Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 21
-ts
Keyboard Configuration and Serial Communications Parameters Group
Parameter Hex.
address
Description
Range MODBUS
R/W
Range
(display)
Default
(display) Note
79
UF
2857 Function mode
/
key
0 oF
1 ÷ 2
oF No function;
1 Direct Eco mode Selection
(+ if configured shop light power OFF);
2 Switch on/off (Stand-by).
1
80
Fb
2858 Function mode
/
key
0 oF
1
oF No function;
1 Enable
for Light command
(
L1
and
Au
with
Fo
=
2
).
1
81
Lo
2859 Automatic keyboard lock function
delay
0 oF
0.01 ÷ 29.59 (min.s)
30
dc
Keyboard lock at
door closed
oF
Disabled
-01 ÷ -59 (s) ÷ 01 ÷ 29 (min)
30
dc
Keyboard lock at door closed
oF
82
Ed
285A Set Point change
0 oF
1 ÷ 2
oF None;
1 Direct selection of
P1
Set Point value
between SH and SE limits;
2 Direct selection of Active Set Point between
the 3 pre-set Set Points (
S1
,
S2
and
S3
)
using the
/
keys
.
2
83
PP
285B Access Password to parameter
functions
0 oF
1 ÷ 99
oF No password;
1 ÷ 999
oF
84
AS
285D MODBUS address (for serial
communications)
0 oF
1 ÷ 99
oF Not used;
1 ÷ 255
1
85
du
285E Display delay when
Pr1
temperature
increases by 0.1°
0 oF
1 ÷ 25.5 s
0 No delay
0.1 ÷ 9.9 ÷ 25 s
oF
86
dd
285F Display delay when Pr1 temperature
decreases by 0.1°
0 oF
1 ÷ 25.5 s
0 No delay
0.1 ÷ 9.9 ÷ 25 s
oF
-UA
Mains Alarm Configuration Parameters Group
Parameter Hex.
address
Description
Range MODBUS
R/W
Range
(display)
Default
(display) Note
87
LU
287D Low voltage alarm
8 oF
9 ÷ 27 V x 10
0 Alarm disabled
9 ÷ 27 V x 10
oF
88
HU
287E High voltage alarm
8 oF
9 ÷ 27 V x 10
0 Alarm disabled
9 ÷ 27 V x 10
oF
89
Ud
287F Voltage alarms delay
0 (oF) / 0.01 ÷ 99.59 (min.s)
0 No delay
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
90
OU
2880 Voltage calibration
-30 ÷ 30 V
-30 ÷ 30 V
0.0