Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 2

The 

4 outputs

 can be used to 

control the compressor

 or the 

temperature control device

, the 

defroster

, the 

evaporator 

fans

 and a 

configurable auxiliary device

 (Light, Alarm, etc.).

The 

3 inputs for temperature probes

 can be used for the 

cell temperature control

, to measure the 

evaporator tem-

perature

 and/or other 

auxiliary temperatures

 (e.g. products 

temperature, condenser temperature, etc.).
The 

digital input

, alternative to the 

Pr3

 probe, can be config-

ured to 

perform various functions

 such as: cell gate signal, 

defrost commands, selection of a different set of temperature 
control, signaling of an external alarm, activation of a continu-
ous cycle, activation of the auxiliary output etc..
The operating parameters configuration can be made through 
the 

keypad

, through the 

A01

 device connected to the TTL 

port (standard) or using the 

NFC

 communication (optional).

1.2 

Front panel pescription

e34B

P

U

trb

4

2

1

5

9

7

8

10

6

3

/

:

 Pressed for about 1 s enables the 

ECO

 function 

or turns the instrument ON/OFF (Stand-by).  The function 
selection is made with 

tUf

 parameter.  Pressed for 5 s 

together with the 

/  key, allows to access to the param-

eter programming mode.  Pressed for 5 s together with the 

/  key allows to access the variable display mode.  In 

programming mode it is used to return to normal operation;

/

:

 In normal mode, pressed an released allows to 

access the direct Set Point selection/change modality.  
Pressed for 5 s can be used to start/stop manual defrost 
cycle ( ).  In programming mode and in variable display 
mode is used to select the parameters and to increase 
the value to be set.  In programming mode can be used 
together with 

/  key to change parameters level.  

When the keyboard is locked, the keys 

/  and 

/  

used together (hold pressed for 5 s), unlock the keyboard.

/  

turbo

:

 In normal mode, pressed an released al-

lows to access the direct Set Point selection/change 
modality.  Pressed for 5 s can be used to start/stop a 
control cycle with “

turbo

” modality (

)

.  In programming 

mode and in variable display mode is used to select the 
parameters and to increase the value to be set.

/ :

 Pressed for about 1 s enables/disables the output 

selected as “

Light

”.  The function selection is made with 

tfb

 

parameter.  Pressed for 5 s together with the 

/  key, 

allows to access to the parameter programming mode.  
In programming mode is used to enter in parameters 
edit mode and confirm the entered values.  In program-
ming mode 

 can be used together with the 

/  key 

to change the programming level of the parameters.  
Pressed together with the 

/  key for 5 s allows the 

keyboard unlock.

5  LED dp/Stand-by:

 During the normal operation is the 

decimal point, when the instrument is placed in Stand-
by mode, this is the only lighted LED.  In programming 
mode, while the parameter code is displayed, the dot 
indicates the parameter protection level: 

not protected 

(lit up), 

protected

 (flashing) and 

hidden

 (turned OFF).

6  LED 

: Indicates the output status (compressor or 

temperature control device) when the instrument 
is programmed for 

cooling operation

ON

 (lit up), 

OFF

 (turned OFF) or 

inhibited

 (flashing).

7  LED  :

 Indicates the output status (compressor or temper-

ature control device) when the instrument is programmed 
for 

heating operation

ON

 (lit), 

OFF

 (turned OFF) or 

inhib-

ited

 (flashing).

8  LED  :

 Indicates the 

alarm status

ON

 (lit), 

OFF

 (turned OFF) or 

silenced or stored

 (flashing).

9  LED  :

 Indicates that the 

defrost

 is 

in progress

 (on) or 

drainage time in progress

 (flashing).

10  LED  :

 Indicates 

fan

 output status 

ON

 (on), 

OFF

 (off) 

or 

inhibited

 (flashing).

2.  PROGRAMMING

2.1 

Fast Normal Set Point Programming

The instrument allows, through the 

tEd

 parameter, to man-

age the selection of the regulation Set point according to two 
distinct  modes.
Setting 

tEd

 =

1

 the instrument allows the 

SP1 

Set Point set-

ting inside the limits inserted with 

SPH

 and 

SPE

 parameters.

Using this method, press and release the 

 or 

 key, the 

controller anwers showing the 

SP1

 active, at this point, using 

the 

 and 

 keys is possible to change the SP2 value to 

the desired one.  Once the desired value has been selected, 
press the 

/

 

key or wait 10 s after which the instrument 

makes the new set Point value active and the display returns 
to the normal operating mode.

