Installing the switch
|
44
The unit is protected with internal fuse (not replaceable) at L pin and it has been tested and approved on 20 (UL)
and 16A (IEC) branch circuits without additional protection device. An external protection device is only required if
the supplying branch has an ampacity greater than above.
1. Identify the wire location for N, L, and PE.
2. Using a wire stripping tool, strip each of the wires leaving 7 mm exposed.
3. Fully insert the wires into the connecting terminal block connectors.
4. Using a ratcheting torque screwdriver, torque the terminal block connector captive screw to
4.67kg.cm (4.05lb in).