Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 16
Parameter
Description
Range
Def.
Note
30
ddL
Display Lock during defrost
oF
Not active;
on
Active at last measure;
Lb
Active with label (
dEF
during defrost and
at defrost).
oF
31
dcd
Defrost activation time for continuous compressor
operating
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
oF
32
dde
Max. defrost duration
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
20
33
ddp
Pre-defrost time length for
dH
output
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
34
dpd
Post-defrost time length for
dH
output
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
35
dtd
Compressor delay after defrost (drainage time)
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min)
20
36
ddt
Defrosting Type
EL
Electrical heating/stop compressor;
in
Hot gas/reverse cycle;
no
Without compressor output condictioning;
Et
Electrical heating with evaporator temperature control.
EL
37
ddC
Defrosting starting mode
rt
Real time intervals;
ct
ot
output on time intervals;
cS
Defrost every
ot
switching OFF (+
rt
intervals);
cL
Do not use.
rt
38
ddi
Defrosting interval
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
39
dSd
Delay first defrost after power-on
oF
Defrost at power-on;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
40
ddd
Dynamic Defrost Percentage reduction
0 ÷ 100%
0
41
dEi
Defrosting interval for evaporator probe error
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
6
42
dEE
Lengh of defrost cycle for evaporator probe error
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
10
43
Ftn
Fan time activation with
ot
output (compressor)
OFF
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
5
44
FtF
Fan time deactivation with
ot
output (compressor)
OFF
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
45
FFL
High temperature fan deactivation
- 99.9 ÷ 999 °C/°F
10.0
46
FLF
Low temperature fan deactivation
- 99.9 ÷ 999°C/°F
-99.9
47
FdF
Differential fan control
0.0 ÷ 30.0°C/°F
1.0
48
FFE
Fan status during defrost
oF - on
oF
49
FFd
Fan delay after defrost
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
50
PP1
ot
output delay at switching
ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
51
PP2
ot
output delay after switching
OFF
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
52
PP3
Min. time between two
ot
output switching
ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
53
Pod
Outputs delay at power
ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
54
AAy
Temperature Alarm 1 type
1
Absolute for
Pr1
with label
Hi
or
Lo
;
2
Relative to
Pr1
with label
Hi
or
Lo
;
3
Absolute for
Au
with label
Hi
or
Lo
;
4
Relative to
Au
with label
Hi
or
Lo
;
5
Absolute for
Pr1
with no label;
6
Relative to
Pr1
with no label;
7
Absolute for
Au
with no label;
8
Relative to
Au
with no label.
1
55
AHA
High temperature Alarm threshold
oF
Function disabled;
-99.9 ÷ +999°C/°F.
oF
56
ALA
Low temperature Alarm threshold
oF
Function disabled;
-99.9 ÷ +999°C/°F
oF
57
AAd
Temperature Alarms Differential
0.0 ÷ 30.0°C/°F
1.0
58
AAt
Temperature Alarms Delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF