background image

Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 4

2.5 

Reset parameters to default value

The instrument allows the reset of the parameters to values 
programmed in factory as default
To restore the default parameters value set value 

-48

 at 

r.p

 password request.  Therefore, to make the reset to the 

default parameters, enable the Password using the 

tPP

 

parameter so that the 

r.p

 setting is requested, at this point 

insert 

-48

 instead of the programmed access password.

Once confirmed the password with the 

/  key the display 

shows “

---

” for 2 s therefore the instrument resets all the 

parameters to factory default setting.

2.6 

Keyboard lock function

On the instrument it is possible to completely lock the keyboard.
This function is useful when the controller is in an accessible 
area and the changes must be avoided.
To activate the keyboard lock it is enough program the pa-
rameter 

tLo

 to a value different from 

oF

.

The 

tLo

 value is the keys inactivity time after which the key-

board will be automatically locked.
Therefore, pressing no buttons for the time set at 

tLo

, the 

instrument automatically disables the keys normal functions.
When the keyboard is locked, if any of the key is pressed, 
the display showss 

Ln

 to indicate that the lock is active.

To unlock the keyboard it is enough to contemporaneously 
press 

/

 

/  keys and keep them pushed for 5 s, after 

which the label 

LF

 appears on the display and all the key 

functions will be available again.

2.7 

Variables display

The display normally shows the variable set with parameter 

idS

, but it is possible to display all the measurement and 

operating variables by simultaneously pressing the 

/  

and 

/  

turbo

 keys for 5 s.

The display will alternately show the code that identifies the 
first displayable variable and its value.
So with the 

/

 keys keys you can view all the variables:

pr1

 Probe 

Pr1

 temperature measurement;

Pr2

 Probe 

Pr3

 temperature measurement;

Pr3

 Probe 

Pr3

 temperature measurement;

Lt

 

Minimum stored temperature readed by 

Pr1

 probe;

Ht

 

Mmaximum stored temperature readed by 

Pr1

 probe.

Peak values 

Lt

 and 

Ht

 are not saved when power failure 

occours; a peak can be reset by pressing the 

/  button 

for 3 s while viewing that peak.  After 3 s, the display shows 

---

” for an instant to indicate that the displayed peak has 

been erased and assumes the temperature measured at that 
moment as the new peak.  To reset the other peak repeat the 
procedure while the system is displaying its value.
To exit the variable display mode, press no keys for about 
10 s or press the 

/  key.

-5.3

Pr2

Previous

Variable

Normal mode

Instrument variable

Next

Variable

2 s

5 s

3.  USAGE WARNINGS

3.1 

Admitted use

D

D

The instrument has been projected and manufactured 
as a measuring and control device to be used accord-
ing to EN60730-1 at altitudes operation below 2000 m.  

Using the instrument for applications not expressly permitted 
by the above mentioned rule must adopt all the necessary 
protective measures.
The instrument 

MUST NOT BE USED

 in dangerous environ-

ments (flammable or explosive) without adequate protections.
The instrument used with NTC 103AT11 probe (identifiable 
by the printed code “103AT-11” visible on the sensor part) 
is compliant with standard EN 13485 (“Thermometers for 
measuring the air and product temperature for the transport, 
storage and distribution of chilled, frozen, deep-frozen/quick-
frozen food and ice cream”) with the following classification: 
[EN13485 air, S, A, 2, -50°C +90°C]
Remember that the end user must periodically check and veri-
fy the thermometers in compliance with standard EN 13486.
The installer must ensure that the EMC rules are respected, 
also after the instrument installation, if necessary using 
proper filters.

Содержание e34B

Страница 1: ...g the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to obtain energy savings f...

Страница 2: ...el of the parameters Pressed together with the key for 5 s allows the keyboard unlock 5 LED dp Stand by During the normal operation is the decimal point when the instrument is placed in Stand by mode...

Страница 3: ...d is correct the instrument displays the code of the first parameter and it will be possible to program the in strument in the same way described in the previous section The password protection can be...

Страница 4: ...yable variable and its value So with the keys keys you can view all the variables pr1 Probe Pr1 temperature measurement Pr2 Probe Pr3 temperature measurement Pr3 Probe Pr3 temperature measurement Lt M...

Страница 5: ...nt con nection inside housing it is not equipped with either switches or internal devices to protect against current overloads the installation will include an overload protection and a two phase circ...

Страница 6: ...ng Elapsed the itt time after the door has been closed and from the activation of SPE Setpoint Eco mode by iEt parameter Eco Normal switching To use this function it is necessary to set the Digital In...

Страница 7: ...delayed for the time programmed with parameter iti The iFi parameter can be configured for the following functions 0 Digital input not active 1 Cell door opening with NO contact at input closure and...

Страница 8: ...ration can be used as a control of the shop window lighting anti fogging resistors or other utilities If present the internal buzzer can be configured by param eter obu for the following functions oF...

Страница 9: ...tions are disabled if the relative parameters are set to OFF oF 5 8 Defrost control The defrost control acts on the outputs configured as ot dF ad dH The type of defrost is set by the parameter ddt EL...

Страница 10: ...y occur with normal op eration when to ensure more system efficiency the defrost ing interval is programmed with a time that is often too short With the parameter ddd Defrost interval percentage reduc...

Страница 11: ...fine the display behaviour during defrost on The ddL parameter locks the display at the last Pr1 temperature reading during all the defrost cycle until at the end of defrost the temperature has not re...

Страница 12: ...l the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory oo1 oo2 oo3 oo4 An n it is necessary to set the parameter AtA on 5 10 1 Tempera...

Страница 13: ...g 200 V off off off ON ON HU LU AL 10 V 10 V Volt time V 5 11 Function of keys and The key function can be defined using the tUF param eter to perform the following functions oF The key carries out no...

Страница 14: ...perature measured by the Pr1 probe using a 2 digit display Power supply TVR Y cable length 10 m max For more information see the user manual for the TVR Y device 6 4 RS485 Serial Interface with ARS1 D...

Страница 15: ...en Door with Fan Fn and Output ot Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF Di...

Страница 16: ...42 dEE Lengh of defrost cycle for evaporator probe error oF Function disabled 1 59 s 1 99 min 10 43 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 44 FtF...

Страница 17: ...tput function oF Function disabled 1 Control output ot delayed 2 Manual activation by key oF 69 otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 70 tUF Key Function oF No...

Страница 18: ...ust be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1...

Страница 19: ...ERING CODE MODEL e34B Instrument with mechanical keyboard e34NB Instrument with NFC technology and mechanical keyboard a POWER SUPPLY H 100 240 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 R Relay SPST NO 16A AC...

Страница 20: ...Ascon Tecnologic e34B OPERATING INSTRUCTIONS PAG 20...

Отзывы: