Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 17
Parameter
Description
Range
Def.
Note
59
AtA
Alarms memory
oF
Alarm memory disabled;
on
Alarm memory enabled;
oF
60
APA
Temperature Alarms delay at power ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
2
61
AdA
Temperature Alarms delay after defrost and
unlock display delay after defrost
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1
62
AoA
Open Door Alarm Delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3
63
oo1
OUT1 function
oF
No function;
ot
Temperature control (compressor);
dF
Defrost;
Fn
Fans;
Au
Auxiliary;
At/-t
Silenceable alarm;
AL/-L
Not silenceable Alarm;
An/-n
Stored Alarm;
on
ON when the instrument is ON;
HE
Heating (Neutral zone control)
L1
Showcase light with ECO function (ON with
SP
, OFF with
SPE
);
L2
Interior light (OFF with door closed, lit with door open);
dH
Pre and post defrost resistance output.
ot
64
oo2
OUT2 function
dF
65
oo3
OUT3 function
Fn
66
oo4
OUT4 function
L1
67
obu
Buzzer function mode
oF
Function disabled;
1
Active for alarms only;
2
Active for key pressed only;
3, 4
Active for alarms and key pressed.
3
68
oFo
Auxiliary output function
oF
Function disabled;
1
Control output
ot
delayed;
2
Manual activation by key.
oF
69
otu
Time relative to auxiliary output
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
70
tUF
/
Key Function
oF
No function;
1
Eco Mode direct selection
(+ turn OFF the showcase light, if configured);
2
Switch ON/Switch OFF (Stand-by) the controller.
1
71
tFb
/
Key Function
oF
No function;
1
Enable key to control the light (
L1
and
Au
with
Fo
=
2
).
1
72
tLo
Keyboard lock function delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
73
tEd
Set Point change procedure
0
Disabled;
1
Active Set Point Direct change between limits
SH
...
SE
;
2
Active Set Point Direct selection between SP1, SP2 and SP3
with
and
keys.
2
74
tPP
Password to Access Parameter set up
oF
Function disabled;
001 ÷ 999.
oF
75
tas
Seroal Communications Address
0 ÷ 255.
1
76
tdu
Filter to suppress the display of increasing temperature
variations lower than 0.1°
oF
Function disabled;
0.1 ÷ 20.0 s
oF
77
tdd
Filter to suppress the display of decreasing temperature
variations lower than 0.1°
oF
Function disabled;
0.1 ÷ 20.0 s
oF
78
ULU
Low mains alarm
oF
Function disabled;
9 ÷ 27 (V x 10).
oF
79
UHU
High Mains alarm
oF
Function disabled;
9 ÷ 27 (V x 10).
oF
80
UUd
Mains alamrs delay
oF
Function disabled;
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
81
UOU
Mains Voltage calibration
-30 ÷ 30 V
0