Installing the switch
|
64
2. Secure the wall anchors to the wall and install the countersunk head M4 screws and washers.
3. Ensure that the ports are facing down.
Supported walls: Concrete (cemented) or Plywood ¾” thick.
JL818A can only be wall mounted with the ports facing downward.
Two-post Rack Mount Option
The switch is designed to be mounted in any EIA-standard 19-inch telco rack or communication equipment
cabinet using the rack mount bracket.
For safe operation, please review the mounting precautions in
Installation Precautions and Guidelines
, before
mounting a switch.
For rack mounting, do not physically stack equipment on top of another. Ensure an air gap of at least 2U. If only 1U
or 1.75 in. (44.5 mm) of air gap is available, do not exceed 60 degrees Celsius (140 degrees Fahrenheit) ambient
temperature.