Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 7

from line voltage wiring.  If the iprobes cables are shielded, the 
shield must to be connected to ground at only one side.

 

D

We recommend that a check should be made that the 
parameters are those desired and that the application 
functions correctly 

before connecting the outputs to 

the actuators

 so as to avoid malfunctioning that may 

cause irregularities in the plant that could cause dam-
age to people, things or animals.

4.3.1 

Electrical wiring diagram

Out 1 (H): 

30  (15) A 

6  (6) A 

6  A Res.

  

     96  LRA/16 FLA

Out 1 (R): 

16  (9) A 

6  (4) A 

6  A Res.

  

     30  LRA/5 FLA

Out 2: 

8  (3) A 

4  (4) A 

4  A Res.

Out 3, 4 (R):  5  (1) A 

1  (1) A 

1  A Res.

Out 3, 4 (Q):  0.1 A min. 0.5 A (max.) Res.

B05B

EN

61810

60730

EN

UL

Power Supply

100... 220 VAC

Pin 1 (com.)
12 A max.

C

7 8 9

10 11 12 13 14 15 16 17

TTL

AT LIN

M D+ +12V

Internal

Buzzer

Pr3

Pr1 Pr2

di3

di2

di4

3 2 1

4 5

M D+ +12V

di1

AT LIN

P03CB

AT LIN

cable

Internal

Buzzer

3

2

1

+12V D+ M

AT LIN

P34B

5.  FUNCTIONS

5.1 

ON/Stand-by function

Once powered the instrument can assume 2 different condi-
tions:

ON

:  Means that the controller uses the control functions.

STAND-BY:  

Means that the controller uses no control function and 
the display is turned off except for the Stand-by LED.

The transition between Standby and ON condition is equiva-
lent to power ON the instrument providing the electrical power.
In case of power failure, the system always sets itself in the 
condition it was in before the black-out.
The ON/Stand-by function can be selected:

 

With the key  /  pressed for 1 s if 

UF

 = 

2

;

 

Using a Digital Input if parameter 

o

F

 = 

7

 (where 

o

 is the 

number of the digital input: 

o

 = 1 ÷ 4 for P03 or  

o

 = 2 ÷ 4 for P34).

5.2 

Normal, Economic and Turbo operation

The controller allows to pre-set 5 different control Set Points:

S1

S2

S3

 are 

Normal

 Set Points,

SE

 is an 

Economic

 Set Point; 

SH

 is a 

Turbo

 Set Point.

Associated with each Setpoint there is the relative differential 
(hysteresis): 

Normal

 - 

d

Economic

 - 

Ed

 and 

Turbo

 - 

Hd

.

As explained at paragraph “

2.1 Fast programming of normal Set 

Point

”, the operative 

Normal

 Set Point is 

only 1

, in particular: 

S1

 if 

Ed

 = 

1

 

or selectable between: 

S1

S2

S3

 pre-set values if 

Ed

 = 

2

.

Note: 

In the examples that follow, the Set Point is generi-
cally indicated as 

S1

, but the instrument controls the 

process using the active Set Point.

5.2.1 

Normal/Economic operation selection

This function can be used if it is necessary to switch two func-
tional temperatures (eg. Day/Night or week-day/week-end).  The 
Normal/Economic operation can be selected in manual mode:

 

Using the  /  key if parameter 

UF

 = 

2

;

 

Using a Digital Input if parameter 

o

F

 = 

6

 (

o

 = DI #).

The Normal/Economic operation can be selected in automatic 
mode:

 

Elapsed the 

Et

 time after the door has been closed 

(Normal/Eco switching).

 

At door opening if the Eco function is active (Eco/Normal 
switching).

 

Elapsed the 

tt

 time after the door has been closed and 

from the activation of Eco function (Eco/Normal switching).

Temp.

SE

SP

Out

(L1)

Door

d

Ed

Et

time

“Norm.”

DAY (Shop open)

“Norm.”

off

ON

ON

Pr1

NIGHT Shop closed)

DAY (Shop open)

Example of automatic ECO - Normal switching mode.  Dur-
ing the 

business hours

, when the door is opened frequently 

and the controller remains in 

Normal

 mode.  After the 

Et

 

Содержание B05B

Страница 1: ...ng the temperature or continuous time compressor operating through stopping the compressor electric heating or hot gas cycle inversion The appliance has special defrosting optimisation func tions and...

Страница 2: ...n be used to start stop a manual defrost In parameter programming or variables display mode is used for selecting the parameters and for increas ing the values to be set In programming mode if pressed...

Страница 3: ...is possible to select which Set Point is to be set as active S1 S2 S3 Once selected the active Set Point press the key or wait 10 s after which the instrument makes the selected Set Point active and...

Страница 4: ...pro tected if instead the SET LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and while keeping it pressed press also t...

Страница 5: ...ut adequate protections The instrument used with NTC 103AT11 probe identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring t...

Страница 6: ...igher than the maximum electricity current permitted As the instrument is built in equipment with permanent con nection inside housing it is not equipped with either switches or internal devices to pr...

Страница 7: ...d With the key pressed for 1 s if UF 2 Using a Digital Input if parameter oF 7 where o is the number of the digital input o 1 4 for P03 or o 2 4 for P34 5 2 Normal Economic and Turbo operation The con...

Страница 8: ...oods temperature recovery after which it returns to normal operation mode and so on Temp SE SP SH Hd Ed tt 2 tC tC time Normal Turbo Turbo Et 1 d Pr1 1 The Et time count is reset at each door opening...

Страница 9: ...nstrument alternately displays the label AL and the variable set at parameter dS 6 Normal ECO mode selection with NO contact at digital input closure the instrument switches to the ECO mode operation...

Страница 10: ...d the key pressed 5 6 Temperature control All parameters relative to the temperature control are con tained in the re group The instrument control is ON OFF and acts on the ot and HE outputs depending...

Страница 11: ...urned ON last time delay between two switching ON off off off ON S1 Temp time d P3 P3 P3 ot output ON ON Pr1 During the output inhibition the LED of the control output blinks It is also possible to pr...

Страница 12: ...rrectly set it is possible to avoid many non necessary defrosting cycles and therefore save energy that could instead happens in normal operation when to guar antee the system efficiency the interval...

Страница 13: ...mperature has not reached the lock value or the SP d value or is elapsed the time set at parameter dA dL Lb Shows the label dF during the defrost cycle and Pd after the defrost until at the end of def...

Страница 14: ...rms and their differentials 1d 2d With parameters 1y and 2y it is also possible to define whether the alarm thresholds 1H 2H 1L 2L are absolute or relative to the Set Point Depending on the desired op...

Страница 15: ...to disable the control outputs when the main voltage is lower or higher than the values set at parameters LU Low voltage Alarm expressed in Volt x 10 HU High voltage Alarm expressed in Volt x 10 At th...

Страница 16: ...remote display To the instrument it is possible to connect the remote display TVR Y through the special cable that can have a maximum length of 10 m The TVR Y device is directly supplied by the instru...

Страница 17: ...C F 0 0 11 CU 280C Measure offset display only 30 0 30 0 C F 30 9 9 9 9 30 C F 0 0 12 P2 280D Probe Pr2 input function 0 oF 1 EP 2 Au 3 cd 4 r1 5 dG oF No function EP Evaporator Au Aux cd Condenser r1...

Страница 18: ...oF 30 tE 2820 Defrost stop temperature 99 9 999 0 C F 99 9 9 9 9 10 99 C F 8 0 31 Ei 2821 Defrost interval for evaporator probe error 0 oF 0 01 99 59 h min oF No interval 01 59 min 01 99 h 6 32 EE 28...

Страница 19: ...Description Range MODBUS R W Range display Default display Note 56 1y 283C Temperature alarms 1 Type 1 10 1 Pr1 absolute with label H L 2 Pr1 Relative with label H L 3 Au absolute with label H L 4 Au...

Страница 20: ...Au Auxiliary At Silenceable alarm AL Not silenceable Alarm An Stored alarm t Silenceable alarm with inverse logic Output open in alarm L Not silenceable Alarm with inverse logic Output open in alarm n...

Страница 21: ...SH and SE limits 2 Direct selection of Active Set Point between the 3 pre set Set Points S1 S2 and S3 using the keys 2 83 PP 285B Access Password to parameter functions 0 oF 1 99 oF No password 1 999...

Страница 22: ...e shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Elec...

Страница 23: ...ir S A 1 50 C 90 C with probe NTC 103AT11 11 INSTRUMENT ORDERING CODE 11 1 B05B Instrument Code MODEL B05B Controller a POWER SUPPLY H 100 230 VAC b OUTPUT 1 OUT 1 H Relay SPST NO 30A AC1 for resistiv...

Страница 24: ...Ascon Tecnologic B05B OPERATING INSTRUCTIONS PAG 24...