Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 7

5.3 

Measure and display configuration

With parameter 

iuP

 it is possible to select the tempera-

ture engineering unit and the desired measure resolution 
(

C0

 = °C/1°; 

C1 

= °C/0.1°; 

F0

 = °F/1°; 

F1

 = °F/0.1°).

The instrument allows the measure calibration, which can 
be used to recalibrate the instrument according to applica-
tion needs, the calibration is made by using parameters 

iC1

 

(input Pr1), 

iC2

 (Pr2 input) and 

iC3

 (Pr3 input).

Parameters 

iP2

/

iP3

 allow to select the controller usage of 

Pr2

/

Pr3

 probe measure as:

EP

 

Evaporator probe

: used to manage the defrost and 

the evaporator fans (see relative functions).

Au

 

Auxiliary probe

: can be used as a display-only probe, 

but it is also possible to associate temperature alarms 
(possible uses: product probe, anti-freeze probe, etc.);

DG

  Digital Input only for 

Pr3

 input.

If probe input is not used, set 

iP2

 or 

ip3

 = 

oF

.

Two inputs cannot be set to perform the same function.   
If two inputs are set to do the same function, this is done 
only by the 

Pr2

 input.

Using 

iFt

 parameter is possible to set a software filter to 

decrease the input sensibility to rapid temperature changes, 
increasing the sampling time, to stabilize the reading of the 
measurement inputs.
In addition to this filter there are other two similar filters used 
only for the 

Pr1

 probe measure visualization, these regard the 

increasing (

tdu

 parameter) and the decreasing (

tdd

) of 

Pr1

 

measurement to avoid to display fast temperature variations.
The filter blocks the maximum decrement displayed at 0.1° 
every 

tdd

 seconds and the maximum increase displayed 

every 

tdu

 seconds. These filters are reset at power OFF.

Through the 

idS

 parameter is possible to set the variable 

normally displayed:

P1

 Pr1 

probe measurement;

P2

 Pr2 

probe measurement;

P3

 Pr3 

probe measurement;

SP

 

Active Set Point;

Ec

 

Pr1

 probe measure if the instrument is in 

Normal

 

mode, the label 

Eco

 if the instrument is in 

Eco

 mode;

oF

 

If the numerical display must be switched OFF.

When one of the measures is displayed (

idS

 = 

P1

/

P2/P3

/

Ec

the 

iCU

 parameter allows to set an offset that is applied only 

to the displayed variable (all controls are made according to 
the correct temperature value, changed only by the calibra-
tion parameters).
Regardless of what is set at 

idS

 parameter, all the measure-

ment variables can be shown as descibed at paragraph: “

2.7 

- Variables display

”.

It is also noted that the 

Pr1

 probe display can also be changed 

by “

Defrost display lock

” function via the 

ddL

 parameter  

(see the 

Defrost function

).

5.4 

Digital input configuration

The digital input function (available on 

terminal 12

) is defined 

using the 

iFi

 parameter and the action is delayed for the 

time programmed with parameter 

iti

.  The 

iFi

 parameter 

can be configured for the following functions:

Digital input not active;

Cell door opening with NO contact: at input closure (and 
after the 

iti

) the instrument displays alternately 

oP

 and 

the variable set at 

idS

 parameter.  With this mode of 

operation of the digital input activates also the time set 
with parameter 

AoA

 elapsed which the alarm is activated 

to warn that the door has been left open.  In addition, at 
door opening, the instrument returns to 

Normal

 operation 

if it was in 

Eco

 mode and the 

Eco

 mode activation was 

enabled through parameter 

iEt

;

Cell door opening with NO contact: Similar to 

iFi

 = 

1

 

but with evaporator fans stop.  In addition, at open door 
alarm intervention (

AoA

), the fans are restarted;

Cell door opening with compressor and fan outputs lock 
and NO contact: similar to 

iFi

 = 

2

 but with compressor 

and fans lock.  At open door alarm intervention (

AoA

both the fans and the compressor are re-activated.

External alarm signal with NO contact: at input closing 
(and after the 

iti

 time) the alarm is activated and the 

instrument alternately shows on the display: 

AL

 and the 

variable set with parameter 

idS

;

External alarm signal withall control outputs disabled and 
NO contact: at input closing (and after the 

iti

 time) all 

the control outputs are disabled, the alarm is activated 
and the instrument alternately shows on the display: 

AL

 

and the variable set with parameter 

idS

;

Normal

/

Eco

 mode selection with NO contact: at input clos-

ing (and after the 

iti

 time) the instrument switches to 

Eco

 operation mode.  Opening the digital input, the instru-

ment returns in 

Normal

 operation mode.

Instrument On/Off (stand-by) selection with NO contact: 
at input closing (and after the 

iti

 time) the instrument 

is switched ON while it is placed in Stand-by mode when 
the digital input is open;

Turbo

 cycle activation command with NO contact: at in-

put closing (and after the 

iti

 time) the instrument starts 

a Turbo cycle;

-1, -2, -3, etc.

 - Features identical to the above but obtained 

through a NC contact and a reversed logic operation.

5.5 

Outputs and buzzer configuration

The instrument outputs can be configured by the relative 
parameters 

oo1

oo2

oo3

 and 

oo4

.  The outputs can be 

configured for the following functions:

ot

 

To control the temperature control device (e.g. Compres-
sor).  To manage the cooling control device for neutral 
zone control or Cooling (

rHC

 = 

nr

);

df

 

To control the defrosting device;

Fn

 

To control the evaporator fans;

Au

 

To control the auxiliary device;

At

 

To control a silenceable alarm device through a contact 
that is NO in normal operation then closed during the 
alarm;

AL

 

To control an alarm that cannot be silenced through 
a contact that is NO in normal operation then closed 
during the alarm;

An

 

To control an alarm with a memory function through 

Содержание e34B

Страница 1: ...g the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to obtain energy savings f...

Страница 2: ...el of the parameters Pressed together with the key for 5 s allows the keyboard unlock 5 LED dp Stand by During the normal operation is the decimal point when the instrument is placed in Stand by mode...

Страница 3: ...d is correct the instrument displays the code of the first parameter and it will be possible to program the in strument in the same way described in the previous section The password protection can be...

Страница 4: ...yable variable and its value So with the keys keys you can view all the variables pr1 Probe Pr1 temperature measurement Pr2 Probe Pr3 temperature measurement Pr3 Probe Pr3 temperature measurement Lt M...

Страница 5: ...nt con nection inside housing it is not equipped with either switches or internal devices to protect against current overloads the installation will include an overload protection and a two phase circ...

Страница 6: ...ng Elapsed the itt time after the door has been closed and from the activation of SPE Setpoint Eco mode by iEt parameter Eco Normal switching To use this function it is necessary to set the Digital In...

Страница 7: ...delayed for the time programmed with parameter iti The iFi parameter can be configured for the following functions 0 Digital input not active 1 Cell door opening with NO contact at input closure and...

Страница 8: ...ration can be used as a control of the shop window lighting anti fogging resistors or other utilities If present the internal buzzer can be configured by param eter obu for the following functions oF...

Страница 9: ...tions are disabled if the relative parameters are set to OFF oF 5 8 Defrost control The defrost control acts on the outputs configured as ot dF ad dH The type of defrost is set by the parameter ddt EL...

Страница 10: ...y occur with normal op eration when to ensure more system efficiency the defrost ing interval is programmed with a time that is often too short With the parameter ddd Defrost interval percentage reduc...

Страница 11: ...fine the display behaviour during defrost on The ddL parameter locks the display at the last Pr1 temperature reading during all the defrost cycle until at the end of defrost the temperature has not re...

Страница 12: ...l the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory oo1 oo2 oo3 oo4 An n it is necessary to set the parameter AtA on 5 10 1 Tempera...

Страница 13: ...g 200 V off off off ON ON HU LU AL 10 V 10 V Volt time V 5 11 Function of keys and The key function can be defined using the tUF param eter to perform the following functions oF The key carries out no...

Страница 14: ...perature measured by the Pr1 probe using a 2 digit display Power supply TVR Y cable length 10 m max For more information see the user manual for the TVR Y device 6 4 RS485 Serial Interface with ARS1 D...

Страница 15: ...en Door with Fan Fn and Output ot Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF Di...

Страница 16: ...42 dEE Lengh of defrost cycle for evaporator probe error oF Function disabled 1 59 s 1 99 min 10 43 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 44 FtF...

Страница 17: ...tput function oF Function disabled 1 Control output ot delayed 2 Manual activation by key oF 69 otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 70 tUF Key Function oF No...

Страница 18: ...ust be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1...

Страница 19: ...ERING CODE MODEL e34B Instrument with mechanical keyboard e34NB Instrument with NFC technology and mechanical keyboard a POWER SUPPLY H 100 240 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 R Relay SPST NO 16A AC...