Max. = 

spE

 value

ECO SET (e.g. 10°)

Min. = 

spH

 value

Turbo SET (e.g. -10°)

Increase

value

Decrease

value

-2.0

tEd

 = 1 mode

Set Point programming

Setting 

tEd

 = 

2

, the controller allows to select which of the 3 

pre-set Set Points (

SP1

SP2

SP3

) is to be set to active.  In 

this mode, pressing and releasing the ss / dd key the instru-
ment shows the active Set Point (

SP1

SP2

SP3

) alternatedto 

its value, pressing the 

/

 keys again it will be possible to 

select which one of the three is to be activated.  Once the de-
sired Set Point has been activated, press the 

/

 

key or wait 

10 s after which the instrument makes the selected Set Point 
active and the display returns to the normal operating mode.

sp1

 (e.g. 4.0°)

sp2

 (e.g. 2.0°)

Increase

selection

Decrease

selection

sp2

tEd

 = 2 mode

Set Point selection

sp3

 (e.g. 0.0°)

Note: 

The use of the device with 

tEd

 = 

2

 is the most practi-

cal and simple for the end user who, with the opera-
tions illustrated below, can easily select, as the active, 
one among the 4/5 preset Set Point temperatures (

SPE

SP1

SP2

 , 

SP3

 and 

SPH

).

Содержание e34B

Страница 1: ...g the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to obtain energy savings f...

Страница 2: ...el of the parameters Pressed together with the key for 5 s allows the keyboard unlock 5 LED dp Stand by During the normal operation is the decimal point when the instrument is placed in Stand by mode...

Страница 3: ...d is correct the instrument displays the code of the first parameter and it will be possible to program the in strument in the same way described in the previous section The password protection can be...

Страница 4: ...yable variable and its value So with the keys keys you can view all the variables pr1 Probe Pr1 temperature measurement Pr2 Probe Pr3 temperature measurement Pr3 Probe Pr3 temperature measurement Lt M...

Страница 5: ...nt con nection inside housing it is not equipped with either switches or internal devices to protect against current overloads the installation will include an overload protection and a two phase circ...

Страница 6: ...ng Elapsed the itt time after the door has been closed and from the activation of SPE Setpoint Eco mode by iEt parameter Eco Normal switching To use this function it is necessary to set the Digital In...

Страница 7: ...delayed for the time programmed with parameter iti The iFi parameter can be configured for the following functions 0 Digital input not active 1 Cell door opening with NO contact at input closure and...

Страница 8: ...ration can be used as a control of the shop window lighting anti fogging resistors or other utilities If present the internal buzzer can be configured by param eter obu for the following functions oF...

Страница 9: ...tions are disabled if the relative parameters are set to OFF oF 5 8 Defrost control The defrost control acts on the outputs configured as ot dF ad dH The type of defrost is set by the parameter ddt EL...

Страница 10: ...y occur with normal op eration when to ensure more system efficiency the defrost ing interval is programmed with a time that is often too short With the parameter ddd Defrost interval percentage reduc...

Страница 11: ...fine the display behaviour during defrost on The ddL parameter locks the display at the last Pr1 temperature reading during all the defrost cycle until at the end of defrost the temperature has not re...

Страница 12: ...l the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory oo1 oo2 oo3 oo4 An n it is necessary to set the parameter AtA on 5 10 1 Tempera...

Страница 13: ...g 200 V off off off ON ON HU LU AL 10 V 10 V Volt time V 5 11 Function of keys and The key function can be defined using the tUF param eter to perform the following functions oF The key carries out no...

Страница 14: ...perature measured by the Pr1 probe using a 2 digit display Power supply TVR Y cable length 10 m max For more information see the user manual for the TVR Y device 6 4 RS485 Serial Interface with ARS1 D...

Страница 15: ...en Door with Fan Fn and Output ot Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF Di...

Страница 16: ...42 dEE Lengh of defrost cycle for evaporator probe error oF Function disabled 1 59 s 1 99 min 10 43 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 44 FtF...

Страница 17: ...tput function oF Function disabled 1 Control output ot delayed 2 Manual activation by key oF 69 otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 70 tUF Key Function oF No...

Страница 18: ...ust be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1...

Страница 19: ...ERING CODE MODEL e34B Instrument with mechanical keyboard e34NB Instrument with NFC technology and mechanical keyboard a POWER SUPPLY H 100 240 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 R Relay SPST NO 16A AC...

Страница 20: ...Ascon Tecnologic e34B OPERATING INSTRUCTIONS PAG 20...

Отзывы: