... 6

5.1  ON/Stand-by function ........................................................ 6
5.2  Normal, Economic and Turbo operation ............................ 6
5.3  Measure and display configuration ................................... 7
5.4  Digital input configuration .................................................. 7
5.5  Outputs and buzzer configuration ..................................... 7
5.6  Temperature control .......................................................... 8
5.7  Compressor protection function and power-on delay ........ 9
5.8  Defrost control ................................................................... 9
5.9  Evaporator fans control ................................................... 11
5.10  Alarm functions ............................................................... 12
5.11  Function of keys 

/  and  /

 ................................... 13

6. Accessories ............................................................... 13

6.1  Parameters configuration by A01 .................................... 13
6.2  Parameters configuration by AFC1 ................................. 14
6.3  Remote display “TVR Y” .................................................. 14
6.4  RS485 Serial Interface with ARS1 .................................. 14

7.  Programmable parameters table .............................. 15
8.  Problems, maintenance ............................................ 18

8.1 Notifications .................................................................... 18
8.2 Cleaning .......................................................................... 18
8.3 Disposal .......................................................................... 18

9.  Warranty and Repairs ............................................... 18
10. Technical data ............................................................ 18

10.1  Electrical characteristics ................................................. 18
10.2  Mechanical characteristics .............................................. 18
10.3  Functional features ......................................................... 19

11. Instrument ordering code ......................................... 19

Содержание e34B

Страница 1: ...g the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to obtain energy savings f...

Страница 2: ...el of the parameters Pressed together with the key for 5 s allows the keyboard unlock 5 LED dp Stand by During the normal operation is the decimal point when the instrument is placed in Stand by mode...

Страница 3: ...d is correct the instrument displays the code of the first parameter and it will be possible to program the in strument in the same way described in the previous section The password protection can be...

Страница 4: ...yable variable and its value So with the keys keys you can view all the variables pr1 Probe Pr1 temperature measurement Pr2 Probe Pr3 temperature measurement Pr3 Probe Pr3 temperature measurement Lt M...

Страница 5: ...nt con nection inside housing it is not equipped with either switches or internal devices to protect against current overloads the installation will include an overload protection and a two phase circ...

Страница 6: ...ng Elapsed the itt time after the door has been closed and from the activation of SPE Setpoint Eco mode by iEt parameter Eco Normal switching To use this function it is necessary to set the Digital In...

Страница 7: ...delayed for the time programmed with parameter iti The iFi parameter can be configured for the following functions 0 Digital input not active 1 Cell door opening with NO contact at input closure and...

Страница 8: ...ration can be used as a control of the shop window lighting anti fogging resistors or other utilities If present the internal buzzer can be configured by param eter obu for the following functions oF...

Страница 9: ...tions are disabled if the relative parameters are set to OFF oF 5 8 Defrost control The defrost control acts on the outputs configured as ot dF ad dH The type of defrost is set by the parameter ddt EL...

Страница 10: ...y occur with normal op eration when to ensure more system efficiency the defrost ing interval is programmed with a time that is often too short With the parameter ddd Defrost interval percentage reduc...

Страница 11: ...fine the display behaviour during defrost on The ddL parameter locks the display at the last Pr1 temperature reading during all the defrost cycle until at the end of defrost the temperature has not re...

Страница 12: ...l the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory oo1 oo2 oo3 oo4 An n it is necessary to set the parameter AtA on 5 10 1 Tempera...

Страница 13: ...g 200 V off off off ON ON HU LU AL 10 V 10 V Volt time V 5 11 Function of keys and The key function can be defined using the tUF param eter to perform the following functions oF The key carries out no...

Страница 14: ...perature measured by the Pr1 probe using a 2 digit display Power supply TVR Y cable length 10 m max For more information see the user manual for the TVR Y device 6 4 RS485 Serial Interface with ARS1 D...

Страница 15: ...en Door with Fan Fn and Output ot Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF Di...

Страница 16: ...42 dEE Lengh of defrost cycle for evaporator probe error oF Function disabled 1 59 s 1 99 min 10 43 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 44 FtF...

Страница 17: ...tput function oF Function disabled 1 Control output ot delayed 2 Manual activation by key oF 69 otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 70 tUF Key Function oF No...

Страница 18: ...ust be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1...

Страница 19: ...ERING CODE MODEL e34B Instrument with mechanical keyboard e34NB Instrument with NFC technology and mechanical keyboard a POWER SUPPLY H 100 240 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 R Relay SPST NO 16A AC...

Страница 20: ...Ascon Tecnologic e34B OPERATING INSTRUCTIONS PAG 20...