Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 20
Parameter Hex.
address
Description
Range MODBUS
R/W
Range
(display)
Default
(display) Note
69
2A
2849 Alarms H2 e L2 actions
0 ÷ 3
See
62
(
1A
) parameter options
1
70
dA
284A Temperature Alarms 1 delay after defrost, and
unlock display delay after defrost
0 oF
0.01 ÷ 99.59 (h.min)
0 No delay
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
1
71
oA
284B Alarm delay with door open
0 oF
0.01 ÷ 99.59 (min.s)
0 Not active
-01 ÷ -59 (min) ÷ 01 ÷ 99 (h)
3
-ou
Outputs Configuration Parameters Group
Parameter Hex.
address
Description
Range MODBUS
R/W
Range
(display)
Default
(display) Note
72
o1
2850 OUT1 function
0 = oF
1 = ot
2 = dF
3 = Fn
4 = Au
5 = At
6 = AL
7 = An
8 = -t
9 = -L
10 = -n
11 = on
12 = HE
13 = 2d
14 = L1
15 = L2
16 = -d
oF No function;
ot Temperature control (compressor);
dF Defrosting;
Fn Fan;
Au Auxiliary;
At Silenceable alarm;
AL Not silenceable Alarm;
An Stored alarm;
-t Silenceable alarm with inverse logic (Output open in alarm);
-L Not silenceable Alarm with inverse logic (Output open in alarm);
-n Stored alarm with inverse logic (Output open in alarm);
on ON when instrument switch on;
HE Heating (Neutral zone control);
2d Not used;
L1 Light with economy mode (on with
SP
and off with
SPE
);
L2 Internal light (off with door closed and on with door opened);
-dF Defrosting NC contact.
ot
73
o2
2851 OUT2 function
dF
74
o3
2852 OUT3 function
Fn
75
o4
2853 OUT4 function
L1
76
bu
2854 Buzzer function mode
0 oF
1 ÷ 4
oF Disable;
1 Active alarms only;
2 Key pressed only;
3 Active alarms and key pressed;
4 Active alarms (intermittent).
4
77
Fo
2855 Auxiliary output function
mode
0 oF
1 ÷ 2
oF No Function;
1
ot
control output delayed;
2 Manual activation by key or digital input.
oF
78
tu
2856 Time relative to auxiliary
output
0 oF
0.01 ÷ 99.59 (min.s)
oF Disable;
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF