Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 6

5.  FUNCTIONS

5.1 

ON/Stand-by function

Once powered the instrument can assume 2 different conditions:

ON

:  Means that the controller uses the control functions.

STAND-BY:   

Means that the controller uses no control function and 
the display is turned off except for the Stand-by LED.

The transition between Standby and ON is equivalent to 
power ON the instrument providing the electrical power
In case of power failure, the system always sets itself in the 
condition it was in before the black-out
The ON/Stand-by function can be selected:

 

With the key 

/  pressed for 1 s if 

tUF

 = 

3

;

 

Using the Digital Input if parameter 

iFi

 = 

7

;

5.2 

Normal, Economic and Turbo operation

The instrument allows to pre-set 5 different control Set 
points, 3 of which (

SP1

SP2

SP3

) are 

Normal

, one 

SPE 

is 

Economic

 (or Eco) and one 

SPH

 

Turbo

.

Associated with each Setpoint there is the relative differential 
(hysteresis): 

Normal

 - 

rd

Eco

 - 

rEd

 and 

Turbo

 - 

rHe

.

As already explained at paragraph “

2.1 - Quick setting of the 

normal Set Point

” the “

Normal

” operating set point can be 

only 

1

 (

Sp1

 if 

tEd

 = 

1

) or selectable between 3 preset values (

SP1

SP2

SP3

 if 

tEd

 = 

2

).

Note: 

In the following examples the Set point is generally 
indicated as 

SP

, however the instrument 

operates on 

the basis of the active Set Point

.

5.2.1 

Normal/Eco operation selection

This function can be used when you need to switch two func-
tional temperatures (eg. Day/Night or week-day/week-end).

Pr1

Temp.

SPE

SP

Door

rd

rEd

iEt

time

Normal

DAY (Shop open)

DAY (Shop open)

NIGHT (Shop closed)

Normal

eco

Out

L1

ON

OFF

ON

Example of automatic 

ECO

/

Normal

 mode activation.  during 

the business hours the door is opened frequently and the 
controller remains in 

Normal

 mode.  After the 

iEt

 time has 

elapsed since the door has not been opened anymore, the 
controller switches to 

ECO

 mode.  As soon as the door is 

opened again, the controller returns to 

Normal

 mode.

The Normal/Eco operation can be selected in manual mode:

 

Using the 

/  key if parameter 

tUF

 = 

2

;

 

Using the Digital Input if parameter 

iFi

 = 

6

.

The Normal/Eco operation can be selected in automatic mode:

 

Elapsed the 

iEt

 time after the door has been closed 

(Normal/Eco switching).

 

At door opening if the 

SPE

 Setpoint is activated by 

iEt

 

parameter (Eco/Normal switching).

 

Elapsed the 

itt

 time after the door has been closed and 

from the activation of 

SPE

 Setpoint (Eco mode) by 

iEt

 

parameter (Eco/Normal switching).

To use this function, it is necessary to set the Digital Input as: 

iFi

 = 

1

2

 or 

3

 (door open Input).

If 

iEt

 = 

oF

 the selection of Eco/Normal modes via the digital 

input is disabled.
If 

itt

 = 

oF

 the time-out switching from Eco to Normal mode 

is disabled.

Temp.

SPE

SP

rd

rEd

iEt

 (1)

iEt

time

Normal

Normal

eco

iTt

 (2)

Pr1

Switching to Economic mode is indicated by the label 

Eco

.  

In addition, the selection of the 

Eco

 mode is always com-

bined with the function of turning OFF the output configured 
as 

L1

 (showcase light).

5.2.2 

Turbo/Normal/Eco mode selection

Turbo

 mode can be used manually when, after a refrigerator 

load phase, a products temperature decrease is required.
It can instead be used automatically to allow the recovery of 
the products temperature at the end of an 

Economic

 cycle.

Turbo

 mode can be selected manually:

 

Pressing 

/  

turbo

 and maintaining it pressed for 5 s;

 

From digital input if parameter 

i.Fi

 = 

8

;

Turbo

 mode can be selected automatically:

 

Leaving 

Eco

 mode (only if 

rHC

 = 

C3

)

 

Every time the instrument is switched ON (only if 

rHC

 = 

C3 

and 

Pr1

 > 

SPE

 + 

rEd

)

The instrument quits 

Turbo

 mode automatically at the end of 

rtC

 time or manually using the programmed command (key or 

digital input), the instrument always returns to 

Normal

 mode.

Setting 

rHC

 = 

C3 

the operating cycle is:

 

At power ON, the instrument starts in the mode it was in 
when it was switched OFF (

Normal

 or 

Eco

) unless the tem-

perature at power ON is > 

SPE

 + 

rEd

.  In this case (see 

the drawing) a 

Turbo

 cycle is automatically started.

 

After time 

rtC

 the instrument automatically switches to 

Normal

 mode.

 

If the door is opened frequently, the instrument remains in 

Normal

 mode.  If however the door is not opened for time set 

at 

iEt

 parameter, it automatically switches to 

Eco

 mode.

 

The instrument remains in 

Eco

 mode until the door is 

opened again or, if set, until the time-out 

itt

.

 

On leaving 

Eco

 mode the instrument therefore runs a 

Turbo

 cycle to allow product temperature to be restored, 

after which it reverts to 

Normal

 mode and so on.

Temp.

SPE

SP

SPH

rHd

rEd

itt

 (2)

rtC

rtC

time

Normal

Turbo

Turbo

iEt

 (1)

rd

Pr1

eco

Notes: 1. 

The time 

iEt

 is reset every time the door is ope-

ned, in the case shown the door is always closed.

2. 

The 

itt

 time is stopedas soon as the door is 

opened, the instrument immediately switches 
to 

Turbo

 mode.  In the case shown, the door is 

always closed.

Содержание e34B

Страница 1: ...g the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to obtain energy savings f...

Страница 2: ...el of the parameters Pressed together with the key for 5 s allows the keyboard unlock 5 LED dp Stand by During the normal operation is the decimal point when the instrument is placed in Stand by mode...

Страница 3: ...d is correct the instrument displays the code of the first parameter and it will be possible to program the in strument in the same way described in the previous section The password protection can be...

Страница 4: ...yable variable and its value So with the keys keys you can view all the variables pr1 Probe Pr1 temperature measurement Pr2 Probe Pr3 temperature measurement Pr3 Probe Pr3 temperature measurement Lt M...

Страница 5: ...nt con nection inside housing it is not equipped with either switches or internal devices to protect against current overloads the installation will include an overload protection and a two phase circ...

Страница 6: ...ng Elapsed the itt time after the door has been closed and from the activation of SPE Setpoint Eco mode by iEt parameter Eco Normal switching To use this function it is necessary to set the Digital In...

Страница 7: ...delayed for the time programmed with parameter iti The iFi parameter can be configured for the following functions 0 Digital input not active 1 Cell door opening with NO contact at input closure and...

Страница 8: ...ration can be used as a control of the shop window lighting anti fogging resistors or other utilities If present the internal buzzer can be configured by param eter obu for the following functions oF...

Страница 9: ...tions are disabled if the relative parameters are set to OFF oF 5 8 Defrost control The defrost control acts on the outputs configured as ot dF ad dH The type of defrost is set by the parameter ddt EL...

Страница 10: ...y occur with normal op eration when to ensure more system efficiency the defrost ing interval is programmed with a time that is often too short With the parameter ddd Defrost interval percentage reduc...

Страница 11: ...fine the display behaviour during defrost on The ddL parameter locks the display at the last Pr1 temperature reading during all the defrost cycle until at the end of defrost the temperature has not re...

Страница 12: ...l the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory oo1 oo2 oo3 oo4 An n it is necessary to set the parameter AtA on 5 10 1 Tempera...

Страница 13: ...g 200 V off off off ON ON HU LU AL 10 V 10 V Volt time V 5 11 Function of keys and The key function can be defined using the tUF param eter to perform the following functions oF The key carries out no...

Страница 14: ...perature measured by the Pr1 probe using a 2 digit display Power supply TVR Y cable length 10 m max For more information see the user manual for the TVR Y device 6 4 RS485 Serial Interface with ARS1 D...

Страница 15: ...en Door with Fan Fn and Output ot Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF Di...

Страница 16: ...42 dEE Lengh of defrost cycle for evaporator probe error oF Function disabled 1 59 s 1 99 min 10 43 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 44 FtF...

Страница 17: ...tput function oF Function disabled 1 Control output ot delayed 2 Manual activation by key oF 69 otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 70 tUF Key Function oF No...

Страница 18: ...ust be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1...

Страница 19: ...ERING CODE MODEL e34B Instrument with mechanical keyboard e34NB Instrument with NFC technology and mechanical keyboard a POWER SUPPLY H 100 240 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 R Relay SPST NO 16A AC...

Страница 20: ...Ascon Tecnologic e34B OPERATING INSTRUCTIONS PAG 20...

Отзывы: