Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 1

B05B

DIGITAL ELECTRONIC 

TEMPERATURE CONTROLLER 

WITH DEFROSTING FUNCTION

OPERATING INSTRUCTIONS

22/01 - Code: ISTR_M_B05B_E_03_--

ASCON TECNOLOGIC S.rl.

Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY 
Tel.:  +39 0381 69871 - Fax: +39 0381 698730 

http:\\www.ascontecnologic.com

 

[email protected]

PREFACE

 

D

This manual contains the information necessary for 
the product to be installed correctly and also instruc-
tions for its maintenance and use; we therefore recom-
mend that the utmost attention is paid to the following 
instructions and to save it

This document is the exclusive property of Ascon Tecnologic 
S.rl. which forbids any reproduction and divulgation, even 
partially, of the document, unless expressly authorized.
Ascon Tecnologic S.rl. reserves the right to make any formal 
or functional changes at any moment and without  any notice.
Ascon Tecnologic S.rl. and its legal representatives do not 
assume any responsibility for any damage to people, things 
or animals deriving from violation, wrong or improper use or 
in any case not in compliance with the instrument features.

 

D

Whenever a failure or a malfunction of the device 
may cause dangerous situations for persons, thing 
or animals, please remember that the plant has to be 
equipped with additional electromechanical devices 
which will guarantee safety.

1.  INSTRUMENT DESCRIPTION

1.1 

General description

The controller 

B05B

 (Supply and control unit) connected to the 

P03CB

 or 

P34B

 Display unit is a 

digital controller system

 

with microprocessor that is typically 

used

 in 

cooling applica-

tions

 that have 

ON/OFF temperature control

 and 

defrost 

control

 at 

time intervals

, by 

reaching the temperature

 or 

continuous time compressor operating

 through s

topping 

the compressor

electric heating

 or 

hot gas/cycle inversion

.

The appliance has 

special defrosting optimisation func-

tions 

and 

other functions

 to 

reduce the amount of en-

ergy used

 by the controlled system.

The system can 

have up to 4 relay outputs

 and 

up to 

5 inputs

3

 configurable 

for NTC

 temperature 

probes

, and 

Index

1.  Instrument description ............................................... 1

1.1  General description ........................................................... 1
1.2  HMI front panel description ............................................... 2
1.3  B05B Control Unit description ........................................... 
3

2. Programming ............................................................... 3

2.1  Fast programming of “Normal” Set Point ........................... 3
2.2  Standard mode parameters programming ........................ 3
2.3  Parameter protection using the password ......................... 
4
2.4  Customized mode parameter programming  

(parameters programming level) ....................................... 4

2.5  Reset parameters to default value .................................... 4
2.6  Keyboard lock function ...................................................... 4
2.7  Variables display ............................................................... 
5

3.  Usage warnings ........................................................... 5

3.1  Admitted use ..................................................................... 5

4.  Installation warnings ................................................... 5

4.1  Mechanical mounting [mm] ............................................... 5
4.2  Mechanical dimensions ..................................................... 6
4.3  Electrical connections ....................................................... 6

5. Functions ..................................................................... 7

5.1  ON/Stand-by function ........................................................ 7
5.2  Normal, Economic and Turbo operation ............................ 7
5.3  Measure and display configuration ................................... 8
5.4  Digital input configuration .................................................. 9
5.5  Outputs and Buzzer configuration ..................................... 9
5.6  Temperature control ........................................................ 10
5.7  Compressor protection functions and power-on delay .... 11
5.8  Defrost control ................................................................. 11
5.9  Evaporator fans control ................................................... 13
5.10  Alarm functions ............................................................... 14
5.11  Function of keys 

/

 and 

/

 ................................ 15

6. Accessories ............................................................... 16

6.1  Parameters configuration by “A01” .................................. 16
6.2  TVR Y remote display ..................................................... 16
6.3  ARS1 Serial Interface ..................................................... 16

7.  Programmable parameters table .............................. 17
8.  Problems and maintenance ...................................... 22

8.1 Notifications .................................................................... 22
8.2 Cleaning .......................................................................... 22
8.3 Disposal .......................................................................... 22

9.  Warranty and Repairs ............................................... 22
10. Technical data ............................................................ 22

10.1  Electrical characteristics ................................................. 22
10.2  Mechanical characteristics .............................................. 22
10.3  Functional features ......................................................... 23

11. Instrument Ordering Code ........................................ 23

11.1  B05B Instrument Code.................................................... 23
11.2  P03CB Display Unit Code ............................................... 23
11.3  P34B Display Unit Code ................................................. 23

Содержание B05B

Страница 1: ...ng the temperature or continuous time compressor operating through stopping the compressor electric heating or hot gas cycle inversion The appliance has special defrosting optimisation func tions and...

Страница 2: ...n be used to start stop a manual defrost In parameter programming or variables display mode is used for selecting the parameters and for increas ing the values to be set In programming mode if pressed...

Страница 3: ...is possible to select which Set Point is to be set as active S1 S2 S3 Once selected the active Set Point press the key or wait 10 s after which the instrument makes the selected Set Point active and...

Страница 4: ...pro tected if instead the SET LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and while keeping it pressed press also t...

Страница 5: ...ut adequate protections The instrument used with NTC 103AT11 probe identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring t...

Страница 6: ...igher than the maximum electricity current permitted As the instrument is built in equipment with permanent con nection inside housing it is not equipped with either switches or internal devices to pr...

Страница 7: ...d With the key pressed for 1 s if UF 2 Using a Digital Input if parameter oF 7 where o is the number of the digital input o 1 4 for P03 or o 2 4 for P34 5 2 Normal Economic and Turbo operation The con...

Страница 8: ...oods temperature recovery after which it returns to normal operation mode and so on Temp SE SP SH Hd Ed tt 2 tC tC time Normal Turbo Turbo Et 1 d Pr1 1 The Et time count is reset at each door opening...

Страница 9: ...nstrument alternately displays the label AL and the variable set at parameter dS 6 Normal ECO mode selection with NO contact at digital input closure the instrument switches to the ECO mode operation...

Страница 10: ...d the key pressed 5 6 Temperature control All parameters relative to the temperature control are con tained in the re group The instrument control is ON OFF and acts on the ot and HE outputs depending...

Страница 11: ...urned ON last time delay between two switching ON off off off ON S1 Temp time d P3 P3 P3 ot output ON ON Pr1 During the output inhibition the LED of the control output blinks It is also possible to pr...

Страница 12: ...rrectly set it is possible to avoid many non necessary defrosting cycles and therefore save energy that could instead happens in normal operation when to guar antee the system efficiency the interval...

Страница 13: ...mperature has not reached the lock value or the SP d value or is elapsed the time set at parameter dA dL Lb Shows the label dF during the defrost cycle and Pd after the defrost until at the end of def...

Страница 14: ...rms and their differentials 1d 2d With parameters 1y and 2y it is also possible to define whether the alarm thresholds 1H 2H 1L 2L are absolute or relative to the Set Point Depending on the desired op...

Страница 15: ...to disable the control outputs when the main voltage is lower or higher than the values set at parameters LU Low voltage Alarm expressed in Volt x 10 HU High voltage Alarm expressed in Volt x 10 At th...

Страница 16: ...remote display To the instrument it is possible to connect the remote display TVR Y through the special cable that can have a maximum length of 10 m The TVR Y device is directly supplied by the instru...

Страница 17: ...C F 0 0 11 CU 280C Measure offset display only 30 0 30 0 C F 30 9 9 9 9 30 C F 0 0 12 P2 280D Probe Pr2 input function 0 oF 1 EP 2 Au 3 cd 4 r1 5 dG oF No function EP Evaporator Au Aux cd Condenser r1...

Страница 18: ...oF 30 tE 2820 Defrost stop temperature 99 9 999 0 C F 99 9 9 9 9 10 99 C F 8 0 31 Ei 2821 Defrost interval for evaporator probe error 0 oF 0 01 99 59 h min oF No interval 01 59 min 01 99 h 6 32 EE 28...

Страница 19: ...Description Range MODBUS R W Range display Default display Note 56 1y 283C Temperature alarms 1 Type 1 10 1 Pr1 absolute with label H L 2 Pr1 Relative with label H L 3 Au absolute with label H L 4 Au...

Страница 20: ...Au Auxiliary At Silenceable alarm AL Not silenceable Alarm An Stored alarm t Silenceable alarm with inverse logic Output open in alarm L Not silenceable Alarm with inverse logic Output open in alarm n...

Страница 21: ...SH and SE limits 2 Direct selection of Active Set Point between the 3 pre set Set Points S1 S2 and S3 using the keys 2 83 PP 285B Access Password to parameter functions 0 oF 1 99 oF No password 1 999...

Страница 22: ...e shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Elec...

Страница 23: ...ir S A 1 50 C 90 C with probe NTC 103AT11 11 INSTRUMENT ORDERING CODE 11 1 B05B Instrument Code MODEL B05B Controller a POWER SUPPLY H 100 230 VAC b OUTPUT 1 OUT 1 H Relay SPST NO 30A AC1 for resistiv...

Страница 24: ...Ascon Tecnologic B05B OPERATING INSTRUCTIONS PAG 24...

Отзывы: