AXP640 Shelf Installation
AXP640 Installation and Use (6806800M24F
)
114
5.3
Installation Prerequisites
This section describes the prerequisites required for installation.
5.3.1
Equipment You Will Need
You will need the following to install the AXP640 six-slot shelf into an approved EIA 23" or
600mm x 600mm ETSI frame:
Torque wrench
Nut driver with 7/16mm socket
Multimeter
Phillips head screwdriver, #1
Front mounting brackets for an EIA 23" frame
5.3.2
Rack/Cabinet Cooling Guidelines
It is important to have sufficient open space at the front and rear of the shelf when installed in
a rack or cabinet. Depending on whether the enclosure has solid or vented doors will determine
the recommended open space required. Follow these guidelines for positioning the shelf to
allow for the optimal open space for the shelf air inlet and shelf air exhaust.
Do not obstruct the ventilation openings at the top, sides and back of the shelf.
Rack Mounting:
Per ETSI 600mm x 600mm ETSI frame on integrated front frame mounting
ears.
Frame mounting brackets are required for a 23" EIA frame. Rear mounting
brackets are recommended in both instances for Central Office
Environment.
Each shelf requires 7U of space and effectively takes up 7U when mounted in
a rack.
Cable management trays are available for the front and the rear of the shelf.
Table 5-1 AXP640 Shelf Physical Characteristics (continued)
Characteristics
Specifications
Содержание AXP640
Страница 1: ...AXP640 Installation and Use P N 6806800M24F May 2014 ...
Страница 8: ...AXP640 Installation and Use 6806800M24F Contents 8 Contents Contents ...
Страница 10: ...AXP640 Installation and Use 6806800M24F 10 List of Tables ...
Страница 50: ...Platform Architecture AXP640 Installation and Use 6806800M24F 50 ...
Страница 53: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 53 Figure 2 2 DC Rear Shelf View ...
Страница 69: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 69 Figure 2 13 AC Inlet Markings 110V ...
Страница 70: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 70 Figure 2 14 AC Inlet 220V ...
Страница 77: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 77 Figure 2 18 DC Rating Label ...
Страница 78: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 78 Figure 2 19 AC Rating Label ...
Страница 90: ...Site Preparation AXP640 Installation and Use 6806800M24F 90 Figure 3 2 ETSI Frame Mount Rear View ...
Страница 91: ...Site Preparation AXP640 Installation and Use 6806800M24F 91 Figure 3 3 ETSI Frame Mount Side View ...
Страница 92: ...Site Preparation AXP640 Installation and Use 6806800M24F 92 Figure 3 4 19 inch Frame Front Mount Front View ...
Страница 93: ...Site Preparation AXP640 Installation and Use 6806800M24F 93 Figure 3 5 19 inch Frame Mid mount Front View ...
Страница 94: ...Site Preparation AXP640 Installation and Use 6806800M24F 94 Figure 3 6 19 23 inch Frame Mid mount Side View ...
Страница 95: ...Site Preparation AXP640 Installation and Use 6806800M24F 95 Figure 3 7 23 inch Frame Front Mount Front View ...
Страница 101: ...Site Preparation AXP640 Installation and Use 6806800M24F 101 Figure 3 13 Planning Checklist 2 ...
Страница 102: ...Site Preparation AXP640 Installation and Use 6806800M24F 102 ...
Страница 112: ...AXP640 Operations AXP640 Installation and Use 6806800M24F 112 ...
Страница 136: ...AXP640 Shelf Installation AXP640 Installation and Use 6806800M24F 136 ...
Страница 164: ...FRU Installation AXP640 Installation and Use 6806800M24F 164 ...
Страница 186: ...Shelf Management Alarm Module AXP640 Installation and Use 6806800M24F 186 ...
Страница 189: ......