Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 15
7. PROGRAMMABLE PARAMETERS TABLE
Here below is a description of all the parameters available on the instrument. Some of them may not be present, either due
to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.
Parameter
Description
Range
Def.
Note
1
SPH
Turbo Set Point (min. SP or Heating SP HC mode)
-99.9 ÷ SPE
-5.0
2
SPE
Eco Set Point
S.PH ÷ 999
10.0
3
SP1
Set Point 1
SPH ÷ SPE
4.0
4
SP2
Set Point 2
SPH ÷ SPE
2.0
5
SP3
Set Point 3
SPH ÷ SPE
0.0
6
iuP
Unit of measurement and resolution (decimal point)
C0
°C, resolution 1°;
F0
°F, resolution 1°;
C1
°C, resolution 0.1°;
F1
°F, resolution 0.1°.
C1
7
iFt
Measurement filter
oF
Not used;
0.1 ÷ 20.0 s
2.0
8
iC1
Pr1 Probe Calibration (temperature control)
-30.0 ÷ +30.0°C/°F
0.0
9
iC2
Pr2 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
10
iC3
Pr3 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
11
iCU
Display offset
-30.0 ÷ +30.0°C/°F
0.0
12
iP2
Input Pr2 usage
oF
Unused;
EP
Evaporator probe;
Au
Auxliary probe;
dG
Digital Input.
dG
13
iP3
Input Pr3 usage
dG
14
iFi
Function and logic functioning of the Digital Input
(adding the “-” minus sign the logic is inverted)
0
No function;
1
Open Door;
2
Open Door with Fan (Fn) Lock;
3
Open Door with Fan (Fn) and Output (ot) Lock;
4
External Alarm;
5
External alarm with control output disabling;
6
Normal/Eco select;
7
On/Stand by select;
8
Start a Turbo cycle.
2
15
iti
Digital Input Delay
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
16
iEt
Eco Mode activation delay at Door closed
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
2
17
itt
Max. time functioning in Eco Mode
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
18
idS
Variable normally displayed
P1
Probe Pr1 measure;
P2
Probe Pr2 measure;
P3
Probe Pr3 measure;
Ec
Measure
Pr1
in Normal mode,
ECO
label when in ECO mode;
SP
Active Set Point;
oF
Display not lit.
P1
19
rd
Differential (Hysteresis) in normal mode
0.0 ÷ 30.0°C/°F
2.0
20
rEd
Differential (Hysteresis) in ECO mode
0.0 ÷ 30.0°C/°F
4.0
21
rHd
Differential (Hysteresis) in Turbo mode or Heating in
HC mode
0.0 ÷ 30.0°C/°F
2.0
22
rt1
Output activation time for Pr1 probe error
oF
Disabled;
-1 ÷ -59 (s) 1 ÷ 99 (min).
oF
23
rt2
Output deactivation time for Pr1 probe error
oF
Disabled;
-1 ÷ -59 (s) 1 ÷ 99 (min).
oF
24
rHC
Output(s) operating mode
H
Heating;
C
Cooling;
nr
Neutral zone;
HC
Neutral Zone with independent Set Point;
C3
Cooling with3 automatic switch modes.
C
25
rtC
Lengh of Turbo cycle
oF
Function disabled;
-1 ÷ -59 (min) 1 ÷ 99 (h).
1
26
dtE
Defrost stop temperature
-99.9 ÷ +999°C/°F
8.0
27
dtS
Defrost enable temperature
-99.9 ÷ +999°C/°F
2.0
28
dtF
Defrost start temperature
-99.9 ÷ +999°C/°F
-99.9
29
dSt
Delay start Defrost by
dtF
start temperature
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min)
1