Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 17
7. PROGRAMMABLE PARAMETERS TABLE
Here below is a description of all the parameters available on the instrument. Some of them may not be present, either due
to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.
-SP
Set Point Parameters Group
Parameter Hex.
address
Description
Range MODBUS
R/W
Range
(display)
Default
(display) Note
1
SH
2800 Turbo Set Point (min. Set Point) and
Heating Set Point (in HC mode)
-99 ÷ HS
-5.0
2
SE
2801 ECO Set Point (max. Set Point)
LS ÷ 99
10
3
S1
2802 Set Point 1
SE ÷ SH
4.0
4
S2
2803 Set Point 2
SE ÷ SH
2.0
5
S3
2804 Set Point 3
SE ÷ SH
0.0
-In
Digital Input Parameters Group
Parameter Hex.
address
Description
Range MODBUS
R/W
Range
(display)
Default
(display) Note
6
uP
2806 Mesurement unit and resolution
(decimal point position)
0 = C0
1 = F0
2 = C1
3 = F1
C0 °C with resolution 1°;
F0 °F with resolution 1°;
C1 °C with resolution 0.1°;
F1 °F with resolution 0.1°.
C1
7
Ft
2807 Measurement filter
oF OFF
0.1 ÷ 9.9 ÷ 20 s
2.0
8
C1
2808 Probe
Pr1
Calibration (control)
-30.0 ÷ 30.0°C/°F
-30 ÷ -9.9 ÷ 9.9 ÷ 30°C/°F
0.0
9
C2
2809 Probe
Pr2
Calibration
-30.0 ÷ 30.0°C/°F
-30 ÷ -9.9 ÷ 9.9 ÷ 30°C/°F
0.0
10
C3
280A Probe
Pr3
Calibration
-30.0 ÷ 30.0°C/°F
-30 ÷ -9.9 ÷ 9.9 ÷ 30°C/°F
0.0
11
CU
280C Measure offset (display only)
-30.0 ÷ 30.0°C/°F
-30 ÷ -9.9 ÷ 9.9 ÷ 30°C/°F
0.0
12
P2
280D Probe
Pr2
input function
0 = oF
1 = EP
2 = Au
3 = cd
4 = r1
5 = dG
oF No function;
EP Evaporator;
Au Aux;
cd Condenser ;
r1 Control Probe;
dG digital input.
EP
13
P3
280E Probe
Pr3
input function
oF
14
1F
2810
DI1
digital input function and logic function
(not present in the P34 display panel)
-14 ÷ 14
0 No function;
1 Door open;
2 Door open with fan stop;
3 Door open with fan and compressor stop;
4 External
AL
alarm;
5 External
AL
alarm with control outputs stop;
6 Selection of active Set Point (SP-SPE);
7 Switch ON/OFF (Stand - by);
8
Turbo
cycle activation;
9 Remote command of
AUX
output;
10 Not used;
11 Not used;
12 External
Pr
alarm;
13 External
HP
alarm;
14 External
LP
alarm.
0
15
1t
2811 Delay in acquiring
DI1
digital input
0 oF
0.01 ÷ 99.59 (min. s)
oF No delay
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
16
2F
2812
DI2
digital input function and logic function -14 ÷ 14
See
14
(
1F
) parameter options
0
17
2t
2813 Delay in acquiring
DI2
digital input
0 oF
0.01 ÷ 99.59 (min. s)
oF No delay
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
18
3F
2814
DI3
digital input function and logic function -14 ÷ 14
See
14
(
1F
) parameter options
0
19
4F
2815
DI4
digital input function and logic function -14 ÷ 14
See
14
(
1F
) parameter options
2
20
Et
2816 Delay to
Eco
mode with door closed
0 oF
0.01 ÷ 99.59 (h. min)
oF No delay
-01 ÷ -59 (min) ÷ 01 ÷ 99 (h)
02
21
tt
2817 Time-out
Eco
mode
0 oF
0.01 ÷ 99.59 (h. min)
oF No time-out
-01 ÷ -59 (min) ÷ 01 ÷ 99 (hrs)