background image

Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 9

SP

 

Active Set Point;

Ec

 

Probe 

Pr1

 measurement when the instrument is in Nor-

mal mode and the 

Ec

 label only when is in 

Eco

 mode;

F1

 The 

Pr1

 probe measurement 

filtered

 through param-

eters 

dd

 and 

du

;

oF

 

Numeric display OFF.

If one of the measurements (

dS

 = 

P1

P2

P3

Ec

F1

) is dis-

played, parameter 

CU

 allows to set an offset that is to be applied 

to the variable display only (all adjustment controls will always 
be in accordance with the correct calibration parameter).
Regardless of what set at parameter 

DS

, all the instrument 

variables can be displayed as explained at paragraph “

2.7 - 

Variables display

”.

Note: 

The Pr1 probe display can also be changed by the de-
frost display lock function set with parameter 

DL

 (see 

the “

Defrost

” function).

5.4 

Digital input configuration

All the parameters for configuring the digital inputs are con-
tained in the 

-In

 group.

The 

P03 operator panel

 has 1 digital input (

DI1

) for free of 

voltage contacts whose function is defined by parameter 

1F

 

and whose action is delayed by the time set at parameter 

1t

.

The 

P34 operator panel

 has no digital input on-board.

The 

B05 controller

 always has a digital inputs (

DI4

) whose 

function is defined by parameter 

4F

.  The B05 controller can 

also have 2 more digital inputs for free of voltage contacts 
(

DI2

 and 

DI3

) as an alternative to 

Pr2

 and 

Pr3

 probe inputs.

To use these inputs as digital ones, their relative param-
eters 

P2

 or 

P3

 must be set to 

dG

 (

P2

/

P3

 = 

dG

).  The function 

performed by these inputs configured as digital is defined by 
parameters 

2F

 and 

3F

.

The 

DI2

 action can be delayed by parameter 

2t

, while the ac-

tion of 

DI3

 and 

DI4

 is instantaneous and can not be delayed.

The function performed by the instrument at 

DI

o

 activation is 

set through parameters 

1F

2F

3F

4F

:

0. 

Digital input not active;

1. 

Cell door opening with NO contact: at input closure the 
instrument displays alternately 

oP

 and the variable set at 

dS

 parameter.  With this mode of operation, the digital in-

put activates also the time set with parameter 

oA

 elapsed 

which the alarm is activated to warn that the door has 
been left open.  In addition, at door opening, the instru-
ment returns to 

Normal

 operation if it was in 

Eco

 mode.

2. 

Cell door opening with NO contact similar to 

o

F

 = 

1

, but with 

evaporator fans lock.  At the intervention of the 

Open Door 

Alarm

 (

oA

), the 

evaporator fans

 are powerd 

ON

 again.

3. 

Cell door opening with NO contact similar to 

o

F

 = 

1

, but 

with compressor and evaporator fans lock.  At the inter-
vention of the 

Open Door Alarm

 (

oA

), the 

evaporator 

fans

 and the 

compressor

 are powerd 

ON

 again.

4. 

External alarm signal with NO contact: at digital input 
closure the alarm is activated, the instrument alternately 
displays 

AL

 and the variable set at parameter 

dS

;

5. 

External alarm signal with control outputs disabling 
(except alarm and light outputs) by NO contact: at digital 
input closure the the control outputs are disabled, the 
alarm is activated and the instrument alternately displays 
the label 

AL

 and the variable set at parameter 

dS

;

6. 

Normal/ECO mode selection with NO contact: at digital 
input closure the instrument switches to the 

ECO

 mode 

operation.  When the Digital Input is open, the instrument 
is in 

Normal

 operation mode;

7. 

Instrument Switching ON/OFF (Stand-by) by NO contact: 
at digital input closure the instrument is switched ON 
while it is placed in Stand-by when the contact is open;

8.  Turbo

 cycle activation command with NO contact: at 

digital input closure the instrument starts a 

turbo

 cycle;

9. 

Remote command of auxiliary output (

AUX

) with NO 

contact: at digital input closure the instrument activates 
the auxiliary output as described in the 

Fo

 = 

2

 operating 

mode of the auxiliary output;

10, 11

 - Not used;

12. 

External 

Pr

 alarm with 

ot

 output disabling with NO con-

tact: at digital input closure the output set as 

ot

 is disa-

bled, the alarm is enabled and the instrument alternately 
displays the label 

PA

 and the variable set at parameter 

dS

;

13. 

External 

Hp

 alarm with 

ot

 output disabling with NO con-

tact: at digital input closure the output set as 

ot

 is disa-

bled, the alarm is enabled and the instrument alternately 
displays the label 

HP

 and the variable set at parameter 

dS

;

14. 

External 

lp

 alarm with 

ot

 output disabling with NO con-

tact: at digital input closure the output set as 

ot

 is disa-

bled, the alarm is enabled and the instrument alternately 
displays the label 

lP

 and the variable set at parameter 

dS

;

-1, -2, -3, etc.

 - Features identical to the above but obtained 

through a NC contact and a reversed logic operation.

Note: 

Where multiple digital inputs are configured for the 
same function, the instrument will treat the contacts 
as if they were parallel (and consequently regard the 
result as an 

OR

 function)

5.5 

Outputs and Buzzer configuration

All the parameters for configuring the instrument ouputs are 
contained in the 

-Ou

 group.

The instrument outputs can be configured by the relative 
parameters 

o1

o2

o3

o4

.

The outputs can be configured for the following functions:

ot

 

To control the temperature control device (e.g. the 
compressor).  In the case of neutral zone control  
(

HC

 = 

nr

) to control the 

cooling

 device;

dF

 

To control the defrosting device;

Fn

 

To control the evaporator fans;

Au

 

To control the auxiliary device;

At

 

To control an alarm that can be acknowledged, the 
output contact is normally open and closed in alarm;

AL

 

To control an alarm that cannot be acknowledged, the 
output contact is normally open and closed in alarm;

An

   To control a latched alarm, the output contact is nor-

mally open and closed in alarm;

-t

 

To control an acknowledgeable alarm device, the out-
put contact is normally closed and open in alarm;

-L

 

To control an alarm that cannot be acknowledged, the 
output contact is normally closed and open in alarm;

-n

   To control a latched alarm, the output contact is nor-

mally closed and open in alarm;

On

 

To control a device that must be ON when the instru-
ment is in ON state.  The output is therefore disabled 
when the instrument is not powered or is in stand-by 
status.  This mode can be used to control the shop win-
dow lights, the anti fogging resistance or other utilities;

Содержание B05B

Страница 1: ...ng the temperature or continuous time compressor operating through stopping the compressor electric heating or hot gas cycle inversion The appliance has special defrosting optimisation func tions and...

Страница 2: ...n be used to start stop a manual defrost In parameter programming or variables display mode is used for selecting the parameters and for increas ing the values to be set In programming mode if pressed...

Страница 3: ...is possible to select which Set Point is to be set as active S1 S2 S3 Once selected the active Set Point press the key or wait 10 s after which the instrument makes the selected Set Point active and...

Страница 4: ...pro tected if instead the SET LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and while keeping it pressed press also t...

Страница 5: ...ut adequate protections The instrument used with NTC 103AT11 probe identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring t...

Страница 6: ...igher than the maximum electricity current permitted As the instrument is built in equipment with permanent con nection inside housing it is not equipped with either switches or internal devices to pr...

Страница 7: ...d With the key pressed for 1 s if UF 2 Using a Digital Input if parameter oF 7 where o is the number of the digital input o 1 4 for P03 or o 2 4 for P34 5 2 Normal Economic and Turbo operation The con...

Страница 8: ...oods temperature recovery after which it returns to normal operation mode and so on Temp SE SP SH Hd Ed tt 2 tC tC time Normal Turbo Turbo Et 1 d Pr1 1 The Et time count is reset at each door opening...

Страница 9: ...nstrument alternately displays the label AL and the variable set at parameter dS 6 Normal ECO mode selection with NO contact at digital input closure the instrument switches to the ECO mode operation...

Страница 10: ...d the key pressed 5 6 Temperature control All parameters relative to the temperature control are con tained in the re group The instrument control is ON OFF and acts on the ot and HE outputs depending...

Страница 11: ...urned ON last time delay between two switching ON off off off ON S1 Temp time d P3 P3 P3 ot output ON ON Pr1 During the output inhibition the LED of the control output blinks It is also possible to pr...

Страница 12: ...rrectly set it is possible to avoid many non necessary defrosting cycles and therefore save energy that could instead happens in normal operation when to guar antee the system efficiency the interval...

Страница 13: ...mperature has not reached the lock value or the SP d value or is elapsed the time set at parameter dA dL Lb Shows the label dF during the defrost cycle and Pd after the defrost until at the end of def...

Страница 14: ...rms and their differentials 1d 2d With parameters 1y and 2y it is also possible to define whether the alarm thresholds 1H 2H 1L 2L are absolute or relative to the Set Point Depending on the desired op...

Страница 15: ...to disable the control outputs when the main voltage is lower or higher than the values set at parameters LU Low voltage Alarm expressed in Volt x 10 HU High voltage Alarm expressed in Volt x 10 At th...

Страница 16: ...remote display To the instrument it is possible to connect the remote display TVR Y through the special cable that can have a maximum length of 10 m The TVR Y device is directly supplied by the instru...

Страница 17: ...C F 0 0 11 CU 280C Measure offset display only 30 0 30 0 C F 30 9 9 9 9 30 C F 0 0 12 P2 280D Probe Pr2 input function 0 oF 1 EP 2 Au 3 cd 4 r1 5 dG oF No function EP Evaporator Au Aux cd Condenser r1...

Страница 18: ...oF 30 tE 2820 Defrost stop temperature 99 9 999 0 C F 99 9 9 9 9 10 99 C F 8 0 31 Ei 2821 Defrost interval for evaporator probe error 0 oF 0 01 99 59 h min oF No interval 01 59 min 01 99 h 6 32 EE 28...

Страница 19: ...Description Range MODBUS R W Range display Default display Note 56 1y 283C Temperature alarms 1 Type 1 10 1 Pr1 absolute with label H L 2 Pr1 Relative with label H L 3 Au absolute with label H L 4 Au...

Страница 20: ...Au Auxiliary At Silenceable alarm AL Not silenceable Alarm An Stored alarm t Silenceable alarm with inverse logic Output open in alarm L Not silenceable Alarm with inverse logic Output open in alarm n...

Страница 21: ...SH and SE limits 2 Direct selection of Active Set Point between the 3 pre set Set Points S1 S2 and S3 using the keys 2 83 PP 285B Access Password to parameter functions 0 oF 1 99 oF No password 1 999...

Страница 22: ...e shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Elec...

Страница 23: ...ir S A 1 50 C 90 C with probe NTC 103AT11 11 INSTRUMENT ORDERING CODE 11 1 B05B Instrument Code MODEL B05B Controller a POWER SUPPLY H 100 230 VAC b OUTPUT 1 OUT 1 H Relay SPST NO 30A AC1 for resistiv...

Страница 24: ...Ascon Tecnologic B05B OPERATING INSTRUCTIONS PAG 24...

Отзывы: